+-- Synso UPS Software Management Information Base
+-- SYNSO-UPSMIB
+-- {iso org(3) internet(1) private(4) enterprises(1) synso(9557)}
+
+SYNSO-UPSMIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ enterprises, IpAddress
+ FROM RFC1155-SMI
+ DisplayString
+ FROM RFC1213-MIB;
+
+
+synso OBJECT IDENTIFIER ::= {enterprises 9557}
+synsoUpsSoftware OBJECT IDENTIFIER ::= {synso 1}
+
+--
+-- The Basic Setting Group
+--
+
+syupsBasicSetting OBJECT IDENTIFIER ::= {synsoUpsSoftware 1}
+
+syupsPlatForm OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..31))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The platform which the UPS software is running on."
+ ::= {syupsBasicSetting 1}
+
+syupsFeatureTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SyupsFeatureEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A table containing the supported features."
+ ::= {syupsBasicSetting 2}
+
+syupsFeatureEntry OBJECT-TYPE
+ SYNTAX SyupsFeatureEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry representing the support information for a feature."
+ INDEX {syupsFeature}
+ ::= {syupsFeatureTable 1}
+
+SyupsFeatureEntry ::= SEQUENCE {
+ syupsFeature INTEGER,
+ syupsSupportInfo DisplayString
+}
+
+syupsFeature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The string representing a feature."
+ ::= {syupsFeatureEntry 1}
+
+syupsSupportInfo OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The string containing the support information for a feature."
+ ::= {syupsFeatureEntry 2}
+
+syupsSystemStartTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The time that the UPS software starts. It is the
+ number of seconds elapsed since 00:00:00,
+ January 1, 1970."
+ ::= {syupsBasicSetting 3}
+
+syupsSignalType OBJECT-TYPE
+ SYNTAX INTEGER {
+ basicSignal(0),
+ smartSignal(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The signaling method between the UPS and software.
+
+ When the basicSignal used, the UPS changes the voltage
+ level of some specific pins to notify the software of what
+ critical event occurs. Usually, the UPS will inform
+ software when a power failure or a low battery condition
+ occurs. On the other hand, the software can change the
+ voltage signal of a specific pin to ask the UPS to shut
+ down (turn off).
+
+ When the smartSignal used, the UPS asks like a standard
+ communication device (such as mouse or modem). That means
+ the UPS and software communicate with each other using a
+ pre-defined protocol. The protocol should include at
+ least the following commands:
+ - query the power status of the UPS
+ - query the power data of the UPS
+ - command the UPS to shut down
+ "
+ ::= {syupsBasicSetting 4}
+
+syupsBasicSignalDefinition OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The signal definitions for the basic signaling UPS. The
+ value can be the following bit combinations:
+ SG_POWER_FAILURE_ENABLE 0x01
+ SG_BATTERY_LOW_ENABLE 0x02
+ SG_SHUTDOWN_ENABLE 0x04
+
+ SG_POWER_FAILURE_VOLTHIGH 0x10
+ SG_BATTERY_LOW_VOLTHIGH 0x20
+ SG_SHUTDOWN_VOLTHIGH 0x40
+
+ SG_POWER_FAILURE_ENABLE, SG_BATTERY_LOW_ENABLE, and
+ SG_SHUTDOWN_ENABLE indicate whether the signals for
+ a power failure , a low battery condition, and the UPS
+ shutdown are enabled. SG_POWER_FAILURE_VOLTHIGH,
+ SG_BATTERY_LOW_VOLTHIGH, and SG_SHUTDOWN_VOLTHIGH indicate
+ whether the voltage level for these signals are high or low."
+ ::= {syupsBasicSetting 5}
+
+syupsUpsComPort OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The serial port which the UPS software use to communicate
+ with the UPS. The format varies from platform to platform.
+ For DOS program, the format is 'portNo, portAddress, portIRQ'
+ (e.g. '1, 0x2f8, 3' for COM2). For Windows program, it
+ is 'portNo'. For NetWare program, it is
+ 'portType, boardNo, portNo'. For UNIX, it is 'device name'."
