+--Delta-MIB { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) delta(2254) ups(2) upsv4(4) }
+
+
+DeltaUPS-MIB DEFINITIONS ::= BEGIN
+
+
+IMPORTS
+ enterprises, IpAddress
+ FROM RFC1155-SMI
+ DisplayString
+ FROM RFC1213-MIB
+ OBJECT-TYPE
+ FROM RFC-1212
+ TRAP-TYPE
+ FROM RFC-1215;
+
+
+delta OBJECT IDENTIFIER ::= { enterprises 2254 }
+
+ups OBJECT IDENTIFIER ::= { delta 2 }
+
+upsv4 OBJECT IDENTIFIER ::= { ups 4 }
+
+dupsIdent OBJECT IDENTIFIER ::= { upsv4 1 }
+dupsControl OBJECT IDENTIFIER ::= { upsv4 2 }
+dupsConfig OBJECT IDENTIFIER ::= { upsv4 3 }
+dupsInput OBJECT IDENTIFIER ::= { upsv4 4 }
+dupsOutput OBJECT IDENTIFIER ::= { upsv4 5 }
+dupsBypass OBJECT IDENTIFIER ::= { upsv4 6 }
+dupsBattery OBJECT IDENTIFIER ::= { upsv4 7 }
+dupsTest OBJECT IDENTIFIER ::= { upsv4 8 }
+dupsAlarm OBJECT IDENTIFIER ::= { upsv4 9 }
+dupsEnvironment OBJECT IDENTIFIER ::= { upsv4 10 }
+dupsTraps OBJECT IDENTIFIER ::= { upsv4 20 }
+
+
+----------------------
+-- dups Ident group --
+----------------------
+ dupsIdentManufacturer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..20))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the UPS manufacturer."
+ ::= { dupsIdent 1 }
+
+ dupsIdentModel OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..31))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS Model designation."
+ ::= { dupsIdent 2 }
+
+ dupsIdentUPSSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..15))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS firmware/software version(s). This variable
+ may or may not has the same value as
+ upsIdentAgentSoftwareVersion in some implementations."
+ ::= { dupsIdent 3 }
+
+ dupsIdentAgentSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..15))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The UPS agent software version. This variable may or
+ may not has the same value as
+ upsIdentUPSSoftwareVersion in some implementations."
+ ::= { dupsIdent 4 }
+
+ dupsIdentName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..63))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string identifying the UPS. This object should be
+ set by the administrator."
+ ::= { dupsIdent 5 }
+
+ dupsAttachedDevices OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..63))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string identifying the devices attached to the
+ output(s) of the UPS. This object should be set by
+ the administrator."
+ ::= { dupsIdent 6 }
+
+ dupsRatingOutputVA OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The magnitude of the nominal output VA rating."
+ ::= { dupsIdent 7 }
+
+ dupsRatingOutputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The magnitude of the nominal output voltage rating."
+ ::= { dupsIdent 8 }
+
+ dupsRatingOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The magnitude of the nominal output frequency rating."
+ ::= { dupsIdent 9 }
+
+ dupsRatingInputVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The magnitude of the nominal input voltage rating."
+ ::= { dupsIdent 10 }
+
+ dupsRatingInputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The magnitude of the nominal input frequency rating."
+ ::= { dupsIdent 11 }
+
+ dupsRatingBatteryVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The magnitude of the nominal battery voltage rating."
+ ::= { dupsIdent 12 }
+
+ dupsLowTransferVoltUpBound OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Volt"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input line voltage upper bound allowed
+ before the UPS system transfers to battery backup."
+ ::= { dupsIdent 13 }
+
+ dupsLowTransferVoltLowBound OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Volt"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input line voltage lower bound allowed
+ before the UPS system transfers to battery backup."
+ ::= { dupsIdent 14 }
+
+ dupsHighTransferVoltUpBound OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Volt"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum input line voltage upper bound allowed
+ before the UPS system transfers to battery backup."
+ ::= { dupsIdent 15 }
+
+ dupsHighTransferVoltLowBound OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Volt"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum input line voltage lower bound allowed
+ before the UPS system transfers to battery backup."
