diff --git a/MIBS/rittal/RITTAL-CMC-TC-MIB b/MIBS/rittal/RITTAL-CMC-TC-MIB new file mode 100644 index 0000000..7584096 --- /dev/null +++ b/MIBS/rittal/RITTAL-CMC-TC-MIB @@ -0,0 +1,3959 @@ +-- RITTAL GmbH & Co. KG, Herborn
+-- CMC-TC-MIB Version 1.1h
+-- CMC-TC - DK7320.100
+--
+-- Management Information Base for SNMP Network Management
+--
+-- Copyright 2002 - 2007 Rittal Herborn.
+-- All Rights Reserved.
+--
+-- The information in this document is subject to change without notice.
+-- Refer to document "AGB_Software_Rittal.pdf"
+--
+--*********************************************************************
+-- Release History
+-- Date: October 17, 2002 (Version 1.0)
+-- Revised by MHain
+-- Date: April 1, 2003 (Version 1.1)
+-- Added: unitXMsgQuit, cmcTcControl, Sensor types, Output types, Unit types
+-- Date: November 3, 2003 (Version 1.1a)
+-- Added: new sensors, new outputs (FCS, RTT)
+-- Date: March 11, 2004 (Version 1.1b)
+-- Added: new sensors, new outputs, new messages (RCT, PSM)
+-- Date: Jan 11, 2006 (Version 1.1c)
+-- Changed: sysName... FROM RFC1213-MIB, seperate lines, for HP SIM
+-- Date: Jan 24, 2006 (Version 1.1d)
+-- Added: new unit type (ActivePSM8)
+-- Added: new output type (power output 16/20A)
+-- Date: Dec 5, 2006 (Version 1.1e)
+-- Added: sensor/output types MeteredPSM, LCP
+-- Date: March 8, 2007 (Version 1.1f)
+-- Changed: Output names (RTT, Power Out)
+-- Date: March 22, 2007 (Version 1.1g)
+-- Changed: New sensor units, wireless sensors, timer function SMS
+-- Date: July 23, 2007 (Version 1.1h)
+-- Added: New sensors/outputs LCP
+--*********************************************************************
+
+ RITTAL-CMC-TC-MIB DEFINITIONS ::= BEGIN
+
+ IMPORTS
+ enterprises FROM RFC1155-SMI
+ DisplayString FROM RFC1213-MIB
+ sysName FROM RFC1213-MIB
+ sysDescr FROM RFC1213-MIB
+ sysContact FROM RFC1213-MIB
+ sysLocation FROM RFC1213-MIB
+
+ OBJECT-TYPE FROM RFC-1212
+ TRAP-TYPE FROM RFC-1215;
+
+ rittal OBJECT IDENTIFIER ::= { enterprises 2606 }
+ cmcTc OBJECT IDENTIFIER ::= { rittal 4 }
+ cmcTcMibRev OBJECT IDENTIFIER ::= { cmcTc 1 }
+ cmcTcStatus OBJECT IDENTIFIER ::= { cmcTc 2 }
+ cmcTcStatusSensorUnit1 OBJECT IDENTIFIER ::= { cmcTcStatus 3 }
+ cmcTcStatusUnit1Sensors OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit1 5 }
+ cmcTcStatusUnit1Outputs OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit1 6 }
+ cmcTcStatusUnit1Msg OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit1 7 }
+ cmcTcStatusSensorUnit2 OBJECT IDENTIFIER ::= { cmcTcStatus 4 }
+ cmcTcStatusUnit2Sensors OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit2 5 }
+ cmcTcStatusUnit2Outputs OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit2 6 }
+ cmcTcStatusUnit2Msg OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit2 7 }
+ cmcTcStatusSensorUnit3 OBJECT IDENTIFIER ::= { cmcTcStatus 5 }
+ cmcTcStatusUnit3Sensors OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit3 5 }
+ cmcTcStatusUnit3Outputs OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit3 6 }
+ cmcTcStatusUnit3Msg OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit3 7 }
+ cmcTcStatusSensorUnit4 OBJECT IDENTIFIER ::= { cmcTcStatus 6 }
+ cmcTcStatusUnit4Sensors OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit4 5 }
+ cmcTcStatusUnit4Outputs OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit4 6 }
+ cmcTcStatusUnit4Msg OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit4 7 }
+ cmcTcStatusExtUnit OBJECT IDENTIFIER ::= { cmcTcStatus 7 }
+ cmcTcSetup OBJECT IDENTIFIER ::= { cmcTc 3 }
+ cmcTcSetupGeneral OBJECT IDENTIFIER ::= { cmcTcSetup 1 }
+ cmcTcTimerTable1 OBJECT IDENTIFIER ::= { cmcTcSetupGeneral 8 }
+ cmcTcTrapControl OBJECT IDENTIFIER ::= { cmcTc 4 }
+ cmcTcTraps OBJECT IDENTIFIER ::= { cmcTcTrapControl 7 }
+ cmcTcControl OBJECT IDENTIFIER ::= { cmcTc 5 }
+
+
+--*****************************************************************************
+--CMC-TC ComputerMultiControl-TopConcept DK7320.100
+--*****************************************************************************
+--cmcTcMibRev-group
+
+ cmcTcMibMajRev OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Major Revision level.