+ ::= {syupsBasicSetting 6}
+
+syupsModemComPort OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The serial port which the UPS software use to dial out
+ when some particular events occur. The format varies from
+ platform to platform. For DOS program, the format is
+ 'portNo, portAddress, portIRQ' (e.g. '1, 0x2f8, 3' for COM2).
+ For Windows program, it is 'portNo'. For NetWare program,
+ it is 'portType, boardNo, portNo'. For UNIX, it is
+ 'device name'."
+ ::= {syupsBasicSetting 7}
+
+
+--
+-- The Ups Extension Group
+--
+
+syupsUpsExtension OBJECT IDENTIFIER ::= {synsoUpsSoftware 2}
+
+
+syupsUpsAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "It is used internally. Each bit indicates a critical event,
+ such as input bad, on battery, communications lost, ...,etc."
+ ::= {syupsUpsExtension 1}
+
+syupsSerialNo OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The serial number of the UPS connected to the UPS software."
+ ::= {syupsUpsExtension 2}
+
+syupsConfigBatteryVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The nominal battery voltage."
+ ::= {syupsUpsExtension 3}
+
+syupsBatteryReplaceDate OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The last battery replacement date. It represents the
+ number of days elapsed since January 1, 1901."
+ ::= {syupsUpsExtension 4}
+
+syupsNoOutlet OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of controllable outlets."
+ ::= {syupsUpsExtension 5}
+
+syupsOutletParamter OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "This object is not used any more."
+ ::= {syupsUpsExtension 6}
+
+syupsShutdownDepend OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string containing those who should perform their shutdown
+ procedure before the UPS turns off. The agent will inform each
+ one in the list to begin their shutdown procedure before it turns
+ off the power of the UPS."
+ ::= {syupsUpsExtension 7}
+
+syupsEnableAutoSave OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting it to 1, the agent will try to save all files opened by
+ applications before shutting down the operation system. Setting it
+ to 0 will disable the auto save feature."
+ ::= {syupsUpsExtension 8}
+
+syupsShutdownOsDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay time before shutting down the operation system.
+ When it is necessary to shut down the operation system, the agent
+ will run the specified command file and try to save all files
+ opened by applications before shutting down the OS. This delay
+ time is used to do such things."
+ ::= {syupsUpsExtension 9}
+
+syupsShutdownUpsDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay time before shutting down the UPS. Before shutting down
+ the operation system, the agent will send a command to tell the UPS
+ to shut down. This delay time is used to allow the agent to shut down
+ the operation system safely."
+ ::= {syupsUpsExtension 10}
+
+syupsSaveConfig OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Used to inform the agnet to save the configurations. Its value indicates
+ which group to be saved. For example, a 1 indicates group 1 (syupsBasicSetting)
+ to be saved, a 6 1 indicates group 6 (syupsCoworker) to be saved. You have to
+ use it to save configurations after changing settings, or the settings may be
+ lost."
+ ::= {syupsUpsExtension 11}
+
+syupsNoOutlets OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of controllable outlets."
+ ::= {syupsUpsExtension 12}
+
+
+syupsOutletTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF syupsOutletEntry
+ MAX-ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of outlet table entries. The number of entries
+ is given by the value of syupsNoOutlets."
+ ::= {syupsUpsExtension 13}
+
+syupsOutletEntry OBJECT-TYPE
+ SYNTAX SyupsOutletEntry
+ MAX-ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular controllable outlet."
+ INDEX { syupsOutletIndex }
+ ::= {syupsOutletTable 1}
+
+syupsOutletEntry ::= SEQUENCE {
+ syupsOutletIndex INTEGER,
+ syupsOutletDescription DisplayString (SIZE (0..15)),
+ syupsOutletShutdownDelay INTEGER,
+ syupsOutletShutdownDepend DisplayString (SIZE (0..63))
+ }
+
+syupsOutletIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet identifier."
