summaryrefslogtreecommitdiff
path: root/MIBS/schneider
diff options
context:
space:
mode:
Diffstat (limited to 'MIBS/schneider')
-rw-r--r--MIBS/schneider/PM8ECCMIB1365
1 files changed, 1365 insertions, 0 deletions
diff --git a/MIBS/schneider/PM8ECCMIB b/MIBS/schneider/PM8ECCMIB
new file mode 100644
index 0000000..691b55c
--- /dev/null
+++ b/MIBS/schneider/PM8ECCMIB
@@ -0,0 +1,1365 @@
+PM8ECCMIB DEFINITIONS ::= BEGIN
+ IMPORTS
+ enterprises
+ FROM RFC1155-SMI
+ OBJECT-TYPE
+ FROM RFC-1212
+ TRAP-TYPE
+ FROM RFC-1215;
+
+ AlarmType ::= INTEGER {
+ overValue( 10 ),
+ overPower( 11 ),
+ overReversePower( 12 ),
+ underValue( 20 ),
+ underPower( 21 ),
+ phaseRotationReversal( 51 ),
+ phaseLossVoltage( 52 ),
+ phaseLossCurrent( 53 ),
+ powerFactorLeading( 54 ),
+ powerFactorLagging( 55 ),
+ digitalInputOFFtoON( 60 ),
+ digitalInputONtoOFF( 61 ),
+ unaryEvent( 70 ),
+ voltageOrCurrentSwell( 80 ),
+ voltageOrCurrentSag( 90 ),
+ combinatorialAND( 100 ),
+ combinatorialNAND( 101 ),
+ combinatorialOR( 102 ),
+ combinatorialNOR( 103 ),
+ combinatorialXOR( 104 ),
+ combinatorialNOT( 105 ),
+ diagnostic( 1280 )
+ }
+
+ IOPointType ::= INTEGER {
+ digitalInput( 1 ),
+ digitalOutput( 2 ),
+ analogInput( 3 ),
+ analogOutput( 4 )
+ }
+
+ IOPointLabel ::= OCTET STRING (SIZE(0..16))
+
+ AlarmLabel ::= OCTET STRING (SIZE(0..16))
+
+
+
+ schneiderElectric OBJECT IDENTIFIER ::= { enterprises 3833 }
+
+ transparentFactoryEthernet OBJECT IDENTIFIER ::= { schneiderElectric 1 }
+
+ equipmentProfile OBJECT IDENTIFIER ::= { transparentFactoryEthernet 7 }
+
+ tfProducts OBJECT IDENTIFIER ::= { equipmentProfile 255 }
+
+ ecc OBJECT IDENTIFIER ::= { tfProducts 15 }
+
+ pm8ecc OBJECT IDENTIFIER ::= { ecc 1 }
+
+ metering OBJECT IDENTIFIER ::= { pm8ecc 1 }
+
+ systemWiringTypeTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SystemWiringTypeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "The wiring system type of the host meter."