+ ::= { dupsIdent 16 }
+
+ dupsLowBattTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Minutes, time from low battery to low battery shutdown."
+ ::= { dupsIdent 17 }
+
+ dupsOutletRelays OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of outlet relay. If it is 0, the function is not
+ available for the UPS."
+ ::= { dupsIdent 18 }
+
+ dupsType OBJECT-TYPE
+ SYNTAX INTEGER {
+ on-line(1),
+ off-line(2),
+ line-interactive(3),
+ 3phase(4),
+ splite-phase(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicate the UPS type."
+ ::= { dupsIdent 19 }
+
+------------------------
+-- dups Control group --
+------------------------
+ dupsShutdownType OBJECT-TYPE
+ SYNTAX INTEGER {
+ output(1),
+ system(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This object determines the nature of the action to be
+ taken at the time when the countdown of the
+ upsShutdownAfterDelay and upsRebootWithDuration
+ objects reaches zero.
+ Setting this object to output(1) indicates that
+ shutdown requests should cause only the output of the
+ UPS to turn off. Setting this object to system(2)
+ indicates that shutdown requests will cause the entire
+ UPS system to turn off."
+ ::= { dupsControl 1 }
+
+ dupsAutoReboot OBJECT-TYPE
+ SYNTAX INTEGER {
+ on(1),
+ off(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "In backup mode, the UPS may shutdown normally by SDA command,
+ dry-contact remote shutdown signal or low battery shutdown.
+ This command is used to determine the unit should restart or
+ not next time when the power restores"
+ ::= { dupsControl 2 }
+
+ dupsShutdownAction OBJECT-TYPE
+ SYNTAX INTEGER
+-- UNITS "Second"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "If the value is greater than 0 the UPS performs
+ shutdown action that defined by ShutdownType after
+ the seconds. 0, aborted."
+ ::= { dupsControl 3 }
+
+ dupsRestartAction OBJECT-TYPE
+ SYNTAX INTEGER
+-- UNITS "Minute"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "UPS will restart after the indicated number of minutes.
+ -1, aborted."
+ ::= { dupsControl 4 }
+
+ dupsSetOutletRelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicate which outlet relay, from 1,2,3... ."
+ ::= { dupsControl 5 }
+
+ dupsRelayOffDelay OBJECT-TYPE
+ SYNTAX INTEGER
+-- UNITS "Second"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turn the relay off after the seconds. The relay was indicated
+ by SetOutletRelay."
+ ::= { dupsControl 6 }
+
+ dupsRelayOnDelay OBJECT-TYPE
+ SYNTAX INTEGER
+-- UNITS "Minute"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Turn the relay on after the seconds. The relay was indicated
+ by SetOutletRelay."
+ ::= { dupsControl 7 }
+
+--------------------------
+-- dups Configure group --
+--------------------------
+ dupsConfigBuzzerAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ alarm(1),
+ silence(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "UPS will keep silence but will alarm again when
+ next power event is occurred"
+ ::= { dupsConfig 1 }
+
+ dupsConfigBuzzerState OBJECT-TYPE
+ SYNTAX INTEGER {
+ enable(1),
+ disable(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "If it is disabled then the UPS is always muted."
+ ::= { dupsConfig 2 }
+
+ dupsConfigSensitivity OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal(0),
+ reduced(1),
+ low(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The seneitivity of the UPS to utility line
+ abnormalities or noises."
+ ::= { dupsConfig 3 }
+
+ dupsConfigLowVoltageTransferPoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Volt"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The minimum input line voltage allowed before the UPS
+ system transfers to battery backup."
+ ::= { dupsConfig 4 }
+
+ dupsConfigHighVoltageTransferPoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Volt"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum line voltage allowed before the UPS
+ system transfers to battery backup."
+ ::= { dupsConfig 5 }
+
+ dupsConfigShutdownOSDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Second"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The operating system shutdown delay time when the
+ input power fail. -1 will disable this option."
+ ::= { dupsConfig 6 }
+
+ dupsConfigUPSBootDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Second"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Delay the UPS startup after power restores. The power
+ quality may not stable when power restores, this
+ feature let the UPS wait a period of time to startup
+ the system."
