summaryrefslogtreecommitdiff
path: root/MIBS/emerson/EES-POWER-MIB
blob: b8bb824597fc21dbed14aec4f265c35ead03e2a1 (plain)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
696
697
698
699
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717
718
719
720
721
722
723
724
725
726
727
728
729
730
731
732
733
734
735
736
737
738
739
740
741
742
743
744
745
746
747
748
749
750
751
752
753
754
755
756
757
758
759
760
761
762
763
764
765
766
767
768
769
770
771
772
773
774
775
776
777
778
779
780
781
782
783
784
785
786
787
788
789
790
791
792
793
794
795
796
797
798
799
800
801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827
828
829
830
831
832
833
834
835
836
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
871
872
873
874
875
876
877
878
879
880
881
882
883
884
885
886
887
888
889
890
891
892
893
894
895
896
897
898
899
900
901
902
903
904
905
906
907
908
909
910
911
912
913
914
915
916
917
918
919
920
921
922
923
924
925
926
927
928
929
930
931
932
933
934
935
936
937
938
939
940
941
942
943
944
945
946
947
948
949
950
951
952
953
954
955
956
957
958
959
960
961
962
963
964
965
966
967
968
969
970
971
972
973
974
975
976
977
978
979
980
981
982
983
984
985
986
987
988
989
990
991
992
993
994
995
996
997
998
999
1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
1011
1012
1013
1014
1015
1016
1017
1018
1019
1020
1021
1022
1023
1024
1025
1026
1027
1028
1029
1030
1031
1032
1033
1034
1035
1036
1037
1038
1039
1040
1041
1042
1043
1044
1045
1046
1047
1048
1049
1050
1051
1052
1053
1054
1055
1056
1057
1058
1059
1060
1061
1062
1063
1064
1065
1066
1067
1068
1069
1070
1071
1072
1073
1074
1075
1076
1077
1078
1079
1080
1081
1082
1083
1084
1085
1086
1087
1088
1089
1090
1091
1092
1093
1094
1095
1096
1097
1098
1099
1100
1101
1102
1103
1104
1105
1106
1107
1108
1109
1110
1111
1112
1113
1114
1115
------------------------------------------------------------
-- Emerson Energy Systems (EES)
-- Power MIB
------------------------------------------------------------

EES-POWER-MIB DEFINITIONS ::= BEGIN


IMPORTS
	MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
	Integer32, Counter32, enterprises
		FROM SNMPv2-SMI
	TEXTUAL-CONVENTION, DisplayString, DateAndTime
		FROM SNMPv2-TC;
		
		
powerMIB MODULE-IDENTITY
	LAST-UPDATED "201504100857Z"
	ORGANIZATION "
		Emerson Energy Systems (EES)"
	CONTACT-INFO "
		Emerson Energy Systems
		141 82 Stockholm
		Sweden"
	DESCRIPTION "
		Emerson Energy Systems (EES) Power MIB, revision D."
	::= { enterprises 6302 2 1 }

------------------------------------------------------------
-- Node definitions
------------------------------------------------------------

ees OBJECT IDENTIFIER ::= { enterprises 6302 }

global OBJECT IDENTIFIER ::= { ees 2 }

------------------------------------------------------------
-- Textual conventions
------------------------------------------------------------

Status ::= TEXTUAL-CONVENTION
	STATUS current
	DESCRIPTION "
		This integer value represents the operational or administrative
		status of the system. Also used as alarm severity.
		Depending on situation there may be limits on allowed values.
		Operational values:
		(1) unknown - status has not yet been defined
		(2) normal - there are no activated alarms
		(3) warning - OA, lowest level of 'abnormal' status
		(4) minor - A3
		(5) major - MA
		(6) critical - CA, highest level of 'abnormal' status
		Administrative values:
		(7) unmanaged
		(8) restricted
		(9) testing
		(10) disabled"
	SYNTAX INTEGER {
		unknown(1),
		normal(2),
		warning(3),
		minor(4),
		major(5),
		critical(6),
		unmanaged(7),
		restricted(8),
		testing(9),
		disabled(10) }