+ A change in the major revision level represents a major change
+ in the architecture of the MIB. A change in the major revision
+ level may indicate a significant change in the information,
+ correct interpretation of data may require a MIB document
+ with the same major revision level."
+ ::= { cmcTcMibRev 1 }
+
+ cmcTcMibMinRev OBJECT-TYPE
+ SYNTAX INTEGER (0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The Minor Revision level.
+ A change in the minor revision level may represent some minor
+ additional support, no changes to any pre-existing information
+ has occurred."
+ ::= { cmcTcMibRev 2 }
+
+ cmcTcMibCondition OBJECT-TYPE
+ SYNTAX INTEGER {
+ other (1),
+ ok (2),
+ degraded (3),
+ failed (4),
+ configChanged (5)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The overall condition (status) of the system represented by
+ this MIB.
+ (2) OK
+ (3) a minor problem, warning condition (yellow LED on CMC)
+ (4) a major problem (red LED on CMC)
+ (5) configuration of sensor units changed or
+ unit detected (red/yellow/green LED on CMC)"
+ ::= { cmcTcMibRev 3 }
+
+
+
+--status-group
+ cmcTcStatusDeviceCMC OBJECT-TYPE
+ SYNTAX INTEGER {
+ failed(1),
+ ok(2)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "General Status of CMC-TC unit itself
+ (1) failed
+ (2) OK"
+ ::= { cmcTcStatus 1 }
+
+ cmcTcUnitsConnected OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of sensor units connected to the CMC, Port 1 to 4"
+ ::= { cmcTcStatus 2 }
+
+
+--status sensor units-group
+
+--unit 1
+ cmcTcUnit1TypeOfDevice OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ unitIO (2),
+ unitAccess (3),
+ unitClimate (4),
+ unitFCS (5),
+ unitRTT (6),
+ unitRCT (7),
+ unitPSM (8),
+ unitPSM8 (9),
+ unitPSMMetered (10),
+ unitIOWireless (11),
+ unitPSM6Schuko (12),
+ unitPSM6C19 (13)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of sensor unit connected to port 1"
+ ::= { cmcTcStatusSensorUnit1 1 }
+
+ cmcTcUnit1Text OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..10))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for sensor unit connected to port 1"
+ ::= { cmcTcStatusSensorUnit1 2 }
+
+ cmcTcUnit1Serial OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Serialnumber of sensor unit connected to port 1"
+ ::= { cmcTcStatusSensorUnit1 3 }
+
+ cmcTcUnit1Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(1),
+ error(2),
+ changed(3),
+ quit(4),
+ timeout(5),
+ detected(6),
+ notAvail(7),
+ lowPower(8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "General Status sensor unit connected to port 1
+ (1) OK
+ (2) error, e. g. value overflow
+ (3) configuration of sensor unit has changed, confirmation required
+ (4) Quit from sensor unit to confirm configuration changes
+ (5) timeout of sensor unit, confirmation required to unload this unit
+ (6) sensor unit detected, needs to be confirmed
+ (7) unit is not available
+ (8) supply voltage is too low"
+ ::= { cmcTcStatusSensorUnit1 4 }
+
+-- Sensors
+ cmcTcUnit1NumberOfSensors OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of sensors connected to sensor unit 1"
+ ::= { cmcTcStatusUnit1Sensors 1 }
+
+-- table with entry for each sensor available on this unit
+ cmcTcUnit1SensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit1SensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of sensor table"
+ ::= { cmcTcStatusUnit1Sensors 2 }
+
+ cmcTcUnit1SensorEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit1SensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of sensor table"
+ INDEX { unit1SensorIndex }
+ ::= { cmcTcUnit1SensorTable 1 }
+
+ CmcTcUnit1SensorEntry ::=
+ SEQUENCE {
+ unit1SensorIndex
+ INTEGER,
+ unit1SensorType
+ INTEGER,
+ unit1SensorText
+ DisplayString,
+ unit1SensorStatus
+ INTEGER,
+ unit1SensorValue
+ INTEGER,
+ unit1SensorSetHigh
+ INTEGER,
+ unit1SensorSetLow
+ INTEGER,
+ unit1SensorSetWarn
+ INTEGER
+ }
+
+ unit1SensorIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of value entries. Its value ranges
+ between 1 and the value of cmcTcUnit1NumberOfSensors."