+ ::= { dupsConfig 7 }
+
+ dupsConfigExternalBatteryPack OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Indicate the number of external battery pack."
+ ::= { dupsConfig 8 }
+
+----------------------
+-- dups Input group --
+----------------------
+ dupsInputNumLines OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of input lines utilized in this device."
+ ::= { dupsInput 1 }
+
+ dupsInputFrequency1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current input line 1 frequency to the UPS
+ system in 1/10 Hz."
+ ::= { dupsInput 2 }
+
+ dupsInputVoltage1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Input line 1 voltage of the UPS system in 1/10 V."
+ ::= { dupsInput 3 }
+
+ dupsInputCurrent1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Input line 1 current to the UPS system in 1/10 A."
+ ::= { dupsInput 4 }
+
+ dupsInputFrequency2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current input line 2 frequency to the UPS system
+ in 1/10 Hz."
+ ::= { dupsInput 5 }
+
+ dupsInputVoltage2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Input line 2 voltage of the UPS system in 1/10 V."
+ ::= { dupsInput 6 }
+
+ dupsInputCurrent2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Input line 2 current to the UPS system in 1/10 A."
+ ::= { dupsInput 7 }
+
+ dupsInputFrequency3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current input line 3 frequency to the UPS system
+ in 1/10 Hz."
+ ::= { dupsInput 8 }
+
+ dupsInputVoltage3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Input line 3 voltage of the UPS system in 1/10 V."
+ ::= { dupsInput 9 }
+
+ dupsInputCurrent3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Input line 3 current to the UPS system in 1/10 A."
+ ::= { dupsInput 10 }
+
+-----------------------
+-- dups Output group --
+-----------------------
+ dupsOutputSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal(0),
+ battery(1),
+ bypass(2),
+ reducing(3),
+ boosting(4),
+ manualBypass(5),
+ other(6),
+ none(7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present source of output power. The enumeration
+ none(7) indicates that there is no source of output
+ power (and therefore no output power), for example,
+ the system has opened the output breaker."
+ ::= { dupsOutput 1 }
+
+ dupsOutputFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Hertz"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present output frequency in 1/10 Hz."
+ ::= { dupsOutput 2 }
+
+ dupsOutputNumLines OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of output lines utilized in this device."
+ ::= { dupsOutput 3 }
+
+ dupsOutputVoltage1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 1 voltage of the UPS system in 1/10 V."
+ ::= { dupsOutput 4 }
+
+ dupsOutputCurrent1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 1 current of the UPS system in 1/10 A."
+ ::= { dupsOutput 5 }
+
+ dupsOutputPower1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 1 real power of the UPS system in watts."
+ ::= { dupsOutput 6 }
+
+ dupsOutputLoad1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current UPS output line 1 load expressed in percent
+ of rated capacity."
+ ::= { dupsOutput 7 }
+
+ dupsOutputVoltage2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 2 voltage of the UPS system in 1/10 V."
+ ::= { dupsOutput 8 }
+
+ dupsOutputCurrent2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 2 current of the UPS system in 1/10 A."
+ ::= { dupsOutput 9 }
+
+ dupsOutputPower2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 2 real power of the UPS system in watts."
+ ::= { dupsOutput 10 }
+
+ dupsOutputLoad2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current UPS output line 2 load expressed in percent
+ of rated capacity."
+ ::= { dupsOutput 11 }
+
+ dupsOutputVoltage3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 3 voltage of the UPS system in 1/10 V."
+ ::= { dupsOutput 12 }
+
+ dupsOutputCurrent3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 3 current of the UPS system in 1/10 A."
+ ::= { dupsOutput 13 }
+
+ dupsOutputPower3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Output line 3 real power of the UPS system in watts."
+ ::= { dupsOutput 14 }
+
+ dupsOutputLoad3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The current UPS output line 3 load expressed in percent
+ of rated capacity."
+ ::= { dupsOutput 15 }
+
+-----------------------
+-- dups Bypass group --
+-----------------------
+ dupsBypassFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Hertz"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present bypass frequency in 1/10 Hz."