+ ::= {syupsOutletEntry 1}
+
+syupsOutletDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The outlet description."
+ ::= {syupsOutletEntry 2}
+
+syupsOutletShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The delay time (in seconds) before turning off the outlet.
+ Before turning off the outlet, the agent will send a shutdown
+ command to anyone specified in the syupsOutletShutdownDepend,
+ telling them to start their shutdown procedure. This delay
+ time is used to allow those cmputers to be shut down safely."
+ ::= {syupsOutletEntry 3}
+
+syupsOutletShutdownDepend OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ MAX-ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string containing those who should perform their shutdown
+ procedure before the outlet turns off. The agent will inform each
+ one in the list to begin their shutdown procedure before it turns
+ off the power of the outlet."
+ ::= {syupsOutletEntry 4}
+
+syupsOutletOperator OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The operator is used to control the outlets. There are two commands:
+ 1. 'SWITCH: OutletNo, OnOff'.
+ The OutletNo specify the outlet.
+ The OnOff can be 0 (off) or 1 (on).
+ For example, 'SWITCH: 2, 1' means turning on (1) the outlet #2.
+ 'SWITCH: 4, 0' means turning off (0) the outlet #4.
+ 2. 'SET: OutletNo, Desc, DelayTime, Depend'.
+ The OutletNo specify the outlet.
+ The Desc specifies the outlet description.
+ The DelayTime specifies the shutdown delay time for the outlet.
+ The Depend specifies the shutdown dependent list for the outlet.
+ For example, 'SET: 3, My Printer, 20, 192.168.1.9' means setting
+ the description of outlet #3 to 'My Printer', the shutdown delay
+ time to 20 seconds and the Shutdown Dependent to '192.168.1.9'."
+ ::= {syupsUpsExtension 14}
+
+--
+-- The Event Action Group
+--
+
+syupsEventAction OBJECT IDENTIFIER ::= {synsoUpsSoftware 3}
+
+syupsNoEventActionEntries OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of event-action items. This variable indicates
+ the number of rows in the event-action table."
+ ::= {syupsEventAction 1}
+
+syupsEventActionTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SyupsEventActionEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of event action entries. The number of entries
+ is given by the value of syupsNoEventActionEntries."
+ ::= {syupsEventAction 2}
+
+syupsEventActionEntry OBJECT-TYPE
+ SYNTAX SyupsEventActionEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular event action."
+ INDEX {syupsEventId}
+ ::= {syupsEventActionTable 1}
+
+SyupsEventActionEntry ::= SEQUENCE {
+ syupsEventId INTEGER,
+ syupsLogEnable INTEGER,
+ syupsNotifyEnable INTEGER,
+ syupsNotifyDelay INTEGER,
+ syupsNotifyMessage DisplayString (SIZE(0..63)),
+ syupsNotifyPeriod INTEGER,
+ syupsNotifyUsers DisplayString (SIZE(0..255)),
+ syupsEmailEnable INTEGER,
+ syupsEmailDelay INTEGER,
+ syupsEmailMessage DisplayString (SIZE(0..63)),
+ syupsEmailUsers DisplayString (SIZE(0..255)),
+ syupsPageEnable INTEGER,
+ syupsPageDelay INTEGER,
+ syupsPageMessage DisplayString (SIZE(0..63)),
+ syupsPageUsers DisplayString (SIZE(0..255)),
+ syupsCommandEnable INTEGER,
+ syupsCommandDelay INTEGER,
+ syupsCommandFile DisplayString (SIZE(0..255)),
+ syupsShutdownEnable INTEGER,
+ syupsShutdownDelay INTEGER
+}
+
+syupsEventId OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The event ID."
+ ::= {syupsEventActionEntry 1}
+
+syupsLogEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Whether to log the event in the log file when it occurs.
+ A 1 indicates enable, a 0 indicates disable."
+ ::= {syupsEventActionEntry 2}
+
+syupsNotifyEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Whether to notify users when the event occurs.
+ A 1 indicates enable, a 0 indicates disable."