+ ::= { cmcTcUnit1SensorEntry 1 }
+
+ unit1SensorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ failure (2),
+ overflow (3),
+ access (4),
+ vibration (5),
+ motion (6),
+ smoke (7),
+ airFlow (8),
+ type6 (9),
+ temperature(10),
+ current4to20(11),
+ humidity(12),
+ userNO (13),
+ userNC (14),
+ lock (15),
+ unlock (16),
+ voltOK (17),
+ voltage (18),
+ fanOK (19),
+ readerKeypad (20),
+ dutyPWM (21),
+ fanStatus (22),
+ leakage (23),
+ warningRTT (24),
+ alarmRTT (25),
+ filterRTT (26),
+ heatflowRCT (27),
+ alarmRCT (28),
+ warningRCT (29),
+ currentPSM (30),
+ statusPSM (31),
+ positionPSM (32),
+ airFlap (33),
+ acoustic (34),
+ detACfault (35),
+ detACfirstAlarm (36),
+ detACmainAlarm (37),
+ rpm11LCP (40),
+ rpm12LCP (41),
+ rpm21LCP (42),
+ rpm22LCP (43),
+ rpm31LCP (44),
+ rpm32LCP (45),
+ rpm41LCP (46),
+ rpm42LCP (47),
+ airTemp11LCP (48),
+ airTemp12LCP (49),
+ airTemp21LCP (50),
+ airTemp22LCP (51),
+ airTemp31LCP (52),
+ airTemp32LCP (53),
+ airTemp41LCP (54),
+ airTemp42LCP (55),
+ temp1LCP (56),
+ temp2LCP (57),
+ waterInTemp (58),
+ waterOutTemp (59),
+ waterFlow (60),
+ fanSpeed (61),
+ valve (62),
+ statusLCP (63),
+ waterDelta (64),
+ valveActual (65),
+ contrTemp2 (66),
+ condensateDuration (67),
+ condensateCycles (68),
+ totalKWhPSM (72),
+ totalKWPSM (73),
+ frequencyPSM (74),
+ voltagePSM (75),
+ voltStatusPSM (76),
+ amperePSM (77),
+ ampStatusPSM (78),
+ kWPSM (79),
+ kWhPSM (80),
+ kWhTempPSM (81),
+ temperatureWL (100),
+ temperature1WL (101),
+ humidityWL (102),
+ accessWL (103),
+ userNOWL (104),
+ userNCWL (105),
+ analogWL (106)
+ }
+
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex]
+ 1: no sensor connected
+ 2: sensor failure
+ 3: value overflow
+ 4: sensor type 1, access sensor
+ 5: sensor type 2, vibration sensor
+ 6: sensor type 3, motion sensor
+ 7: sensor type 4, smoke sensor
+ 8: sensor type 5, air flow sensor
+ 9: sensor type 6, reserved
+ 10: sensor type 7, temperature sensor
+ 11: sensor type 8, 4..20mA sensor
+ 12: sensor type 9, humidity sensor
+ 13: user sensor with normally opened contact
+ 14: user sensor with normally closed contact
+ 15: door locked sensor from locking device
+ 16: remote unlock sensor (e.g. external keypad)
+ 17: voltage sensor, indicates status of main voltage (OK, NOK)
+ 18: voltage value
+ 19: fan status, from CMC-TC-FAS-Unit
+ 20: cardreader or keypad, connected to I2C port
+ 21: duty cycle of fan, FCS-Unit
+ 22: status of fan, FCS-Unit
+ 23: leakage sensor
+ 24: warning, RittalTopTherm(RTT)-Unit
+ 25: alarm, RittalTopTherm-Unit
+ 26: temperature difference filter monitor, RTT-Unit
+ 27: heatflow RCT-Unit
+ 28: alarm RCT-Unit
+ 29: warning RCT-Unit
+ 30: actual current*10, PSM-Unit
+ 31: status PSM-Unit
+ 32: position PSM-Unit, normal/reversed = circuit 1/2
+ 33: air Flap
+ 34: acoustic sensor
+ 35: DET-AC fault (extinguisher)
+ 36: DET-AC first alarm (extinguisher)
+ 37: DET-AC main alarm (extinguisher)
+ 40-47: RPM Fan 1.1 - Fan 4.2, LCP
+ 48-55: Air temperature 1.1 - 4.2, LCP
+ 56,57: actual temperature 1,2, LCP