+ ::= { dupsBypass 1 }
+
+ dupsBypassNumLines OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of bypass lines utilized in this device."
+ ::= { dupsBypass 2 }
+
+ dupsBypassVoltage1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 1 voltage of the UPS system in 1/10 V."
+ ::= { dupsBypass 3 }
+
+ dupsBypassCurrent1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 1 current of the UPS system in 1/10 A."
+ ::= { dupsBypass 4 }
+
+ dupsBypassPower1 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 1 real power of the UPS system in watts."
+ ::= { dupsBypass 5 }
+
+ dupsBypassVoltage2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 2 voltage of the UPS system in 1/10 V."
+ ::= { dupsBypass 6 }
+
+ dupsBypassCurrent2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 2 current of the UPS system in 1/10 A."
+ ::= { dupsBypass 7 }
+
+ dupsBypassPower2 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 2 real power of the UPS system in watts."
+ ::= { dupsBypass 8 }
+
+ dupsBypassVoltage3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 3 voltage of the UPS system in 1/10 V."
+ ::= { dupsBypass 9 }
+
+ dupsBypassCurrent3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 3 current of the UPS system in 1/10 A."
+ ::= { dupsBypass 10 }
+
+ dupsBypassPower3 OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The bypass line 3 real power of the UPS system in watts."
+ ::= { dupsBypass 11 }
+
+------------------------
+-- dups Battery group --
+------------------------
+ dupsBatteryCondiction OBJECT-TYPE
+ SYNTAX INTEGER {
+ good(0),
+ weak(1),
+ replace(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The indication of the capacity remaining in the UPS
+ system's batteries when AC normal."
+ ::= { dupsBattery 1 }
+
+ dupsBatteryStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(0),
+ low(1),
+ depleted(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The indication of the capacity remaining in the UPS
+ system's batteries when AC failed. A value of ok
+ indicates that the remaining run-time is greater than
+ upsConfigLowBattTime. A value of low indicates
+ that the remaining battery run-time is less than or
+ equal to upsConfigLowBattTime. A value of
+ depleted indicates that the UPS will be unable
+ to sustain the present load when and if the utility
+ power is lost (including the possibility that the
+ utility power is currently absent and the UPS is
+ unable to sustain the output)."
+ ::= { dupsBattery 2 }
+
+ dupsBatteryCharge OBJECT-TYPE
+ SYNTAX INTEGER {
+ floating(0),
+ charging(1),
+ resting(2),
+ discharging(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsBattery 3 }
+
+ dupsSecondsOnBattery OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "seconds"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "If the unit is on battery power, the elapsed time
+ since the UPS last switched to battery power, or the
+ time since the network management subsystem was last
+ restarted, whichever is less. Zero shall be returned
+ if the unit is not on battery power."
+ ::= { dupsBattery 4 }
+
+ dupsBatteryEstimatedTime OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "minutes"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Estimated time from backup to low battery shutdown."
+ ::= { dupsBattery 5 }
+
+ dupsBatteryVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Volt DC"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The magnitude of the present battery voltage
+ in 1/10 V."
+ ::= { dupsBattery 6 }
+
+ dupsBatteryCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "0.1 Amp DC"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The present battery current in 1/10 A."
+ ::= { dupsBattery 7 }
+
+ dupsBatteryCapacity OBJECT-TYPE
+ SYNTAX INTEGER (0..100)
+ UNITS "percent"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "An estimate of the battery charge remaining expressed
+ as a percent of full charge."
+ ::= { dupsBattery 8 }
+
+ dupsTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Centigrade"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ambient temperature at or near the UPS Battery
+ casing."
+ ::= { dupsBattery 9 }
+
+ dupsLastReplaceDate OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The last battery replacement date. The format is YYYYMMDD."
+ ::= { dupsBattery 10 }
+
+ dupsNextReplaceDate OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..8))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The next battery replacement date. The format is YYYYMMDD."