+ ::= { metering 1 }
+
+ systemWiringTypeEntry OBJECT-TYPE
+ SYNTAX SystemWiringTypeEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter System Wiring Type"
+ INDEX {
+ swtIndex
+ }
+ ::= { systemWiringTypeTable 1 }
+
+ SystemWiringTypeEntry ::= SEQUENCE {
+ swtIndex
+ INTEGER,
+ swtWiringType
+ INTEGER
+ }
+
+ swtIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "System Wiring Type Table Index"
+ ::= { systemWiringTypeEntry 1 }
+
+ swtWiringType OBJECT-TYPE
+ SYNTAX INTEGER (10 | 11 | 12 | 30 | 31 | 32 | 40 | 42 | 44)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Single Phase Line to Neutral 2 Wire 1CT 1PT is
+ '10' Single Phase Line to Line 2 Wire 1CT 1PT
+ is '11' Single Phase 3-Wire 3 wire 2CT 2PT is
+ '12' Three Phase 3 Wire 2CT 2PT is '30' Three
+ Phase 3 Wire 3CT 2PT is '31' Three Phase 3 Wire
+ 1CT 2PT is '32' Three Phase 4 Wire 3CT 3PT is
+ '40' Three Phase 4 Wire 3CT 2PT is '42' Three
+ Phase 4 Wire 1CT 3PT is '44'"
+ ::= { systemWiringTypeEntry 2 }
+
+ loadCurrentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF LoadCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Load Current Table"
+ ::= { metering 2 }
+
+ loadCurrentEntry OBJECT-TYPE
+ SYNTAX LoadCurrentEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Load Current Table"
+ INDEX {
+ lcIndex
+ }
+ ::= { loadCurrentTable 1 }
+
+ LoadCurrentEntry ::= SEQUENCE {
+ lcIndex
+ INTEGER,
+ lcIa
+ OCTET STRING,
+ lcIb
+ OCTET STRING,
+ lcIc
+ OCTET STRING,
+ lcIAvg
+ OCTET STRING
+ }
+
+ lcIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Load Current Table Index"
+ ::= { loadCurrentEntry 1 }
+
+ lcIa OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Load Current Phase A Units = A (Amps)"
+ ::= { loadCurrentEntry 2 }
+
+ lcIb OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Load Current Phase B Units = A (Amps)"
+ ::= { loadCurrentEntry 3 }
+
+ lcIc OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Load Current Phase C Units = A (Amps)"
+ ::= { loadCurrentEntry 4 }
+
+ lcIAvg OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Load Current 3 Phase Average Units
+ = A (Amps)"
+ ::= { loadCurrentEntry 5 }
+
+ powerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PowerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Table"
+ ::= { metering 3 }
+
+ powerEntry OBJECT-TYPE
+ SYNTAX PowerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Table"
+ INDEX {
+ pIndex
+ }
+ ::= { powerTable 1 }
+
+ PowerEntry ::= SEQUENCE {
+ pIndex
+ INTEGER,
+ pReal
+ OCTET STRING,
+ pReactive
+ OCTET STRING,
+ pApparent
+ OCTET STRING
+ }
+
+ pIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Power Table Index"
+ ::= { powerEntry 1 }
+
+ pReal OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Real Power Units = kW"
+ ::= { powerEntry 2 }
+
+ pReactive OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Reactive Power Units = kVAR"
+ ::= { powerEntry 3 }
+
+ pApparent OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Apparent Power Units = kVA"
+ ::= { powerEntry 4 }
+
+ powerFactorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PowerFactorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Factor Table"
+ ::= { metering 4 }
+
+ powerFactorEntry OBJECT-TYPE
+ SYNTAX PowerFactorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Factor Table"
+ INDEX {
+ pfIndex
+ }
+ ::= { powerFactorTable 1 }
+
+ PowerFactorEntry ::= SEQUENCE {
+ pfIndex
+ INTEGER,
+ pfPowerFactorTotal
+ OCTET STRING,
+ pfPowerFactorDescription
+ OCTET STRING
+ }
+
+ pfIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Power Factor Table Index"
+ ::= { powerFactorEntry 1 }
+
+ pfPowerFactorTotal OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter 3 Phase Total Power Factor"