+ 58: water inlet temperature, LCP
+ 59: water outlet temperature, LCP
+ 60: water flow
+ 61: fan speed (desired value)
+ 62: status valve, LCP
+ 63: status LCP
+ 64: temperature difference water temperatures
+ 65: control temperature 1, LCP
+ 66: control temperature 2, LCP
+ 67: condensate pump, duration, LCP
+ 68: condensate pump, cycles, LCP
+ 72: total energy*10 (kWh), PSM
+ 73: total power*10 (kW), PSM
+ 74: frequency*10 (Hz), PSM
+ 75: voltage*10 (V), PSM
+ 76: voltage status, PSM
+ 77: current*10 (A), PSM
+ 78: current status, PSM
+ 79: power*10 (kW) per phase, PSM
+ 80: energy*10 (kWh) per phase, PSM
+ 81: temporary energy*10 (kWh) per phase, PSM
+ 100: temperature sensor, wireless
+ 101: temperature sensor (combi), wireless
+ 102: humidity sensor, wireless
+ 103: access sensor, wireless
+ 104: user sensor with normally opened contact, wireless
+ 105: user sensor with normally closed contact, wireless
+ 106: analog sensor 4..20mA, wireless"
+ ::= { cmcTcUnit1SensorEntry 2 }
+
+ unit1SensorText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each sensor (entry in the table)"
+ ::= { cmcTcUnit1SensorEntry 3 }
+
+ unit1SensorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ off(5),
+ on(6),
+ warning(7),
+ tooLow(8),
+ tooHigh(9)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the sensor"
+ ::= { cmcTcUnit1SensorEntry 4 }
+
+ unit1SensorValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Value of sensor"
+ ::= { cmcTcUnit1SensorEntry 5 }
+
+ unit1SensorSetHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for high setpoint of sensor"
+ ::= { cmcTcUnit1SensorEntry 6 }
+
+ unit1SensorSetLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for low setpoint of sensor,
+ also used as alarm delay"
+ ::= { cmcTcUnit1SensorEntry 7 }
+
+ unit1SensorSetWarn OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for warning setpoint of sensor,
+ also used as fan threshold"
+ ::= { cmcTcUnit1SensorEntry 8 }
+
+
+-- table END
+
+-- Outputs
+ cmcTcUnit1NumberOfOutputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of outputs available on sensor unit 1"
+ ::= { cmcTcStatusUnit1Outputs 1 }
+
+-- table with entry for each output available on this unit
+
+ cmcTcUnit1OutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit1OutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of output table"
+ ::= { cmcTcStatusUnit1Outputs 2 }
+
+ cmcTcUnit1OutputEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit1OutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of output table"
+ INDEX { unit1OutputIndex }
+ ::= { cmcTcUnit1OutputTable 1 }
+
+ CmcTcUnit1OutputEntry ::=
+ SEQUENCE {
+ unit1OutputIndex
+ INTEGER,
+ unit1OutputType
+ INTEGER,
+ unit1OutputText
+ DisplayString,
+ unit1OutputStatus
+ INTEGER,
+ unit1OutputValue
+ INTEGER,
+ unit1OutputSet
+ INTEGER,
+ unit1OutputConfig
+ INTEGER,
+ unit1OutputDelay
+ INTEGER,
+ unit1OutputTimeoutAction
+ INTEGER
+ }
+
+ unit1OutputIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of output entries. Its value ranges
+ between 1 and the value of cmcTcUnit1NumberOfOutputs."
