@@ -0,0 +1,794 @@
+ --
+ -- Copyright(C) 2008 Western Telematic, Inc.
+ --
+ WTI-MPC-MIB DEFINITIONS ::= BEGIN
+
+ IMPORTS
+ MODULE-IDENTITY, NOTIFICATION-TYPE,
+ OBJECT-TYPE, enterprises FROM SNMPv2-SMI
+ DisplayString FROM SNMPv2-TC;
+ westernTelematic OBJECT IDENTIFIER ::= { enterprises 2634 }
+
+ wti MODULE-IDENTITY
+ LAST-UPDATED "200812171530Z" -- 17 Dec 2008
+ ORGANIZATION "Western Telematic, Inc."
+ CONTACT-INFO
+ "Western Telematic, Inc.
+ 5 Sterling
+ Irvine, Ca 92618
+ Email: anthonyb@wti.com"
+ DESCRIPTION
+ "This is the MIB module for the MPC"
+
+ REVISION "200812171530Z" -- 17 Dec 2008
+
+ DESCRIPTION
+ "V3.00 for the MPC 1.60"
+
+ ::= { westernTelematic 3 }
+
+ --
+ -- System Tables
+ --
+
+ systemTables OBJECT IDENTIFIER ::= { wti 100 }
+ --
+ -- Plug Table
+ --
+
+ plugTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PlugEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of plugs."
+ ::= { systemTables 200 }
+
+ plugEntry OBJECT-TYPE
+ SYNTAX PlugEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Row definition for the plug table."
+ INDEX { plugIndex }
+ ::= { plugTable 1 }
+
+ PlugEntry ::= SEQUENCE {
+ plugIndex INTEGER,
+ plugID DisplayString,
+ plugStatus INTEGER,
+ plugAction INTEGER,
+ plugName DisplayString
+ }
+
+ plugIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..80)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Index for the plug table."
+ ::= { plugEntry 1 }
+
+ plugID OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(9..11))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ID of the plug."
+ ::= { plugEntry 2 }
+
+ plugStatus OBJECT-TYPE
+ SYNTAX INTEGER (0..1)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Plug status"
+ ::= { plugEntry 3 }
+
+ plugAction OBJECT-TYPE
+ SYNTAX INTEGER (0..8)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Plug action"
+ ::= { plugEntry 4 }
+
+ plugName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The Name of the plug."
+ ::= { plugEntry 5 }
+
+ --
+ -- Plug Group Table
+ --
+
+ plugGroupTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PlugGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of plug groups."
+ ::= { systemTables 300 }
+
+ plugGroupEntry OBJECT-TYPE
+ SYNTAX PlugGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Row definition for the plug group table."
+ INDEX { plugGroupIndex }
+ ::= { plugGroupTable 1 }
+
+ PlugGroupEntry ::= SEQUENCE {
+ plugGroupIndex INTEGER,
+ plugGroupName DisplayString,
+ plugGroupAction INTEGER
+ }
+
+ plugGroupIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..54)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Index for the plug group table."
+ ::= { plugGroupEntry 1 }
+
+ plugGroupName OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(1..24))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The name of the plug group."
+ ::= { plugGroupEntry 2 }
+
+ plugGroupAction OBJECT-TYPE
+ SYNTAX INTEGER (0..8)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Plug group action"
+ ::= { plugGroupEntry 3 }
+
+ --
+ -- User Table
+ --
+
+ userTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF UserEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of users."
+ ::= { systemTables 400 }
+
+ userEntry OBJECT-TYPE
+ SYNTAX UserEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Row definition for the user table."