StatusChange ::= TEXTUAL-CONVENTION
	STATUS current
	DESCRIPTION "
		Indicates 'activated' (1) or 'deactivated' (2) alarm events."
	SYNTAX INTEGER {
		activated(1),
		deactivated(2) }


------------------------------------------------------------
-- 1.1 Identification of the plant { powerMIB 1 }
------------------------------------------------------------

ident OBJECT IDENTIFIER ::= { powerMIB 1 }

identManufacturer OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The name of the equipment manufacturer."
	::= { ident 1 }

identModel OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The manufacturers model designation of the power system."
	::= { ident 2 }

identControllerFirmwareVersion OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The firmware (software) version of the controller."
	::= { ident 3 }

identName OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-write
	STATUS current
	DESCRIPTION "
		The name of the power plant. This object should be set by
		the administrator."
	::= { ident 4 }

identSNMPCfgVer OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The snmp cfg version"
	::= { ident 5 }
	
identControllerSerialNumber OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The serial number of this controller"
	::= { ident 6 }	
	
------------------------------------------------------------
-- 1.2 System values { powerMIB 2 }
------------------------------------------------------------

system OBJECT IDENTIFIER ::= { powerMIB 2 }

systemStatus OBJECT-TYPE
	SYNTAX Status
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Status of the complete plant (highest alarm). One of
		(1) unknown - status has not yet been defined
		(2) normal - there are no activated alarms
		(3) warning - OA, lowest level of 'abnormal' status
		(4) minor - A3
		(5) major - MA
		(6) critical - CA, highest level of 'abnormal' status
		(7) unmanaged
		(8) restricted
		(9) testing
		(10) disabled"
	::= { system 1 }

systemVoltage OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		System voltage, stored as mV, including positive or negative
		sign. The integer 2147483647 represents invalid value."
	::= { system 2 }

systemCurrent OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		System current, stored as mA, including positive or negative
		sign. The integer 2147483647 represents invalid value."
	::= { system 3 }

systemUsedCapacity OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Used capacity, stored as % of the total capacity.
		The integer 2147483647 represents invalid value."
	::= { system 4 }



-- ------------------------------------------------------------------------ 
-- 1.2.5. Battery group
-- ------------------------------------------------------------------------ 

psBattery OBJECT IDENTIFIER ::= { system 5 }

    psBatteryVoltage OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Battery voltage, stored as mV, including positive or negative
		sign. The integer 2147483647 represents invalid value."
        ::= { psBattery 1 }
    
    psTotalBatteryCurrent OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Battery current, stored as mA, including positive or negative
		sign. The integer 2147483647 represents invalid value."
        ::= { psBattery 2 }

	psBatteryCapacity OBJECT-TYPE
		SYNTAX Integer32
		MAX-ACCESS read-only
		STATUS current
		DESCRIPTION "
			Calculated capacity, stored as % of the total capacity.
			The integer 2147483647 represents invalid value."
		::= { psBattery 3 }

	psBatteryNominalCapacity OBJECT-TYPE
		SYNTAX Integer32
		MAX-ACCESS read-only
		STATUS current
		DESCRIPTION "
			nominal installed capacity, stored as mAh.
			The integer 2147483647 represents invalid value."
		::= { psBattery 4 }

    psBatteryTable OBJECT-TYPE
        SYNTAX SEQUENCE OF PSBatteryEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION     
                "Battery Table."
    ::= { psBattery 5 }
    
    psBatteryEntry OBJECT-TYPE
        SYNTAX PSBatteryEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
            "Battery Measurement Table Entry."
        INDEX { psBatteryIndex }
    ::= { psBatteryTable 1 }