+ ::= { powerFactorEntry 2 }
+
+ pfPowerFactorDescription OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Describes the current power factor Lead/Lag for
+ IEEE mode Cap/Ind for IEC mode"
+ ::= { powerFactorEntry 3 }
+
+ voltageTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Table"
+ ::= { metering 5 }
+
+ voltageEntry OBJECT-TYPE
+ SYNTAX VoltageEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Table"
+ INDEX {
+ vIndex
+ }
+ ::= { voltageTable 1 }
+
+ VoltageEntry ::= SEQUENCE {
+ vIndex
+ INTEGER,
+ vVab
+ OCTET STRING,
+ vVbc
+ OCTET STRING,
+ vVca
+ OCTET STRING,
+ vVllAvg
+ OCTET STRING,
+ vVan
+ OCTET STRING,
+ vVbn
+ OCTET STRING,
+ vVcn
+ OCTET STRING,
+ vVlnAvg
+ OCTET STRING
+ }
+
+ vIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Voltage Table Index"
+ ::= { voltageEntry 1 }
+
+ vVab OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Line A to Line B Units = V
+ (Volts)"
+ ::= { voltageEntry 2 }
+
+ vVbc OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Line B to Line C Units = V
+ (Volts)"
+ ::= { voltageEntry 3 }
+
+ vVca OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Line C to Line A Units = V
+ (Volts)"
+ ::= { voltageEntry 4 }
+
+ vVllAvg OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Line to Line Average Voltage
+ Units = V (Volts)"
+ ::= { voltageEntry 5 }
+
+ vVan OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Line A to Neutral Units = V
+ (Volts)"
+ ::= { voltageEntry 6 }
+
+ vVbn OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Line B to Neutral Units = V
+ (Volts)"
+ ::= { voltageEntry 7 }
+
+ vVcn OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Line C to Neutral Units = V
+ (Volts)"
+ ::= { voltageEntry 8 }
+
+ vVlnAvg OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Voltage Line to Neutral 3 Phase Average
+ Units = V (Volts)"
+ ::= { voltageEntry 9 }
+
+ frequencyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF FrequencyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Frequency Table"
+ ::= { metering 6 }
+
+ frequencyEntry OBJECT-TYPE
+ SYNTAX FrequencyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Frequency Table"
+ INDEX {
+ fIndex
+ }
+ ::= { frequencyTable 1 }
+
+ FrequencyEntry ::= SEQUENCE {
+ fIndex
+ INTEGER,
+ fFrequency
+ OCTET STRING
+ }
+
+ fIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Frequency Table Index"
+ ::= { frequencyEntry 1 }
+
+ fFrequency OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Frequency Units = Hz"
+ ::= { frequencyEntry 2 }
+
+ currentDemandTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CurrentDemandEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Current Demand Table"
+ ::= { metering 7 }
+
+ currentDemandEntry OBJECT-TYPE
+ SYNTAX CurrentDemandEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Current Demand Table"
+ INDEX {
+ cdPhase,
+ cdIndex
+ }
+ ::= { currentDemandTable 1 }
+
+ CurrentDemandEntry ::= SEQUENCE {
+ cdIndex
+ INTEGER,
+ cdPhase
+ OCTET STRING,
+ cdPresentCurrentDemand
+ OCTET STRING,
+ cdPeakCurrentDemand
+ OCTET STRING,
+ cdLastCurrentDemand
+ OCTET STRING,
+ cdPeakDateTime
+ OCTET STRING,
+ cdResetDateTime
+ OCTET STRING,
+ cdPhaseEnum
+ INTEGER
+ }
+
+ cdIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Demand Current Table Index"
+ ::= { currentDemandEntry 1 }
+
+ cdPhase OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(2))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Current Demand Phase Name"
+ ::= { currentDemandEntry 2 }
+
+ cdPresentCurrentDemand OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Present Demand Current Units = A (Amps)"
+ ::= { currentDemandEntry 3 }
+
+ cdPeakCurrentDemand OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Peak Current Demand Units = A (Amps)"