+ INDEX { userIndex }
+ ::= { userTable 1 }
+
+ UserEntry ::= SEQUENCE {
+ userIndex INTEGER,
+ userName DisplayString,
+ userPasswd DisplayString,
+ userAccessLevel INTEGER,
+ userPortAccess DisplayString,
+ userLocalAccess DisplayString,
+ userAux1Access DisplayString,
+ userAux2Access DisplayString,
+ userAux3Access DisplayString,
+ userGroupAccess DisplayString,
+ userSerialAccess INTEGER,
+ userTelnetSshAccess INTEGER,
+ userWebAccess INTEGER,
+ userCurrentPowerMetering INTEGER,
+ userCallbackNum DisplayString,
+ userSubmit INTEGER
+ }
+
+ userIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..128)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Index for the user table."
+ ::= { userEntry 1 }
+
+ userName OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(0..32))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The name of the user."
+ ::= { userEntry 2 }
+
+ userPasswd OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(1..16))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The password of the user."
+ ::= { userEntry 3 }
+
+ userAccessLevel OBJECT-TYPE
+ SYNTAX INTEGER (0..3)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Users access level"
+ ::= { userEntry 4 }
+
+ userPortAccess OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(1..5))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to ports."
+ ::= { userEntry 5 }
+
+ userLocalAccess OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(1..20))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to LOCAL plugs."
+ ::= { userEntry 6 }
+
+ userAux1Access OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(1..20))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to AUX1 plugs."
+ ::= { userEntry 7 }
+
+ userAux2Access OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(1..20))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to AUX2 plugs."
+ ::= { userEntry 8 }
+
+ userAux3Access OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(1..20))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to AUX3 plugs."
+ ::= { userEntry 9 }
+
+ userGroupAccess OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(1..54))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to plug groups."
+ ::= { userEntry 10 }
+
+ userSerialAccess OBJECT-TYPE
+ SYNTAX INTEGER (0..1)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to serial interface."
+ ::= { userEntry 11 }
+
+ userTelnetSshAccess OBJECT-TYPE
+ SYNTAX INTEGER (0..1)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to Telnet/SSH interface."
+ ::= { userEntry 12 }
+
+ userWebAccess OBJECT-TYPE
+ SYNTAX INTEGER (0..1)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to web interface."
+ ::= { userEntry 13 }
+
+ userCurrentPowerMetering OBJECT-TYPE
+ SYNTAX INTEGER (0..1)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Access to Current/Power Metering."
+ ::= { userEntry 15 }
+
+ userCallbackNum OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(0..32))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Callback number."
+ ::= { userEntry 16 }
+
+ userSubmit OBJECT-TYPE
+ SYNTAX INTEGER (0..1)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Submit changes to user."
+ ::= { userEntry 31 }
+
+ --
+ -- Environment Tables
+ --
+
+ environmentTables OBJECT IDENTIFIER ::= { wti 200 }
+
+ environmentUnitTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EnvironmentUnitEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of environment status for units."
+ ::= { environmentTables 10 }
+
+ environmentUnitEntry OBJECT-TYPE
+ SYNTAX EnvironmentUnitEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Row definition for the environment unit table."
+ INDEX { environmentUnitIndex }
+ ::= { environmentUnitTable 1 }
+
+ EnvironmentUnitEntry ::= SEQUENCE {
+ environmentUnitIndex INTEGER,
+ environmentUnitName DisplayString,
+ environmentUnitTemperature INTEGER,
+ environmentUnitCurrentA INTEGER,
+ environmentUnitVoltageA INTEGER,
+ environmentUnitPowerA INTEGER,
+ environmentUnitCurrentB INTEGER,
+ environmentUnitVoltageB INTEGER,
+ environmentUnitPowerB INTEGER,
+ environmentUnitCurrentC INTEGER,
+ environmentUnitVoltageC INTEGER,
+ environmentUnitPowerC INTEGER,
+ environmentUnitCurrentD INTEGER,
+ environmentUnitVoltageD INTEGER,
+ environmentUnitPowerD INTEGER
+ }
+
+ environmentUnitIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..3)
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Index for the environment unit table."
+ ::= { environmentUnitEntry 1 }
+
+ environmentUnitName OBJECT-TYPE
+ SYNTAX DisplayString(SIZE(0..10))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The name of the unit."