    PSBatteryEntry ::= SEQUENCE {
        psBatteryIndex              Integer32,
        psBatteryCurrent         	Integer32,
        psBatteryName		  		DisplayString
    }

    psBatteryIndex OBJECT-TYPE
        SYNTAX		  Integer32(1..16777215)
        MAX-ACCESS              read-only
        STATUS                  current
        DESCRIPTION
                "Automatically generated index object."
    ::= { psBatteryEntry 1 }

    psBatteryCurrent OBJECT-TYPE
        SYNTAX 		  Integer32
        MAX-ACCESS              read-only
        STATUS                  current
        DESCRIPTION
                "Battery current in Amps."
    ::= { psBatteryEntry 2 }

    psBatteryName OBJECT-TYPE
        SYNTAX 		  DisplayString
        MAX-ACCESS              read-only
        STATUS                  current
        DESCRIPTION
                "Battery shunt name."
    ::= { psBatteryEntry 3 }


-- ------------------------------------------------------------------------ 
-- 1.2.6. the psInput group
-- ------------------------------------------------------------------------ 

psInput OBJECT IDENTIFIER ::= { system 6 }

    psInputLineAVoltage OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The AC line A voltage, stored as mV. The integer 2147483647 
		represents invalid value."
        ::= { psInput 1 }

    psInputLineBVoltage OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The AC line B voltage, stored as mV. The integer 2147483647 
		represents invalid value."
        ::= { psInput 2 }

    psInputLineCVoltage OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The AC line C voltage, stored as mV. The integer 2147483647 
		represents invalid value."
        ::= { psInput 3 }

-- ------------------------------------------------------------------------ 
-- 1.2.7. the temperatures
-- ------------------------------------------------------------------------ 

psTemperature OBJECT IDENTIFIER ::= { system 7 }

    psTemperature1 OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The first route temperature, stored as 0.001 Celsius degree. 
		The integer 2147483647 represents invalid value."
        ::= { psTemperature 1 }

    psTemperature2 OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The second route temperature, stored as 0.001 Celsius degree. 
		The integer 2147483647 represents invalid value.."
        ::= { psTemperature 2 }


    psTemperatureTable OBJECT-TYPE
        SYNTAX SEQUENCE OF PSTemperatureEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION     
                "Temperature Measurement Table."
    ::= { psTemperature 3 }
    
    psTemperatureEntry OBJECT-TYPE
        SYNTAX PSTemperatureEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
            "Temperature Measurement Table Entry."
        INDEX { psTemperatureIndex }
    ::= { psTemperatureTable 1 }

    PSTemperatureEntry ::= SEQUENCE {
        psTemperatureIndex               Integer32,
        psTemperatureMeasurement         Integer32,
        psTemperatureName                DisplayString,
        psTemperatureType                INTEGER,	
        psTemperatureAlarmStatus         INTEGER
    }

    psTemperatureIndex OBJECT-TYPE
        SYNTAX Integer32(1..71)
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Temperature Probe Number "
    ::= { psTemperatureEntry 1 }

    psTemperatureMeasurement OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Temperature Value In Centigrade."
    ::= { psTemperatureEntry 2 }

    psTemperatureName OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Configured Temperature Probe Name."
    ::= { psTemperatureEntry 3 }

    psTemperatureType OBJECT-TYPE
        SYNTAX INTEGER { 
        none(0), 
        ambient(1), 
        battery(2) 
        }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Temperature Probe Type "
    ::= { psTemperatureEntry 4 }

    psTemperatureAlarmStatus OBJECT-TYPE
        SYNTAX INTEGER { 
        high(0), 
        low(1), 
        fail(2), 
        none(3) 
        }
        MAX-ACCESS                  read-only
        STATUS                  current
        DESCRIPTION
                "Temperature Probe Alarm Status "
    ::= { psTemperatureEntry 5 }

psStatusCommunication OBJECT-TYPE
        SYNTAX INTEGER {
            unknown(1),
            normal(2),
            interrupt(3)
        }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The status of communication with the Power System. interrupt(3) indicates
             some errors occurred between Power System and agent."
        ::= { system 8 }