+ ::= { currentDemandEntry 4 }
+
+ cdLastCurrentDemand OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Current Demand Last Interval Units
+ = A (Amps)"
+ ::= { currentDemandEntry 5 }
+
+ cdPeakDateTime OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Peak Current Demand Date and Time"
+ ::= { currentDemandEntry 6 }
+
+ cdResetDateTime OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Date and Time of Demand Current Reset"
+ ::= { currentDemandEntry 7 }
+
+ cdPhaseEnum OBJECT-TYPE
+ SYNTAX INTEGER {
+ currentPhaseA( 1 ),
+ currentPhaseB( 2 ),
+ currentPhaseC( 3 )
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Current Demand Phase"
+ ::= { currentDemandEntry 8 }
+
+ powerDemandTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF PowerDemandEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Demand"
+ ::= { metering 8 }
+
+ powerDemandEntry OBJECT-TYPE
+ SYNTAX PowerDemandEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Demand Table"
+ INDEX {
+ pdComponent,
+ pdIndex
+ }
+ ::= { powerDemandTable 1 }
+
+ PowerDemandEntry ::= SEQUENCE {
+ pdIndex
+ INTEGER,
+ pdComponent
+ OCTET STRING,
+ pdPresentPowerDemand
+ OCTET STRING,
+ pdPeakPowerDemand
+ OCTET STRING,
+ pdLastPowerDemand
+ OCTET STRING,
+ pdPeakDateTime
+ OCTET STRING,
+ pdResetDateTime
+ OCTET STRING,
+ pdComponentEnum
+ INTEGER
+ }
+
+ pdIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Power Demand Table Index"
+ ::= { powerDemandEntry 1 }
+
+ pdComponent OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(4..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Demand Component Units: Real
+ = kW Reacitve = kVAR Apparent = kVA"
+ ::= { powerDemandEntry 2 }
+
+ pdPresentPowerDemand OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Present Demand Power"
+ ::= { powerDemandEntry 3 }
+
+ pdPeakPowerDemand OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Peak Power Demand"
+ ::= { powerDemandEntry 4 }
+
+ pdLastPowerDemand OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Demand Last Interval"
+ ::= { powerDemandEntry 5 }
+
+ pdPeakDateTime OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Peak Power Demand Date and Time"
+ ::= { powerDemandEntry 6 }
+
+ pdResetDateTime OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Date and Time of Power Demand Reset"
+ ::= { powerDemandEntry 7 }
+
+ pdComponentEnum OBJECT-TYPE
+ SYNTAX INTEGER {
+ realPower( 1 ),
+ reactivePower( 2 ),
+ apparentPower( 3 )
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Power Demand Component"
+ ::= { powerDemandEntry 8 }
+
+ energyTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF EnergyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Energy Table"
+ ::= { metering 9 }
+
+ energyEntry OBJECT-TYPE
+ SYNTAX EnergyEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Energy Table"
+ INDEX {
+ eIndex
+ }
+ ::= { energyTable 1 }
+
+ EnergyEntry ::= SEQUENCE {
+ eIndex
+ INTEGER,
+ eRealEnergy
+ OCTET STRING,
+ eDateTimeRealEnergyReset
+ OCTET STRING,
+ eReactiveEnergy
+ OCTET STRING,
+ eDateTimeReactiveEnergyReset
+ OCTET STRING,
+ eApparentEnergy
+ OCTET STRING,
+ eDateTimeApparentEnergyReset
+ OCTET STRING
+ }
+
+ eIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Energy Table Index"
+ ::= { energyEntry 1 }
+
+ eRealEnergy OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Real Energy Units = Wh"
+ ::= { energyEntry 2 }
+
+ eDateTimeRealEnergyReset OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Date and Time Real Energy Accumulation
+ was reset"
+ ::= { energyEntry 3 }
+
+ eReactiveEnergy OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Reactive Energy Units = VARh"
+ ::= { energyEntry 4 }
