summaryrefslogtreecommitdiff
path: root/MIBS/imco/IMCO-LS110-MIB
diff options
context:
space:
mode:
Diffstat (limited to 'MIBS/imco/IMCO-LS110-MIB')
-rw-r--r--MIBS/imco/IMCO-LS110-MIB378
1 files changed, 378 insertions, 0 deletions
diff --git a/MIBS/imco/IMCO-LS110-MIB b/MIBS/imco/IMCO-LS110-MIB
new file mode 100644
index 0000000..0961e2f
--- /dev/null
+++ b/MIBS/imco/IMCO-LS110-MIB
@@ -0,0 +1,378 @@
+IMCO-LS110-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ MODULE-IDENTITY, OBJECT-TYPE,
+ Counter32, Integer32, Gauge32,
+ TimeTicks, IpAddress,
+ enterprises
+ FROM SNMPv2-SMI
+ TRAP-TYPE FROM RFC-1215;
+
+
+mib-AN-Dcz-SDS MODULE-IDENTITY
+ LAST-UPDATED "201702090000Z"
+ ORGANIZATION "ViaNet.sk"
+ CONTACT-INFO
+ " Ivan Mochnac
+ ViaNet
+ -
+ -
+ SK EUROPE
+
+ -
+ vianet@vianet.sk"
+ DESCRIPTION
+ "The MIB module to describe PSMSmicro version of SDS."
+
+
+ REVISION "201702090000Z"
+ DESCRIPTION
+ "PSMSmicro, by ViaNet.sk."
+ ::= { enterprises 33283 }
+
+
+--
+-- MIB file definition for device: PSMSmicro
+--
+
+sdsxpublic OBJECT IDENTIFIER ::= { mib-AN-Dcz-SDS 1 }
+
+sdsBIGandSTSW OBJECT IDENTIFIER ::= { sdsxpublic 30 }
+
+-- ****************************************************************************
+
+sdsOptoInput OBJECT IDENTIFIER ::= { sdsBIGandSTSW 2 }
+
+opto1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ activeSignalPresent(0),
+ noSignal(32768)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Current OPTO1 binary input status."
+ ::= { sdsOptoInput 1 }
+
+opto2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ activeSignalPresent(0),
+ noSignal(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Current OPTO2 binary input status."
+ ::= { sdsOptoInput 2 }
+
+opto3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ activeSignalPresent(0),
+ noSignal(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Current Mains (OPTO3) binary input status."
+ ::= { sdsOptoInput 3 }
+
+-- ****************************************************************************
+
+sdsOutputRelays OBJECT IDENTIFIER ::= { sdsBIGandSTSW 3 }
+
+sdsOutputRelay1 OBJECT IDENTIFIER ::= { sdsOutputRelays 1 }
+
+sdsRE1state OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(0),
+ activated(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Current RELAY 1 output status."
+ ::= { sdsOutputRelay1 1 }
+
+sdsOutputRelay2 OBJECT IDENTIFIER ::= { sdsOutputRelays 2 }
+
+sdsRE2state OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(0),
+ activated(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Current RELAY 2 output status."
+ ::= { sdsOutputRelay2 1 }
+
+sdsOutputRelay3 OBJECT IDENTIFIER ::= { sdsOutputRelays 3 }
+
+sdsRE3state OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(0),
+ activated(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Current RELAY 3 output status."
+ ::= { sdsOutputRelay3 1 }
+
+-- ****************************************************************************
+
+sdsADCinputs OBJECT IDENTIFIER ::= { sdsBIGandSTSW 5 }
+
+sdsADCitem0 OBJECT IDENTIFIER ::= { sdsADCinputs 1 }
+
+sdsTempSensValue OBJECT-TYPE
+ SYNTAX Gauge32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Temperature Sensor (C) multiplied by 100."
+ ::= { sdsADCitem0 3 }
+
+sdsTempSensName OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "User name for the analog temperature sensor."
+ ::= { sdsADCitem0 4 }
+
+-- ****************************************************************************
+
+sdsADCvalues OBJECT IDENTIFIER ::= { sdsBIGandSTSW 7 }
+
+sdsMaximumLoad OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Maximum Load (W) multiplied by 10."