+ ::= {syupsEventActionEntry 3}
+
+syupsNotifyDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long the event must last before notifying users."
+ ::= {syupsEventActionEntry 4}
+
+syupsNotifyMessage OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The message which will be sent when the event occurs."
+ ::= {syupsEventActionEntry 5}
+
+syupsNotifyPeriod OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How often (in seconds) to send the message. The -1 means once."
+ ::= {syupsEventActionEntry 6}
+
+syupsNotifyUsers OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Who will receive the message when the event occurs."
+ ::= {syupsEventActionEntry 7}
+
+syupsEmailEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Whether to email users when the event occurs.
+ A 1 indicates enable, a 0 indicates disable."
+ ::= {syupsEventActionEntry 8}
+
+syupsEmailDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long the event must last before emailing users."
+ ::= {syupsEventActionEntry 9}
+
+syupsEmailMessage OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The additional message which will be sent when the event occurs."
+ ::= {syupsEventActionEntry 10}
+
+syupsEmailUsers OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Who will receive the mail when the event occurs."
+ ::= {syupsEventActionEntry 11}
+
+syupsPageEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Whether to page users when the event occurs.
+ A 1 indicates enable, a 0 indicates disable."
+ ::= {syupsEventActionEntry 12}
+
+syupsPageDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long the event must last before paging users."
+ ::= {syupsEventActionEntry 13}
+
+syupsPageMessage OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The message which will be sent when the event occurs."
+ ::= {syupsEventActionEntry 14}
+
+syupsPageUsers OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..255))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Who will receive the code when the event occurs."
+ ::= {syupsEventActionEntry 15}
+
+syupsCommandEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Whether to execute the external command file when the event occurs.
+ A 1 indicates enable, a 0 indicates disable."
+ ::= {syupsEventActionEntry 16}
+
+syupsCommandDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long the event must last before executing the external command file."
+ ::= {syupsEventActionEntry 17}
+
+syupsCommandFile OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The external command file which will be executed when the event occurs."
+ ::= {syupsEventActionEntry 18}
+
+syupsShutdownEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Whether to shut down the system when the event occurs.
+ A 1 indicates enable, a 0 indicates disable."
+ ::= {syupsEventActionEntry 19}
+
+syupsShutdownDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "How long the event must last before shutting down the system."
+ ::= {syupsEventActionEntry 20}
+
+
+--
+-- The History Group
+--
+
+syupsHistory OBJECT IDENTIFIER ::= {synsoUpsSoftware 4}
+
+syupsMaxEventFileLength OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum length (in bytes) of the event log file.
+ UPS software will cut the first half of the file whenever
+ the file exceeds this maximum length."
+ ::= {syupsHistory 1}
+
+syupsEventNumRecords OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of records in the event log file."
+ ::= {syupsHistory 2}
+
+syupsEventTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SyupsEventEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of event entries. Each entry represents a record
+ in the event log file."
+ ::= {syupsHistory 3}
+
+syupsEventEntry OBJECT-TYPE
+ SYNTAX SyupsEventEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry representing a record in the event log file."
+ INDEX {syupsEventIndex}
+ ::= {syupsEventTable 1}
+
+SyupsEventEntry ::= SEQUENCE {
+ syupsEventIndex INTEGER,
+ syupsEventRecord DisplayString
+}
+
+syupsEventIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The record number of an event entry."
+ ::= {syupsEventEntry 1}
+
+syupsEventRecord OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The string containing an event entry."
+ ::= {syupsEventEntry 2}
+
+syupsDataRecordInterval OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The number of minutes to wait between each
+ recording to the data log file."
+ ::= {syupsHistory 4}
+
+syupsMaxDataFileLength OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The maximum length (in bytes) of the data log file.
+ UPS software will cut the first half of the file whenever
+ the file exceeds this maximum length."
+ ::= {syupsHistory 5}
+
+syupsDataNumRecords OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of records in the data log file."
+ ::= {syupsHistory 6}
+
+syupsDataTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SyupsDataEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of data entries. Each entry represents a record
+ in the data log file."