+
+ eDateTimeReactiveEnergyReset OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Date and Time Reative Energy Accumulation
+ was reset"
+ ::= { energyEntry 5 }
+
+ eApparentEnergy OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Apparent Energy Units = VAh"
+ ::= { energyEntry 6 }
+
+ eDateTimeApparentEnergyReset OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Date and Time Reactive Energy Accumulation
+ was reset"
+ ::= { energyEntry 7 }
+
+ alarms OBJECT IDENTIFIER ::= { pm8ecc 2 }
+
+ alarmConfigurationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AlarmConfigurationEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Displays the current configuration of the Host
+ Meter On-board alarms"
+ ::= { alarms 1 }
+
+ alarmConfigurationEntry OBJECT-TYPE
+ SYNTAX AlarmConfigurationEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Contains configuration information for the Host
+ Meter On-board Alarms"
+ INDEX {
+ acIndex,
+ acPosition
+ }
+ ::= { alarmConfigurationTable 1 }
+
+ AlarmConfigurationEntry ::= SEQUENCE {
+ acIndex
+ INTEGER,
+ acPosition
+ INTEGER,
+ acAlarmLabel
+ AlarmLabel,
+ acEnabled
+ INTEGER,
+ acStatus
+ INTEGER,
+ acCounter
+ INTEGER,
+ acPriority
+ INTEGER,
+ acType
+ AlarmType,
+ acAlarmList1
+ INTEGER,
+ acAlarmList2
+ INTEGER,
+ acAlarmList3
+ INTEGER,
+ acAlarmList4
+ INTEGER
+ }
+
+ acIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm Configuration Table Index"
+ ::= { alarmConfigurationEntry 1 }
+
+ acPosition OBJECT-TYPE
+ SYNTAX INTEGER (1..74)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the position of the alarm. 1 - 74"
+ ::= { alarmConfigurationEntry 2 }
+
+ acAlarmLabel OBJECT-TYPE
+ SYNTAX AlarmLabel
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The name of the alarm (user configurable)"
+ ::= { alarmConfigurationEntry 3 }
+
+ acEnabled OBJECT-TYPE
+ SYNTAX INTEGER (0 | 255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates whether the alarm is enabled or not.
+ 0 = Disabled 255 = Enabled"
+ ::= { alarmConfigurationEntry 4 }
+
+ acStatus OBJECT-TYPE
+ SYNTAX INTEGER (0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates whether the alarm is active. 0 = Inactive
+ 1 = Active"
+ ::= { alarmConfigurationEntry 5 }
+
+ acCounter OBJECT-TYPE
+ SYNTAX INTEGER (0..32767)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the number of times the alarm has been
+ activated. Note: This counter resets at 32767"
+ ::= { alarmConfigurationEntry 6 }
+
+ acPriority OBJECT-TYPE
+ SYNTAX INTEGER (0..3)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The priority of the alarm. 0 = No Priority 1 =
+ Low Priority 2 = Medium Priority 3 = High Priority"
+ ::= { alarmConfigurationEntry 7 }
+
+ acType OBJECT-TYPE
+ SYNTAX AlarmType
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the type of the alarm."
+ ::= { alarmConfigurationEntry 8 }
+
+ acAlarmList1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Used for combinatorial type alarms - The position
+ of the first alarm that is used to evaluate the
+ alarm state."
+ ::= { alarmConfigurationEntry 9 }
+
+ acAlarmList2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Used for combinatorial type alarms - The position
+ of the second alarm that is used to evaluate
+ the alarm state."
+ ::= { alarmConfigurationEntry 10 }
+
+ acAlarmList3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Used for combinatorial type alarms - The position
+ of the third alarm that is used to evaluate the
+ alarm state."
+ ::= { alarmConfigurationEntry 11 }
+
+ acAlarmList4 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Used for combinatorial type alarms - The position
+ of the fourth alarm that is used to evaluate
+ the alarm state."