+ ::= { sdsADCvalues 2 }
+
+sdsAlarmText OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "SDS Alarm Text."
+ ::= { sdsADCvalues 3 }
+
+sdsOutputVoltage1 OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Output voltage U1 (V) multiplied by 100."
+ ::= { sdsADCvalues 4 }
+
+sdsOutputVoltage2 OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Output voltage U2 (V) multiplied by 100."
+ ::= { sdsADCvalues 5 }
+
+sdsOutputCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Output current I (A) multiplied by 10."
+ ::= { sdsADCvalues 6 }
+
+sdsBatteryCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery Capacity (%) multiplied by 10."
+ ::= { sdsADCvalues 7 }
+
+sdsLoad OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Load (%) multiplied by 10."
+ ::= { sdsADCvalues 8 }
+
+sdsCapTestTime OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Time (min) of last Capacity Test."
+ ::= { sdsADCvalues 9 }
+
+-- ****************************************************************************
+
+sdsGeneralInfoEntry OBJECT IDENTIFIER ::= { sdsBIGandSTSW 8 }
+
+sdsManufacturer OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Manufacturer of the device."
+ ::= { sdsGeneralInfoEntry 80 }
+
+sdsModel OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Model (type) of the device."
+ ::= { sdsGeneralInfoEntry 81 }
+
+sdsName OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Name/Location of the device."
+ ::= { sdsGeneralInfoEntry 82 }
+
+sdsSerialNumber OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Serial number of the device."
+ ::= { sdsGeneralInfoEntry 83 }
+
+sdsSoftware OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Software version of the device."
+ ::= { sdsGeneralInfoEntry 84 }
+
+-- ****************************************************************************
+
+-- ****************************************************************************
+-- TRAP-SDS-MICRO-MIB DEFINITIONS
+-- ****************************************************************************
+
+opto1-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { opto1 }
+ DESCRIPTION "TRAP: optical input 1 status."
+ ::= 100
+
+opto2-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { opto2 }
+ DESCRIPTION "TRAP: optical input 2 status."
+ ::= 101
+
+opto3-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { opto3 }
+ DESCRIPTION "TRAP: optical input 3 status."
+ ::= 102
+
+-- next
+
+sdsRE1state-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsRE1state }
+ DESCRIPTION "TRAP: Current RELAY 1 output status."
+ ::= 150
+
+sdsRE2state-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsRE2state }
+ DESCRIPTION "TRAP: Current RELAY 2 output status."
+ ::= 153
+
+-- next
+
+sdsTempSensValue-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsTempSensValue }
+ DESCRIPTION "TRAP: Temperature Sensor (C) multiplied by 100."
+ ::= 222
+
+sdsTempSensName-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsTempSensName }
+ DESCRIPTION "TRAP: User name for analog temperature sensor."
+ ::= 223
+
+-- next
+
+sdsMaximumLoad-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsMaximumLoad }
+ DESCRIPTION "TRAP: SDS Maximum Load-trap."
+ ::= 401
+
+sdsAlarmText-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsAlarmText }
+ DESCRIPTION "TRAP: SDS Alarm Text."
+ ::= 402
+
+sdsOutputVoltage1-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsOutputVoltage1 }
+ DESCRIPTION "TRAP: SDS Output Voltage1-trap."
+ ::= 403
+
+sdsOutputVoltage2-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsOutputVoltage2 }
+ DESCRIPTION "TRAP: SDS Outpur Voltage2-trap."
+ ::= 404
+
+sdsOutputCurrent-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsOutputCurrent }
+ DESCRIPTION "TRAP: SDS Output current-trap."
+ ::= 405
+
+sdsBatteryCapacity-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsBatteryCapacity }
+ DESCRIPTION "TRAP: SDS Battery Capacity-trap."
+ ::= 406
+
+sdsLoad-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsLoad }
+ DESCRIPTION "TRAP: SDS Load-trap."
+ ::= 407
+
+sdsCapTestTime-trap TRAP-TYPE
+ -- STATUS current
+ ENTERPRISE mib-AN-Dcz-SDS
+ VARIABLES { sdsCapTestTime }
+ DESCRIPTION "TRAP: SDS CapTestTime-trap."
+ ::= 408
+
+-- end
+
+END
+
+
+