+ ::= { dupsBattery 11 }
+
+-------------------
+-- dups Test group
+-------------------
+ dupsTestType OBJECT-TYPE
+ SYNTAX INTEGER {
+ abort(0),
+ generalTest(1),
+ batteryTest(2),
+ testFor10sec(3),
+ testUntilBattlow(4)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Perform the UPS Test procedure."
+ ::= { dupsTest 1 }
+
+ dupsTestResultsSummary OBJECT-TYPE
+ SYNTAX INTEGER {
+ noTestsInitiated(0),
+ donePass(1),
+ inProgress(2),
+ generalTestFail(3),
+ batteryTestFail(4),
+ deepBatteryTestFail(5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The results of the current or last UPS diagnostics
+ test performed. The values for donePass(1),
+ generalTestFail(3), and batteryTestFail(4) indicate that the
+ test completed either successfully, with a warning, or
+ with an error, respectively.Tests which have not yet
+ concluded are indicated by inProgress(2). The value
+ noTestsInitiated(0) indicates that no previous test
+ results are available."
+ ::= { dupsTest 2 }
+
+ dupsTestResultsDetail OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Additional information about upsTestResultsSummary.
+ If no additional information available, a zero length
+ string is returned."
+ ::= { dupsTest 3 }
+
+-----------------------
+-- dups Alarm group --
+-----------------------
+ dupsAlarmDisconnect OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS disconnect?"
+ ::= { dupsAlarm 1 }
+
+ dupsAlarmPowerFail OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the input power fail?"
+ ::= { dupsAlarm 2 }
+
+ dupsAlarmBatteryLow OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Are the UPS batteries low?"
+ ::= { dupsAlarm 3 }
+
+ dupsAlarmLoadWarning OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS load percent over the load warning value?"
+ ::= { dupsAlarm 4 }
+
+ dupsAlarmLoadSeverity OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS load percent over the load severity value?"
+ ::= { dupsAlarm 5 }
+
+ dupsAlarmLoadOnBypass OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS load on bypass?"
+ ::= { dupsAlarm 6 }
+
+ dupsAlarmUPSFault OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS general fail?"
+ ::= { dupsAlarm 7 }
+
+ dupsAlarmBatteryGroundFault OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS battery ground fault?"
+ ::= { dupsAlarm 8 }
+
+ dupsAlarmTestInProgress OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS test in progress?"
+ ::= { dupsAlarm 9 }
+
+ dupsAlarmBatteryTestFail OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS test fail?"
+ ::= { dupsAlarm 10 }
+
+ dupsAlarmFuseFailure OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS fuse failure?"
+ ::= { dupsAlarm 11 }
+
+ dupsAlarmOutputOverload OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS output overload?"
+ ::= { dupsAlarm 12 }
+
+ dupsAlarmOutputOverCurrent OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS output overcurrent?"
+ ::= { dupsAlarm 13 }
+
+ dupsAlarmInverterAbnormal OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS inverter abnormal?"
+ ::= { dupsAlarm 14 }
+
+ dupsAlarmRectifierAbnormal OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS rectifier abnormal?"
+ ::= { dupsAlarm 15 }
+
+ dupsAlarmReserveAbnormal OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS reserve abnormal?"
+ ::= { dupsAlarm 16 }
+
+ dupsAlarmLoadOnReserve OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS load on reserve?"
+ ::= { dupsAlarm 17 }
+
+ dupsAlarmOverTemperature OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS over heat?"
+ ::= { dupsAlarm 18 }
+
+ dupsAlarmOutputBad OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Is the UPS output abnormal?"
+ ::= { dupsAlarm 19 }
+
+ dupsAlarmBypassBad OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Is the UPS bypass bad?"
+ ::= { dupsAlarm 20 }
+
+ dupsAlarmUPSOff OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Is the UPS in standby mode?"
+ ::= { dupsAlarm 21 }
+
+ dupsAlarmChargerFail OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS charger fail?"
+ ::= { dupsAlarm 22 }
+
+ dupsAlarmFanFail OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the UPS fan fail?"
+ ::= { dupsAlarm 23 }
+
+ dupsAlarmEconomicMode OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether the UPS is in the economic mode."