+ ::= { alarmConfigurationEntry 12 }
+
+ alarmSummaryBitmapsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AlarmSummaryBitmapsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Indicates the state of the Host Meter On-Board
+ Alarms"
+ ::= { alarms 2 }
+
+ alarmSummaryBitmapsEntry OBJECT-TYPE
+ SYNTAX AlarmSummaryBitmapsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Indicates the status of the Host Meter On-Board
+ Alarms"
+ INDEX {
+ alSumIndex
+ }
+ ::= { alarmSummaryBitmapsTable 1 }
+
+ AlarmSummaryBitmapsEntry ::= SEQUENCE {
+ alSumIndex
+ INTEGER,
+ alSumAlarms1to16
+ OCTET STRING,
+ alSumAlarms17to32
+ OCTET STRING,
+ alSumAlarms33to48
+ OCTET STRING,
+ alSumAlarms49to64
+ OCTET STRING,
+ alSumAlarms65to74
+ OCTET STRING
+ }
+
+ alSumIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm Summary Bitmap Table Index"
+ ::= { alarmSummaryBitmapsEntry 1 }
+
+ alSumAlarms1to16 OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(16))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the status of Alarms 1 - 16 (16-bits,
+ bit-0 = Alarm 1)"
+ ::= { alarmSummaryBitmapsEntry 2 }
+
+ alSumAlarms17to32 OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(16))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the status of Alarms 17 - 32 (16-bits,
+ bit-0 = Alarm 17)"
+ ::= { alarmSummaryBitmapsEntry 3 }
+
+ alSumAlarms33to48 OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(16))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the status of Alarms 33 - 48 (16-bits,
+ bit-0 = Alarm 33)"
+ ::= { alarmSummaryBitmapsEntry 4 }
+
+ alSumAlarms49to64 OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(16))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the status of Alarms 49 - 64 (16-bits,
+ bit-0 = Alarm 49)"
+ ::= { alarmSummaryBitmapsEntry 5 }
+
+ alSumAlarms65to74 OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(16))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the status of Alarms 65 - 74 (16-bits,
+ bit-0 = Alarm 65, bit-9 = Alarm 74)"
+ ::= { alarmSummaryBitmapsEntry 6 }
+
+ alarmCountersTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF AlarmCountersEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter On-Board Alarm Counters"
+ ::= { alarms 3 }
+
+ alarmCountersEntry OBJECT-TYPE
+ SYNTAX AlarmCountersEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter On-Board Alarm Counters"
+ INDEX {
+ alCntAlarmPosition,
+ alCntIndex
+ }
+ ::= { alarmCountersTable 1 }
+
+ AlarmCountersEntry ::= SEQUENCE {
+ alCntIndex
+ INTEGER,
+ alCntAlarmPosition
+ INTEGER,
+ alCntCount
+ INTEGER
+ }
+
+ alCntIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm Counters Table Index"
+ ::= { alarmCountersEntry 1 }
+
+ alCntAlarmPosition OBJECT-TYPE
+ SYNTAX INTEGER (1..74)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The Host Meter Alarm Position"
+ ::= { alarmCountersEntry 2 }
+
+ alCntCount OBJECT-TYPE
+ SYNTAX INTEGER (0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The number of times the Host Meter On-Board alarm
+ has transitioned from an inactive state to an
+ active state"
+ ::= { alarmCountersEntry 3 }
+
+ io OBJECT IDENTIFIER ::= { pm8ecc 3 }
+
+ ioOptionIDTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IoOptionIDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "I/O Option Module Installed on the Host Meter"
+ ::= { io 1 }
+
+ ioOptionIDEntry OBJECT-TYPE
+ SYNTAX IoOptionIDEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "I/O Option Card Installed On-board the Host Meter"
+ INDEX {
+ ioIDIndex
+ }
+ ::= { ioOptionIDTable 1 }
+
+ IoOptionIDEntry ::= SEQUENCE {
+ ioIDIndex
+ INTEGER,
+ ioIDInstalledOptionSlot1
+ INTEGER,
+ ioIDInstalledOptionSlot2
+ INTEGER
+ }
+
+ ioIDIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "I/O Installed Option ID Table Index"