+ ::= {syupsHistory 7}
+
+syupsDataEntry OBJECT-TYPE
+ SYNTAX SyupsDataEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An entry representing a record in the data log file."
+ INDEX {syupsDataIndex}
+ ::= {syupsDataTable 1}
+
+SyupsDataEntry ::= SEQUENCE {
+ syupsDataIndex INTEGER,
+ syupsDataRecord DisplayString
+}
+
+syupsDataIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The record number of a data entry."
+ ::= {syupsDataEntry 1}
+
+syupsDataRecord OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The string containing a data entry."
+ ::= {syupsDataEntry 2}
+
+syupsHistoryOperator OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The operator which is used to operate on the
+ history file. The command format is
+ 'Command, File, Range'. So far, Command can be
+ PURGE, File can be EVENT or DATA, and Range can be
+ ALL or 'mm/dd/year..mm/dd/year'. For example,
+ 'PURGE, EVENT, ALL' tells the UPS software to purge
+ all entries in the event log file. And
+ 'PURGE, DATA, 03/20/1995..07/02/1995' tells the UPS
+ software to purge the entries which are recorded
+ form 03/20/1995 to 07/20/1995 from the event log
+ file."
+ ::= {syupsHistory 8}
+
+syupsScopeSettings OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The string contains the settings for UPS Scope Chart,
+ including Value Original Point, Value Unit, Time Unit,
+ Time Interval, and Display Items. The format for the
+ settings string is '%d, %d, %d, %d, %d'. Display Items can
+ be any one or any combination of the following items:
+ SCOPE_INPUT_VOLT 0x0001
+ SCOPE_OUTPUT_VOLT 0x0010
+ SCOPE_INPUT_FREQ 0x0100
+ SCOPE_OUTPUT_FREQ 0x1000
+ "
+ ::= {syupsHistory 9}
+
+
+
+--
+-- The Schedule Group
+--
+
+syupsSchedule OBJECT IDENTIFIER ::= {synsoUpsSoftware 5}
+
+syupsNoSchEntries OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of schedule entries."
+ ::= {syupsSchedule 1}
+
+syupsSchOperator OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The operator which is used to operate on the
+ schedule table. There are three commands:
+ 1. 'ADD: action, mm/dd/yyyy, hh:mm:ss,
+ week_day, repeat' indicates to add a new entry
+ to the schedule list.
+ 2. 'REPLACE: i, action, mm/dd/yyyy, hh:mm:ss,
+ week_day, repeat' indicates to replace the
+ i-th entry in the table with the new settings.
+ 3. 'DELETE:n1, n2' indicates to delete the entries
+ ranging from number n1 to number n2 from the schedule
+ table.
+ 'action' could be the following:
+ General System Test (1)
+ Quick Battery Test (2)
+ Deep Battery Test (3)
+ Turn On UPS (11)
+ Turn Off UPS (21)
+ Turn On Outlet (100+x)
+ Turn Off Outlet (200+x)
+ where x indicates the outlet number.
+ 'mm/dd/year' and 'hh:mm:ss' specify the action's
+ starting time. 'repeat' indicates the frequency
+ of the action, it could be Once(1), Daily(2),
+ Weekly(3) and Monthly(4). 'week_day' indicating the
+ day of week is meaningful only when the repeat is
+ set to Weekly, and it could be Sun(0), Mon(1), ...,
+ and Sat(6).
+ For example, '1, 07/08/1994, 15:30:00, 0, 4'
+ indicates that the UPS will do a General System Test
+ at 3:30 PM every month from July 8, 1994.
+ '203, 06/20/1995, 07:00:00, 0, 1' indicates that the UPS
+ will turn off outlet #3 at 7 o'clock on June 20, 1995 and
+ do it only once."
+ ::= {syupsSchedule 2}
+
+syupsSchTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SyupsSchEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of schedule entries."
+ ::= {syupsSchedule 3}
+
+syupsSchEntry OBJECT-TYPE
+ SYNTAX SyupsSchEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A schedule entry."