+ ::= { environmentUnitEntry 2 }
+
+ environmentUnitTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The name of the unit."
+ ::= { environmentUnitEntry 3 }
+
+ environmentUnitCurrentA OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of amps in branch A for unit (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentUnitEntry 4 }
+
+ environmentUnitVoltageA OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The voltage of branch A for unit."
+ ::= { environmentUnitEntry 5 }
+
+ environmentUnitPowerA OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of watts used by branch A for unit."
+ ::= { environmentUnitEntry 6 }
+
+ environmentUnitCurrentB OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of amps in branch B for unit (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentUnitEntry 7 }
+
+ environmentUnitVoltageB OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The voltage of branch B for unit."
+ ::= { environmentUnitEntry 8 }
+
+ environmentUnitPowerB OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of watts used by branch b for unit."
+ ::= { environmentUnitEntry 9 }
+
+ environmentUnitCurrentC OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of amps in branch C for unit (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentUnitEntry 10 }
+
+ environmentUnitVoltageC OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The voltage of branch C for unit."
+ ::= { environmentUnitEntry 11 }
+
+ environmentUnitPowerC OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of watts used by branch c for unit."
+ ::= { environmentUnitEntry 12 }
+
+ environmentUnitCurrentD OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of amps in branch D for unit (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentUnitEntry 13 }
+
+ environmentUnitVoltageD OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The voltage of branch D for unit."
+ ::= { environmentUnitEntry 14 }
+
+ environmentUnitPowerD OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of watts used by branch d for unit."
+ ::= { environmentUnitEntry 15 }
+
+ environmentBranchATotalCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total Current on BRANCH A (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentTables 20 }
+
+ environmentBranchATotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total Power on BRANCH A."
+ ::= { environmentTables 30 }
+
+ environmentBranchBTotalCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total Current on BRANCH B (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentTables 40 }
+
+ environmentBranchBTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total Power on BRANCH B."
+ ::= { environmentTables 50 }
+
+ environmentBranchCTotalCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total Current on BRANCH C (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentTables 51 }
+
+ environmentBranchCTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total Power on BRANCH C."
+ ::= { environmentTables 52 }
+
+ environmentBranchDTotalCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total Current on BRANCH D (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentTables 53 }
+
+ environmentBranchDTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total Power on BRANCH D."
+ ::= { environmentTables 54 }
+
+ environmentSystemTotalCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total current for system (In tenths of amps, divide by 10 for value in amps)."
+ ::= { environmentTables 60 }
+
+ environmentSystemTotalPower OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total power on system."
+ ::= { environmentTables 70 }
+
+ environmentMonthlyPowerLog OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The monthly power usage log"
+ ::= { environmentTables 80 }
+
+ --
+ -- Traps
+ --
+
+ wtiTraps OBJECT IDENTIFIER ::= { wti 300 }
+
+ -- Trap Info
+