+ ::= { dupsAlarm 24 }
+
+ dupsAlarmOutputOff OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether the UPS output is turned off or not."
+ ::= { dupsAlarm 25 }
+
+ dupsAlarmSmartShutdown OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Indicates whether the Smart Shutdown is in progress."
+ ::= { dupsAlarm 26 }
+
+ dupsAlarmEmergencyPowerOff OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "UPS emergency power off."
+ ::= { dupsAlarm 27 }
+
+ dupsAlarmUPSShutdown OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "UPS shutdown."
+ ::= { dupsAlarm 28 }
+
+-----------------------
+-- dups Environment group --
+-----------------------
+
+ dupsEnvTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Centigrade"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The ambient environmental temperature."
+ ::= { dupsEnvironment 1 }
+
+ dupsEnvHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "percentage"
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The environmental humidity."
+ ::= { dupsEnvironment 2 }
+
+ dupsEnvSetTemperatureLimit OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Centigrade"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Alarm dupsAlarmOverTemperature on when the environmental
+ temperature over the value."
+ ::= { dupsEnvironment 3 }
+
+ dupsEnvSetHumidityLimit OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "percentage"
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Alarm dupsAlarmOverHumidity on when the environmental
+ humidity over the value."
+ ::= { dupsEnvironment 4 }
+
+ dupsEnvSetEnvRelay1 OBJECT-TYPE
+ SYNTAX INTEGER{
+ normalOpen(0),
+ normalClose(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsEnvironment 5 }
+
+ dupsEnvSetEnvRelay2 OBJECT-TYPE
+ SYNTAX INTEGER{
+ normalOpen(0),
+ normalClose(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsEnvironment 6 }
+
+ dupsEnvSetEnvRelay3 OBJECT-TYPE
+ SYNTAX INTEGER{
+ normalOpen(0),
+ normalClose(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsEnvironment 7 }
+
+ dupsEnvSetEnvRelay4 OBJECT-TYPE
+ SYNTAX INTEGER{
+ normalOpen(0),
+ normalClose(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsEnvironment 8 }
+
+ dupsAlarmOverEnvTemperature OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the environment over temperature?"
+ ::= { dupsEnvironment 9 }
+
+ dupsAlarmOverEnvHumidity OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Does the environment over humidity?"
+ ::= { dupsEnvironment 10 }
+
+ dupsAlarmEnvRelay1 OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsEnvironment 11 }
+
+ dupsAlarmEnvRelay2 OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsEnvironment 12 }
+
+ dupsAlarmEnvRelay3 OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsEnvironment 13 }
+
+ dupsAlarmEnvRelay4 OBJECT-TYPE
+ SYNTAX INTEGER{
+ off(0),
+ on(1)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ ""
+ ::= { dupsEnvironment 14 }
+
+-----------------------
+-- dups Trap group --
+-----------------------
+
+ dupsCommunicationLost TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: Communication with the UPS failed."
+ ::= 1
+
+ dupsCommunicationEstablished TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Communication with the UPS reestablished."
+ ::= 2
+
+ dupsPowerFail TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "WARNING: Power failed! The UPS is operating on battery power."
+ ::= 3
+
+ dupsPowerRestored TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Power restored! The utility power restored."
+ ::= 4
+
+ dupsLowBattery TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS batteries are low and will soon be exhausted."
+ ::= 5
+
+ dupsReturnFromLowBattery TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS has returned from a low battery condition."
+ ::= 6
+
+ dupsLoadWarning TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Loading percent of the UPS over the Load Warning value."
+ ::= 7
+
+ dupsNoLongerLoadWarning TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Returnd from Load Warning condition."
+ ::= 8
+
+ dupsLoadSeverity TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "Warning: Loading percent of the UPS over the Load Severity value."
+ ::= 9
+
+ dupsNoLongerLoadSeverity TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Returned from Load Severity condition."
+ ::= 10
+
+ dupsLoadOnBypass TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS loads on bypass."
+ ::= 11
+
+ dupsNoLongerLoadOnBypass TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS is not on bypass mode."
+ ::= 12
+
+ dupsUPSFault TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: A general fault caused in the UPS."