+ INDEX {syupsSchIndex}
+ ::= {syupsSchTable 1}
+
+SyupsSchEntry ::= SEQUENCE {
+ syupsSchIndex INTEGER,
+ syupsSchStartDate DisplayString,
+ syupsSchStartTime DisplayString,
+ syupsSchWeekDay INTEGER,
+ syupsSchAction INTEGER,
+ syupsSchRepeat INTEGER
+}
+
+syupsSchIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The entry number of a schedule setting."
+ ::= {syupsSchEntry 1}
+
+syupsSchStartDate OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The starting date (mm/dd/yyyy) of the schedule entry."
+ ::= {syupsSchEntry 2}
+
+syupsSchStartTime OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The starting time (hh:mm:ss) of the schedule entry."
+ ::= {syupsSchEntry 3}
+
+syupsSchWeekDay OBJECT-TYPE
+ SYNTAX INTEGER {
+ sunday(0),
+ monday(1),
+ tuesday(2),
+ wednesday(3),
+ thursday(4),
+ friday(5),
+ saturday(6)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The starting day of week for the schedule entry. It could
+ be Sun(0), Mon(1), ..., and Sat(6). It is used when syupsSchRepeat
+ is set to weekly."
+ ::= {syupsSchEntry 4}
+
+syupsSchAction OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The action of the schedule entry. It could be:
+ General System Test (1)
+ Quick Battery Test (2)
+ Deep Battery Test (3)
+ Turn On UPS (11)
+ Turn Off UPS (21)
+ Turn On Outlet (100+x)
+ Turn Off Outlet (200+x)
+ where x indicates the outlet number."
+ ::= {syupsSchEntry 5}
+
+syupsSchRepeat OBJECT-TYPE
+ SYNTAX INTEGER {
+ once(1),
+ daily(2),
+ weekly(3),
+ monthly(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "It indicates the frequency of the action, it could be
+ Once(1), Daily(2), Weekly(3) and Monthly(4)."
+ ::= {syupsSchEntry 6}
+
+
+--
+-- The Co-worker Group
+--
+
+syupsCoworker OBJECT IDENTIFIER ::= {synsoUpsSoftware 6}
+
+syupsNoAccessControl OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of access control entries."
+ ::= {syupsCoworker 1}
+
+syupsAccessControlOperator OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The operator which is used to operate on the
+ access control table. There are three commands:
+ 1. 'ADD: community' indicates
+ to add a new entry to the access control list.
+ 2. 'REPLACE: x, community'
+ indicates to replace the x-th entry in the table
+ with the new settings.
+ 3. 'DELETE:n1, n2' indicates to delete the entries
+ from number n1 to number n2 from the access control
+ table."
+ ::= {syupsCoworker 2}
+
+syupsAccessControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SyupsAccessControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of access control entries. Only entries in this list
+ can have access to the agent."
+ ::= {syupsCoworker 3}
+
+syupsAccessControlEntry OBJECT-TYPE
+ SYNTAX SyupsAccessControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An access control entry."
+ INDEX {syupsAccessControlIndex}
+ ::= {syupsAccessControlTable 1}
+
+SyupsAccessControlEntry ::= SEQUENCE {
+ syupsAccessControlIndex INTEGER,
+ syupsAccessControlSetting DisplayString
+}
+
+syupsAccessControlIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The entry number of a access control setting."
+ ::= {syupsAccessControlEntry 1}
+
+syupsAccessControlSetting OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A string containing the community name."
+ ::= {syupsAccessControlEntry 2}
+
+
+syupsNoTrapReceiver OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The total number of trap receiver entries."
+ ::= {syupsCoworker 4}
+
+syupsTrapReceiverOperator OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The operator which is used to operate on the
+ trap receiver table. There are three commands:
+ 1. 'ADD: ipAddress' indicates to add a new
+ entry to the trap receiver list.
+ 2. 'REPLACE: x, ipAddress' indicates to replace
+ the x-th entry in the table with the new settings.