psStatusBatteryMode OBJECT-TYPE
        SYNTAX INTEGER  {
	    unknown(1),
	    floatCharging(2),
	    shortTest(3),
	    bcForTest(4),
	    manualTesting(5),
	    planTesting(6),
	    acFailTesting(7),
	    acFail(8),
	    manualBC(9),
	    autoBC(10),
	    cyclicBC(11),
	    masterBC(12),
	    masterBT(13)
	}
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The status of battery modes, 
		FloatCharging(2),
		ShortTest(3),
		BoostChargingForTest(4),
		ManualTesting(5),
		PlanTesting(6),
		ACFailTesting(7),
		ACFail(8),
		ManualBoostCharging(9),
		AutoBoostCharging(10),
		CyclicBoostCharging(11),
		MasterBoostCharging(12),
		MasterBateryTesting(13)."
        ::= { system 9 }

-- ------------------------------------------------------------------------ 
-- 1.2.10. the SM series group(only get number of SM series)
-- ------------------------------------------------------------------------ 

psSMNumber OBJECT IDENTIFIER ::= { system 10 }

    psSMACNumber OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The number of SM AC module."
        ::= { psSMNumber 1 }

    psSMBATNumber OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The number of SM BAT module."
        ::= { psSMNumber 2 }

    psSMIONumber OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "The number of SM IO module."
        ::= { psSMNumber 3 }

-- ------------------------------------------------------------------------ 
-- 1.2.11. Rectifier group
-- ------------------------------------------------------------------------ 

psRectifier OBJECT IDENTIFIER ::= { system 11 }

numberOfInstalledRectifiers OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		number of rectifiers, stored as integer.
		The integer 2147483647 represents invalid value."
	::= { psRectifier 1 }

numberOfRectifiersCommunicating OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		number of rectifiers communicating, stored as integer.
		The integer 2147483647 represents invalid value."
	::= { psRectifier 2 }

rectifiersUsedCapacity OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Used capacity, stored as % of the total capacity.
		The integer 2147483647 represents invalid value."
	::= { psRectifier 3 }

psRectifierTable OBJECT-TYPE
	SYNTAX SEQUENCE OF PSRectifierEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION "
		Table holding information about indivual rectifiers."
	::= { psRectifier 4 }

psRectifierEntry OBJECT-TYPE
	SYNTAX PSRectifierEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION "
		An entry (conceptual row) in the rectifierInfoTable."
	INDEX { psRectifierIndex }
	::= { psRectifierTable 1 }

PSRectifierEntry ::= SEQUENCE {
	psRectifierIndex Integer32,
	psRectifierProductNumber DisplayString,
	psRectifierHWVersion DisplayString,
	psRectifierSWVersion DisplayString,
	psRectifierSerialNumber DisplayString,
	psRectifierCurrent Integer32,
	psRectifierIdent DisplayString,
	psRectifierFail StatusChange
	}

psRectifierIndex OBJECT-TYPE
  SYNTAX Integer32(1..16777215)
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION "Automatically generated index object."
::= { psRectifierEntry 1 }

psRectifierProductNumber OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Rectifier Product Number."
::= { psRectifierEntry 2}

psRectifierHWVersion OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Rectifier Hardware Revision."
::= { psRectifierEntry 3}

psRectifierSWVersion OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Rectifier Software Revision."
::= { psRectifierEntry 4}

psRectifierSerialNumber OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Rectifier Serial Number."
::= { psRectifierEntry 5}

psRectifierCurrent OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Rectifier Current."
::= { psRectifierEntry 6}

psRectifierIdent OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Rectifier physical location identifier."
::= { psRectifierEntry 7}

psRectifierFail OBJECT-TYPE
        SYNTAX StatusChange
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION "
	The type of alarm change. One of
	(1) activated
	(2) deactivated"
::= { psRectifierEntry 8}