+ trapInfo OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Alarm information"
+ ::= { wtiTraps 1 }
+
+ -- Test Traps
+
+ testTraps OBJECT IDENTIFIER ::= { wtiTraps 2}
+
+ testTrap TRAP-TYPE
+ ENTERPRISE testTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "A test trap"
+ ::= 1
+
+ -- Alarm Traps
+
+ overCurrentInitialTraps OBJECT IDENTIFIER ::= { wtiTraps 4}
+
+ overCurrentInitialSetTrap TRAP-TYPE
+ ENTERPRISE overCurrentInitialTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Over Current Initial Alarm"
+ ::= 1
+
+ overCurrentInitialClearTrap TRAP-TYPE
+ ENTERPRISE overCurrentInitialTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Over Current Initial Alarm (Clear)"
+ ::= 2
+
+ overCurrentCriticalTraps OBJECT IDENTIFIER ::= { wtiTraps 5}
+
+ overCurrentCriticalSetTrap TRAP-TYPE
+ ENTERPRISE overCurrentCriticalTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Over Current Critical Alarm"
+ ::= 1
+
+ overCurrentCriticalClearTrap TRAP-TYPE
+ ENTERPRISE overCurrentCriticalTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Over Current Critical Alarm (Clear)"
+ ::= 2
+
+ overTemperatureInitialTraps OBJECT IDENTIFIER ::= { wtiTraps 6}
+
+ overTemperatureInitialSetTrap TRAP-TYPE
+ ENTERPRISE overTemperatureInitialTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Over Temperature Initial Alarm"
+ ::= 1
+
+ overTemperatureInitialClearTrap TRAP-TYPE
+ ENTERPRISE overTemperatureInitialTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Over Temperature Initial Alarm (Clear)"
+ ::= 2
+
+ overTemperatureCriticalTraps OBJECT IDENTIFIER ::= { wtiTraps 7}
+
+ overTemperatureCriticalSetTrap TRAP-TYPE
+ ENTERPRISE overTemperatureCriticalTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Over Temperature Critical Alarm"
+ ::= 1
+
+ overTemperatureCriticalClearTrap TRAP-TYPE
+ ENTERPRISE overTemperatureCriticalTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Over Temperature Critical Alarm (Clear)"
+ ::= 2
+
+ circuitBreakerOpenTraps OBJECT IDENTIFIER ::= { wtiTraps 8}
+
+ circuitBreakerOpenSetTrap TRAP-TYPE
+ ENTERPRISE circuitBreakerOpenTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Circuit Breaker Open Alarm"
+ ::= 1
+
+ circuitBreakerOpenClearTrap TRAP-TYPE
+ ENTERPRISE circuitBreakerOpenTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Circuit Breaker Open Alarm (Clear)"
+ ::= 2
+
+ lostCommTraps OBJECT IDENTIFIER ::= { wtiTraps 9}
+
+ lostCommSetTrap TRAP-TYPE
+ ENTERPRISE lostCommTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Lost Communication with AUX Unit"
+ ::= 1
+
+ lostCommClearTrap TRAP-TYPE
+ ENTERPRISE lostCommTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Lost Communication with AUX Unit (Clear)"
+ ::= 2
+
+ lostVoltageTraps OBJECT IDENTIFIER ::= { wtiTraps 10}
+
+ lostVoltageSetTrap TRAP-TYPE
+ ENTERPRISE lostVoltageTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Lost Voltage (Line In)"
+ ::= 1
+
+ lostVoltageClearTrap TRAP-TYPE
+ ENTERPRISE lostVoltageTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Lost Voltage (Line In) (Clear)"
+ ::= 2
+
+ pingNoAnswerTraps OBJECT IDENTIFIER ::= { wtiTraps 11}
+
+ pingNoAnswerSetTrap TRAP-TYPE
+ ENTERPRISE pingNoAnswerTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Ping No Answer"
+ ::= 1
+
+ pingNoAnswerClearTrap TRAP-TYPE
+ ENTERPRISE pingNoAnswerTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Ping No Answer (Clear)"
+ ::= 2
+
+ lockoutTraps OBJECT IDENTIFIER ::= { wtiTraps 12}
+
+ lockoutSetTrap TRAP-TYPE
+ ENTERPRISE lockoutTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Invalid Access Lockout"
+ ::= 1
+
+ lockoutClearTrap TRAP-TYPE
+ ENTERPRISE lockoutTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Invalid Access Lockout (Clear)"
+ ::= 2
+
+ powercycleTraps OBJECT IDENTIFIER ::= { wtiTraps 13}
+
+ powercycleSetTrap TRAP-TYPE
+ ENTERPRISE powercycleTraps
+ VARIABLES {
+ trapInfo
+ }
+ DESCRIPTION
+ "Power Cycle"
+ ::= 1
+
+ END \ No newline at end of file