+ ::= { ioOptionIDEntry 1 }
+
+ ioIDInstalledOptionSlot1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ unused( 1 ),
+ io-22( 2 ),
+ io-26( 3 ),
+ io-2222( 4 )
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "0 = Not Installed 1 = Unused 2 = IO22 3 = IO26
+ 4 = IO 2222"
+ ::= { ioOptionIDEntry 2 }
+
+ ioIDInstalledOptionSlot2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ unused( 1 ),
+ io-22( 2 ),
+ io-26( 3 ),
+ io-2222( 4 )
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "0 = Not Installed 1 = Unused 2 = IO22 3 = IO26
+ 4 = IO 2222"
+ ::= { ioOptionIDEntry 3 }
+
+ ioConfigurationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IoConfigurationEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Displays the current I/O configuration for each
+ I/O point"
+ ::= { io 2 }
+
+ ioConfigurationEntry OBJECT-TYPE
+ SYNTAX IoConfigurationEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Contains configuration information for the Host
+ Meter On-board I/O"
+ INDEX {
+ iocIndex,
+ iocPointNumber
+ }
+ ::= { ioConfigurationTable 1 }
+
+ IoConfigurationEntry ::= SEQUENCE {
+ iocIndex
+ INTEGER,
+ iocPointNumber
+ INTEGER,
+ iocLabel
+ IOPointLabel,
+ iocStateOrValue
+ OCTET STRING,
+ iocPointType
+ IOPointType,
+ iocMode
+ INTEGER,
+ iocType
+ INTEGER,
+ iocCount
+ OCTET STRING
+ }
+
+ iocIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "I/O Configuration Table Index"
+ ::= { ioConfigurationEntry 1 }
+
+ iocPointNumber OBJECT-TYPE
+ SYNTAX INTEGER (1..18)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The point number for this I/O Point"
+ ::= { ioConfigurationEntry 2 }
+
+ iocLabel OBJECT-TYPE
+ SYNTAX IOPointLabel
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The name of the I/O Point (user configurable)"
+ ::= { ioConfigurationEntry 3 }
+
+ iocStateOrValue OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Displays the current value for the I/O Point Digial
+ I/O: 1 = Active or 0 = Inactive
+
+ Analog I/O: Scaled input/output value"
+ ::= { ioConfigurationEntry 4 }
+
+ iocPointType OBJECT-TYPE
+ SYNTAX IOPointType
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The type of I/O at this point"
+ ::= { ioConfigurationEntry 5 }
+
+ iocMode OBJECT-TYPE
+ SYNTAX INTEGER (0..9)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "For Digital Inputs and Outputs this object is
+ always 0 indicating “Discrete”.
+
+ For Analog Inputs and Outputs this object indicates
+ the range of analog I/O values (used without
+ units) 0 = 0 – 1 1 = 0 – 5 2 = 0 – 10 3 = 0 –
+ 20 4 = 1 – 5 5 = 4 – 20 6 = -5 – 5 7 = -10 –
+ 10 8 = -100 – 100 9 = User defined (values default
+ to 0)"
+ ::= { ioConfigurationEntry 6 }
+
+ iocType OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "For Digital Inputs this object indicates input
+ type 1 = Unused 2 = AC/DC
+
+ For Digital Outputs this object indicates output
+ type 1 = solid state relay 2 = electromechanical
+ relay
+
+ For Analog Inputs and Outputs this object indicates
+ the digital resolution of the I/O hardware. 0
+ = 8-Bit, unipolar 1 = 10-Bit, unipolar 2 = 12-Bit,
+ unipolar 3 = 14-Bit, unipolar 4 = 16-Bit, unipolar
+ 5 = 16-Bit, bipolar with sign 6 = reserved 7
+ = reserved 8 = Resolution for IO2222 Voltage
+ range 0 - 4000 9 = Resolution for IO2222 Current
+ range 800 - 4000"
+ ::= { ioConfigurationEntry 7 }
+
+ iocCount OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Number of times digital I/O point has transitioned
+ from OFF to ON"
+ ::= { ioConfigurationEntry 8 }
+
+ ioStatusBitmapsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF IoStatusBitmapsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter I/O Status Bitmaps"
+ ::= { io 3 }
+
+ ioStatusBitmapsEntry OBJECT-TYPE
+ SYNTAX IoStatusBitmapsEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter On-Board I/O Status Bitmaps"