-- ------------------------------------------------------------------------ 
-- 1.2.12. the Distribution
-- ------------------------------------------------------------------------ 

psDistribution OBJECT IDENTIFIER ::= { system 12 }

psTotalLoadCurrent OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Total Load current, stored as integer.
		The integer 2147483647 represents invalid value."
	::= { psDistribution 1 }
    psDistributionLoadTable OBJECT-TYPE
        SYNTAX SEQUENCE OF PSDistributionLoadEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION     
                "Distribution Table."
    ::= { psDistribution 2 }
    
    psDistributionLoadEntry OBJECT-TYPE
        SYNTAX PSDistributionLoadEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
            "Distribution Measurement Table Entry."
        INDEX { psDistributionLoadIndex }
    ::= { psDistributionLoadTable 1 }

    PSDistributionLoadEntry ::= SEQUENCE {
        psDistributionLoadIndex               Integer32,
        psDistributionLoadCurrent         	  Integer32,
        psDistributionLoadName		  DisplayString	
    }

    psDistributionLoadIndex OBJECT-TYPE
        SYNTAX		  Integer32(1..268386303)
        MAX-ACCESS              not-accessible
        STATUS                  current
        DESCRIPTION
                "Automatically generated index object."
    ::= { psDistributionLoadEntry 1 }

    psDistributionLoadCurrent OBJECT-TYPE
        SYNTAX 		  Integer32
        MAX-ACCESS              read-only
        STATUS                  current
        DESCRIPTION
                "Distribution current in Amps."
    ::= { psDistributionLoadEntry 2 }

    psDistributionLoadName OBJECT-TYPE
        SYNTAX 		  DisplayString
        MAX-ACCESS              read-only
        STATUS                  current
        DESCRIPTION
                "Distribution name."
    ::= { psDistributionLoadEntry 3 }

    psDistributionGeneralTable OBJECT-TYPE
        SYNTAX SEQUENCE OF PSDistributionGeneralEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION     
                "Distribution Table."
    ::= { psDistribution 3 }
    
    psDistributionGeneralEntry OBJECT-TYPE
        SYNTAX PSDistributionGeneralEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
            "Distribution Measurement Table Entry."
        INDEX { psDistributionGeneralIndex }
    ::= { psDistributionGeneralTable 1 }

    PSDistributionGeneralEntry ::= SEQUENCE {
        psDistributionGeneralIndex               Integer32,
        psDistributionGeneralCurrent         	  Integer32,
        psDistributionGeneralName		  DisplayString	
    }

    psDistributionGeneralIndex OBJECT-TYPE
        SYNTAX		  Integer32(1..268386303)
        MAX-ACCESS              not-accessible
        STATUS                  current
        DESCRIPTION
                "Automatically generated index object."
    ::= { psDistributionGeneralEntry 1 }

    psDistributionGeneralCurrent OBJECT-TYPE
        SYNTAX 		  Integer32
        MAX-ACCESS              read-only
        STATUS                  current
        DESCRIPTION
                "Distribution current in Amps."
    ::= { psDistributionGeneralEntry 2 }

    psDistributionGeneralName OBJECT-TYPE
        SYNTAX 		  DisplayString
        MAX-ACCESS              read-only
        STATUS                  current
        DESCRIPTION
                "Distribution name."
    ::= { psDistributionGeneralEntry 3 }

-- ------------------------------------------------------------------------ 
-- 1.2.13. Converter group
-- ------------------------------------------------------------------------ 

psConverter OBJECT IDENTIFIER ::= { system 13 }

numberOfInstalledConverters OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		number of converters, stored as integer.
		The integer 2147483647 represents invalid value."
	::= { psConverter 1 }

numberOfConvertersCommunicating OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		number of converters communicating, stored as integer.
		The integer 2147483647 represents invalid value."
	::= { psConverter 2 }

convertersUsedCapacity OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Used capacity, stored as % of the total capacity.
		The integer 2147483647 represents invalid value."
	::= { psConverter 3 }

psConverterVoltage OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Converter voltage in mV.
		The integer 2147483647 represents invalid value."
	::= { psConverter 4 }

psTotalConverterCurrent OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Total Converter current in Amps.
		The integer 2147483647 represents invalid value."
	::= { psConverter 5 }

psConverterTable OBJECT-TYPE
	SYNTAX SEQUENCE OF PSConverterEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION "
		Table holding information about indivual converters."
	::= { psConverter 6 }

psConverterEntry OBJECT-TYPE
	SYNTAX PSConverterEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION "
		An entry (conceptual row) in the ConverterInfoTable."
	INDEX { psConverterIndex }
	::= { psConverterTable 1 }