+ 3. 'DELETE:n1, n2' indicates to delete the entries
+ from number n1 to number n2 from the trap receiver
+ table."
+ ::= {syupsCoworker 5}
+
+syupsTrapReceiverTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SyupsTrapReceiverEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of trap receiver entries. When an important event
+ occurs, the agent will send traps to all the entries in the
+ list."
+ ::= {syupsCoworker 6}
+
+syupsTrapReceiverEntry OBJECT-TYPE
+ SYNTAX SyupsTrapReceiverEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "An trap receiver entry."
+ INDEX {syupsTrapReceiverIndex}
+ ::= {syupsTrapReceiverTable 1}
+
+SyupsTrapReceiverEntry ::= SEQUENCE {
+ syupsTrapReceiverIndex INTEGER,
+ syupsTrapReceiverSetting DisplayString
+}
+
+syupsTrapReceiverIndex OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The entry number of a trap receiver setting."
+ ::= {syupsTrapReceiverEntry 1}
+
+syupsTrapReceiverSetting OBJECT-TYPE
+ SYNTAX DisplayString
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "A string containing a trap receiver's IP address."
+ ::= {syupsTrapReceiverEntry 2}
+
+
+--
+-- notifications, i.e., traps
+--
+syupsTraps OBJECT IDENTIFIER ::= { synsoUpsSoftware 7 }
+
+-- This section defines the extension notifications sent by
+-- UPS agents.
+
+syupsTrapOverTemperature NOTIFICATION-TYPE
+ OBJECTS { upsBatteryTemperature }
+ STATUS current
+ DESCRIPTION
+ "The battery temperature is too high. This trap is
+ persistent and is resent at one minute intervals until
+ the UPS either turns off or the status is no longer
+ present."
+ ::= { syupsTraps 1 }
+
+syupsTrapOverCurrent NOTIFICATION-TYPE
+ OBJECTS { upsInputCurrent }
+ STATUS current
+ DESCRIPTION
+ "The current is too high. This trap is
+ persistent and is resent at one minute intervals until
+ the UPS either turns off or the status is no longer
+ present."
+ ::= { syupsTraps 2 }
+
+syupsTrapOverVoltage NOTIFICATION-TYPE
+ OBJECTS { upsInputVoltage }
+ STATUS current
+ DESCRIPTION
+ "The voltage is too high. This trap is
+ persistent and is resent at one minute intervals until
+ the UPS either turns off or the status is no longer
+ present."
+ ::= { syupsTraps 3 }
+
+syupsTrapUnderVoltage NOTIFICATION-TYPE
+ OBJECTS { upsInputVoltage }
+ STATUS current
+ DESCRIPTION
+ "The voltage is too low. This trap is
+ persistent and is resent at one minute intervals until
+ the UPS either turns off or the status is no longer
+ present."
+ ::= { syupsTraps 4 }
+
+syupsOffFrequency NOTIFICATION-TYPE
+ OBJECTS { upsInputFrequency }
+ STATUS current
+ DESCRIPTION
+ "The frequency is abnormal. This trap is
+ persistent and is resent at one minute intervals until
+ the UPS either turns off or the status is no longer
+ present."
+ ::= { syupsTraps 5 }
+
+syupsLowBattery NOTIFICATION-TYPE
+ OBJECTS { upsBatteryStatus, upsBatteryVoltage }
+ STATUS current
+ DESCRIPTION
+ "The battery is too low. This trap is
+ persistent and is resent at one minute intervals until
+ the UPS either turns off or the status is no longer
+ present."
+ ::= { syupsTraps 6 }
+
+syupsBadBattery NOTIFICATION-TYPE
+ OBJECTS { upsBatteryStatus, upsBatteryVoltage }
+ STATUS current
+ DESCRIPTION
+ "The battery is bad. This trap is
+ persistent and is resent at one minute intervals until
+ the UPS either turns off or the status is no longer
+ present."
+ ::= { syupsTraps 7 }
+
+END