+ INDEX {
+ ioStatIndex
+ }
+ ::= { ioStatusBitmapsTable 1 }
+
+ IoStatusBitmapsEntry ::= SEQUENCE {
+ ioStatIndex
+ INTEGER,
+ ioStatSummaryBitmap
+ OCTET STRING
+ }
+
+ ioStatIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "I/O Summary Bitmaps Table Index"
+ ::= { ioStatusBitmapsEntry 1 }
+
+ ioStatSummaryBitmap OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(18))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Indicates the Status of the Host Meter I/O Points
+ Bit-0 = I/O Point 1 Bit-1 = I/O Point 2 ... Bit-17
+ = I/O Point 18"
+ ::= { ioStatusBitmapsEntry 2 }
+
+ meterSystem OBJECT IDENTIFIER ::= { pm8ecc 4 }
+
+ meterIdentificationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF MeterIdentificationEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Identification"
+ ::= { meterSystem 1 }
+
+ meterIdentificationEntry OBJECT-TYPE
+ SYNTAX MeterIdentificationEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION "Host Meter Identification"
+ INDEX {
+ midIndex
+ }
+ ::= { meterIdentificationTable 1 }
+
+ MeterIdentificationEntry ::= SEQUENCE {
+ midIndex
+ INTEGER,
+ midSerialNumber
+ INTEGER,
+ midFirmwareVersion
+ OCTET STRING,
+ midModelNumber
+ OCTET STRING,
+ midDeviceName
+ OCTET STRING
+ }
+
+ midIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Meter Identification Table Index"
+ ::= { meterIdentificationEntry 1 }
+
+ midSerialNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host meter 32 bit Serial Number"
+ ::= { meterIdentificationEntry 2 }
+
+ midFirmwareVersion OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Firmware Version"
+ ::= { meterIdentificationEntry 3 }
+
+ midModelNumber OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Model Number"
+ ::= { meterIdentificationEntry 4 }
+
+ midDeviceName OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Host Meter Label plus Nameplate"
+ ::= { meterIdentificationEntry 5 }
+
+ trapVariables OBJECT IDENTIFIER ::= { pm8ecc 5 }
+
+ alarmDateAndTime OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The Date and Time of the alarm state change."
+ ::= { trapVariables 1 }
+
+ alarmLabel OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The Descriptive Label given to the alarm"
+ ::= { trapVariables 2 }
+
+ alarmState OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The state of the Alarm - pickup, dropout, unary,
+ diagnostic"
+ ::= { trapVariables 3 }
+
+ alarmValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The value of the alarm when it changed state."
+ ::= { trapVariables 4 }
+
+ alarmPriority OBJECT-TYPE
+ SYNTAX INTEGER {
+ highPriority( 1 ),
+ mediumPriority( 2 ),
+ lowPriority( 3 )
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The priority defined for the alarm."
+ ::= { trapVariables 5 }
+
+ mibVersion OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "This is the current version of the MIB"
+ ::= { pm8ecc 6 }
+
+
+ pm8OnBoardAlarmP1 TRAP-TYPE
+ ENTERPRISE pm8ecc
+ VARIABLES {
+ alarmDateAndTime,
+ alarmLabel,
+ alarmState,
+ alarmValue,
+ alarmPriority
+ }
+ DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
+ detected a state change of an enabled alarm with a
+ priority of 1"
+ ::= 1
+
+ pm8OnBoardAlarmP2 TRAP-TYPE
+ ENTERPRISE pm8ecc
+ VARIABLES {
+ alarmDateAndTime,
+ alarmLabel,
+ alarmState,
+ alarmValue,
+ alarmPriority
+ }
+ DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
+ detected a state change of an enabled alarm with a
+ priority of 2"
+ ::= 2
+
+ pm8OnBoardAlarmP3 TRAP-TYPE
+ ENTERPRISE pm8ecc
+ VARIABLES {
+ alarmDateAndTime,
+ alarmLabel,
+ alarmState,
+ alarmValue,
+ alarmPriority
+ }
+ DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
+ detected a state change of an enabled alarm with a
+ priority of 3"
+ ::= 3
+
+
+END
+