PSConverterEntry ::= SEQUENCE {
	psConverterIndex Integer32,
	psConverterProductNumber DisplayString,
	psConverterHWVersion DisplayString,
	psConverterSWVersion DisplayString,
	psConverterSerialNumber DisplayString,
	psConverterCurrent Integer32,
          psConverterIdent DisplayString,
          psConverterFail StatusChange	}

psConverterIndex OBJECT-TYPE
  SYNTAX Integer32(1..100)
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION "Automatically generated index object."
::= { psConverterEntry 1 }

psConverterProductNumber OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Converter Product Number."
::= { psConverterEntry 2}

psConverterHWVersion OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Converter Hardware Revision."
::= { psConverterEntry 3}

psConverterSWVersion OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Converter Software Revision."
::= { psConverterEntry 4}

psConverterSerialNumber OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Converter Serial Number."
::= { psConverterEntry 5}

psConverterCurrent OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Converter Current."
::= { psConverterEntry 6}

psConverterIdent OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
            "Converter physical location identifier."
::= { psConverterEntry 7}

psConverterFail OBJECT-TYPE
        SYNTAX StatusChange
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION "
	The type of alarm change. One of
	(1) activated
	(2) deactivated"
::= { psConverterEntry 8}

-- ------------------------------------------------------------------------ 
-- 1.2.14. Control group
-- ------------------------------------------------------------------------ 

psControl OBJECT IDENTIFIER ::= { system 14 }

controlBatteryTest OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-write
	STATUS current
	DESCRIPTION "
		Control battery test, start(1), stop (0)."
	::= { psControl 1 }

controlRelay8 OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-write
	STATUS current
	DESCRIPTION "
		Control relay8, close(1), open(0)."
	::= { psControl 2 }

controlRelay7 OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-write
	STATUS current
	DESCRIPTION "
		Control relay7, close(1), open(0)."
	::= { psControl 3 }

controlRelay6 OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-write
	STATUS current
	DESCRIPTION "
		Control relay6, close(1), open(0)."
	::= { psControl 4 }

controlRelayTest OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-write
	STATUS current
	DESCRIPTION "
		Control Relay test, start(1), stop (0)."
	::= { psControl 5 }


-- ------------------------------------------------------------------------ 
-- 1.2.15. EquipmentSignalTable
-- ------------------------------------------------------------------------ 

psEquipmentSignalTable OBJECT-TYPE
	SYNTAX SEQUENCE OF EquipmentSignalTableEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION "
		Table of indexed equipment signal values."
	::= { system 15 }

equipmentSignalTableEntry OBJECT-TYPE
	SYNTAX EquipmentSignalTableEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION "
		An entry (conceptual row) in the psEquipment Signal Table."
	INDEX { psEquipmentSignalTableEntryIndex }
	::= { psEquipmentSignalTable 1 }

EquipmentSignalTableEntry ::= SEQUENCE {
	psEquipmentSignalTableEntryIndex Integer32,
	psEquipmentSignalValue Integer32 }

psEquipmentSignalTableEntryIndex OBJECT-TYPE
	SYNTAX Integer32(1..268386303)
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The unique sequence number of this equipment signal."
	::= { equipmentSignalTableEntry 1 }

psEquipmentSignalValue OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Indexed equipment signal value."
	::= { equipmentSignalTableEntry 2 }

------------------------------------------------------------
-- Alarm trap counter { powerMIB 3 }
------------------------------------------------------------

alarmLastTrapNo OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The sequence number of last submitted alarm trap,
		also last row in alarmTrapTable."
	::= { powerMIB 3 }