+ ::= 13
+
+ dupsReturnFromUPSFault TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS is returned from general fault."
+ ::= 14
+
+ dupsBatteryGroundFault TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS battery ground fault."
+ ::= 15
+
+ dupsNoLongerBatteryFault TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS recovered from battery ground fault."
+ ::= 16
+
+ dupsTestInProgress TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS test in progress."
+ ::= 17
+
+ dupsBatteryTestFail TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS test fail."
+ ::= 18
+
+ dupsFuseFailure TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS fuse failed."
+ ::= 19
+
+ dupsFuseRecovered TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS fuse recovered."
+ ::= 20
+
+ dupsOutputOverload TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS overload!."
+ ::= 21
+
+ dupsNoLongerOverload TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Recovered from UPS overload."
+ ::= 22
+
+ dupsOutputOverCurrent TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS output overcurrent."
+ ::= 23
+
+ dupsNoLongerOutputOverCurrent TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Recovered from UPS overcurrent."
+ ::= 24
+
+ dupsInverterAbnormal TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS inverter abnormal."
+ ::= 25
+
+ dupsInverterRecovered TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Recovered from UPS inverter abnormal."
+ ::= 26
+
+ dupsRectifierAbnormal TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS rectifier abnormal."
+ ::= 27
+
+ dupsRectifierRecovered TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS recovered from rectifier abnormal."
+ ::= 28
+
+ dupsReserveAbnormal TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS rectifier abnormal."
+ ::= 29
+
+ dupsReserveRecovered TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS rectifier abnormal."
+ ::= 30
+
+ dupsLoadOnReserve TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: The UPS load on reserve."
+ ::= 31
+
+ dupsNoLongerLoadOnReserve TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS no longer load on reserve."
+ ::= 32
+
+ dupsEnvOverTemperature TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "WARNING: The environment overtemperature."
+ ::= 33
+
+ dupsNoLongerEnvOverTemperature TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment recovered from overtemperature."
+ ::= 34
+
+ dupsEnvOverHumidity TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "WARNING: The environment overhumidity."
+ ::= 35
+
+ dupsNoLongerEnvOverHumidity TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment recovered from overhumidity."
+ ::= 36
+
+ dupsEnvRelay1Alarm TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment relay1 is not in normal state."
+ ::= 37
+
+ dupsEnvRelay1Normal TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment relay1 is in normal state."
+ ::= 38
+
+ dupsEnvRelay2Alarm TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment relay2 is not in normal state."
+ ::= 39
+
+ dupsEnvRelay2Normal TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment relay2 is in normal state."
+ ::= 40
+
+ dupsEnvRelay3Alarm TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment relay3 is not in normal state."
+ ::= 41
+
+ dupsEnvRelay3Normal TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment relay3 is in normal state."
+ ::= 42
+
+ dupsEnvRelay4Alarm TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment relay4 is not in normal state."
+ ::= 43
+
+ dupsEnvRelay4Normal TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The environment relay4 is in normal state."
+ ::= 44
+
+ dupsSmartShutdown TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: Smart Shutdown is initiated."
+ ::= 45
+
+ dupsCancelShutdown TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: Cancel UPS Shutdown."
+ ::= 46
+
+ dupsTestCompleted TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: This trap is sent upon completion of a UPS diagnostic test."
+ ::= 47
+
+ dupsEPOON TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: This trap is sent when emergency power off is on."
+ ::= 48
+
+ dupsEPOOFF TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: This trap is sent when UPS recover from emergency power off."
+ ::= 49
+
+ dupsOverTemperature TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "SEVER: This trap is sent when the UPS is over heat."
+ ::= 50
+
+ dupsNormalTemperature TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: This trap is sent when UPS recover from over heat."
+ ::= 51
+
+ dupsBattReplace TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "WARNING: The battery needs to be replaced."
+ ::= 52
+
+ dupsReturnFromBattReplace TRAP-TYPE
+ ENTERPRISE dupsTraps
+ DESCRIPTION
+ "INFORMATION: The UPS recovered from battery replacement."
+ ::= 53
+END