------------------------------------------------------------
-- Active Alarm table { powerMIB 4 }
------------------------------------------------------------

alarmActiveAlarmTable OBJECT-TYPE
	SYNTAX SEQUENCE OF ActiveAlarmEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION "
		Table holding information about the currently active alarms."
	::= { powerMIB 4 }

activeAlarmEntry OBJECT-TYPE
	SYNTAX ActiveAlarmEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION "
		An entry (conceptual row) in the alarmTrapTable."
	INDEX { alarmIndex }
	::= { alarmActiveAlarmTable 1 }

ActiveAlarmEntry ::= SEQUENCE {
	alarmIndex Counter32,
	alarmTime DateAndTime,
	alarmStatusChange StatusChange,
	alarmSeverity Status,
	alarmDescription DisplayString,
	alarmType Integer32 }

alarmIndex OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The unique sequence number of this alarm trap."
	::= { activeAlarmEntry 1 }

alarmTime OBJECT-TYPE
	SYNTAX DateAndTime
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Date and time when event occured (local time), including
		timezone if supported by controller."
	::= { activeAlarmEntry 2 }

alarmStatusChange OBJECT-TYPE
	SYNTAX StatusChange
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The type of alarm change. One of
		(1) activated
		(2) deactivated"
	::= { activeAlarmEntry 3 }

alarmSeverity OBJECT-TYPE
	SYNTAX Status
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		The severity of the alarm. One of
		(3) warning - OA, lowest level of alarm severity
		(4) minor - A3
		(5) major - MA
		(6) critical - CA, highest level of alarm severity"
	::= { activeAlarmEntry 4 }

alarmDescription OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Free-text description of alarm."
	::= { activeAlarmEntry 5 }

alarmType OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION "
		Alarm type, i.e. an integer specifying the type of alarm."
	::= { activeAlarmEntry 6 }

------------------------------------------------------------
-- Events/traps { powerMIB 5 }
------------------------------------------------------------

powerEvents OBJECT IDENTIFIER ::= { powerMIB 5 }

alarmTrap NOTIFICATION-TYPE
	OBJECTS {
		alarmIndex,
		alarmTime,
		alarmStatusChange,
		alarmSeverity,
		alarmDescription,
		alarmType }
	STATUS current
	DESCRIPTION "
		An alarm trap is sent when an alarm occurs (activated) or
		returns to normal state (deactivated). Alarm traps are logged
		in alarmTrapTable. Variables in this trap:
		* alarmIndex - The unique sequence number of this alarm trap.
		* alarmTime - Date and time when event occured (local time),
		      including timezone if supported by controller.
		* alarmStatusChange - (1) activated or (2) deactivated.
		* alarmSeverity - Integer describing the severity of the alarm.
		* alarmDescription - Free-text description of alarm.
		* alarmType - Integer indicating type of alarm."
	::= { powerEvents 1 }

alarmActiveTrap NOTIFICATION-TYPE
	OBJECTS {
		alarmTime,
		alarmSeverity,
		alarmDescription,
		alarmType }
	STATUS current
	DESCRIPTION "
		An alarm trap is sent when an alarm occurs (activated)
		Variables in this trap
		* alarmTime - Date and time when event occured (local time),
		      including timezone if supported by controller.
		* alarmSeverity - Integer describing the severity of the alarm.
		* alarmDescription - Free-text description of alarm.
		* alarmType - Integer indicating type of alarm."
	::= { powerEvents 2 }

alarmCeaseTrap NOTIFICATION-TYPE
	OBJECTS {
		alarmTime,
		alarmSeverity,
		alarmDescription,
		alarmType }
	STATUS current
	DESCRIPTION "
		An alarm trap is sent when an alarm returns to normal state (clear, deactivated). 
                Variables in this trap:
		* alarmTime - Date and time when event occured (local time),
		      including timezone if supported by controller.
		* alarmSeverity - Integer describing the severity of the alarm.
		* alarmDescription - Free-text description of alarm.
		* alarmType - Integer indicating type of alarm."
	::= { powerEvents 3 }

------------------------------------------------------------
-- End of MIB definitions
------------------------------------------------------------

END