+ ::= { cmcTcUnit1OutputEntry 1 }
+
+ unit1OutputType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ failure (2),
+ overflow (3),
+ doorLock (4),
+ univLock1 (5),
+ univLock2 (6),
+ fan (7),
+ fanSpeedContr (8),
+ universalOut (9),
+ roomLock(10),
+ powerOut(11),
+ doorLockMaster(12),
+ doorLockFRi (13),
+ setpoint (14),
+ setpointTimax (15),
+ hysteresisRCT (16),
+ commandRCT (17),
+ relayPSM (18),
+ setHighPSM (19),
+ setLowPSM (20),
+ setpointRTT (21),
+ setTimaxRTT (22),
+ powerOut1(23),
+ controlModeLCP (30),
+ minFanSpeedLCP (31),
+ minDeltaTLCP (32),
+ maxDeltaTLCP (33),
+ kPLCP (34),
+ kILCP (35),
+ kDLCP (36),
+ flowRateLCP(37),
+ cwValueLCP (38),
+ deltaTLCP (39),
+ ctrModLCP (40),
+ voltHighPSM (42),
+ voltLowPSM (43),
+ ampHighPSM (44),
+ ampLowPSM (45),
+ commandPSM (46)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of output which is connected to sensor unit 1 to output[unit1OutputIndex]
+ 1: no output connected
+ 2: output failure
+ 3: value overflow
+ 4: output type 1, door locking TS8,Ergoform
+ 5: output type 2, universal lock 1, lock with power
+ 6: output type 3, universal lock 2, unlock with power
+ 7: output type 4, fan relay
+ 8: output type 5, fan controlled
+ 9: output type 6, universal relay output
+ 10: output type 7, room door lock
+ 11: output type 8, power output
+ 12: output type 9, door lock with Master key
+ 13: output type 10, door lock FR(i)
+ 14: setpoint (FCS, LCP)
+ 15: setpoint temperature monitoring (LCP)
+ 16: hysteresis of setpoint (LCP)
+ 17: command for remote control of RCT
+ 18: relay PSM, 1=On, 0=Off
+ 19: high setpoint current monitoring PSM
+ 20: low setpoint current monitoring PSM
+ 21: setpoint temperature RTT
+ 22: setpoint temperature monitoring RTT
+ 23: power output 20A
+ 30: control mode, LCP
+ 31: min fan speed (fan control), LCP
+ 32: min delta T (fan control), LCP
+ 33: max delta T (fan control), LCP
+ 34: PID controller, KP, LCP
+ 35: PID controller, KI, LCP
+ 36 PID controller, KD, LCP
+ 37 flowrate flowmeter, LCP
+ 38: cw value of water (default: 4187), LCP
+ 39: deltaT, LCP
+ 40: control mode, LCP
+ 42: setpoint high voltage PSM
+ 43: setpoint low voltage PSM
+ 44: setpoint high current PSM
+ 45: setpoint low current PSM
+ 46: command PSM"
+ ::= { cmcTcUnit1OutputEntry 2 }
+
+
+ unit1OutputText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each output (entry in the table)"
+ ::= { cmcTcUnit1OutputEntry 3 }
+
+ unit1OutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ off(5),
+ on(6),
+ setOff(7),
+ setOn(8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the output"
+ ::= { cmcTcUnit1OutputEntry 4 }
+
+ unit1OutputValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for output"
+ ::= { cmcTcUnit1OutputEntry 5 }
+
+ unit1OutputSet OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2),
+ lock (3),
+ unlock (4),
+ unlockDelay (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Command for output"
+ ::= { cmcTcUnit1OutputEntry 6 }
+
+ unit1OutputConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ disRemote (1),
+ enRemote (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration for output
+ 1: disable remote control (e.g. keypad)
+ 2: enable remote control "
+ ::= { cmcTcUnit1OutputEntry 7 }
+
+ unit1OutputDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unsigned Value for delay,
+ after this time the output will fall into the previous state"
+ ::= { cmcTcUnit1OutputEntry 8 }
+
+ unit1OutputTimeoutAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ stay (1),
+ off (2),
+ on (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "State for output if timeout (RS422) occurs"
+ ::= { cmcTcUnit1OutputEntry 9 }
+
+
+-- Messages
+
+ cmcTcUnit1NumberOfMsgs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of messages that can be created with sensor unit 1"
+ ::= { cmcTcStatusUnit1Msg 1 }
+
+-- table with entry for each alarm available on this unit
+
+ cmcTcUnit1MsgTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit1MsgEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of message table"
+ ::= { cmcTcStatusUnit1Msg 2 }
+
+ cmcTcUnit1MsgEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit1MsgEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of message table"
+ INDEX { unit1MsgIndex }
+ ::= { cmcTcUnit1MsgTable 1 }
+
+ CmcTcUnit1MsgEntry ::=
+ SEQUENCE {
+ unit1MsgIndex
+ INTEGER,
+ unit1MsgText
+ DisplayString,
+ unit1MsgStatus
+ INTEGER,
+ unit1MsgRelay
+ INTEGER,
+ unit1MsgBeeper
+ INTEGER,
+ unit1MsgTrap1
+ INTEGER,
+ unit1MsgTrap2
+ INTEGER,
+ unit1MsgTrap3
+ INTEGER,
+ unit1MsgTrap4
+ INTEGER,
+ unit1MsgQuit
+ INTEGER
+ }
+
+ unit1MsgIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of message entries. Its value ranges
+ between 1 and the value of cmcTcUnit1NumberOfMsgs."
+ ::= { cmcTcUnit1MsgEntry 1 }
+
+ unit1MsgText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each message (entry in the table)"
+ ::= { cmcTcUnit1MsgEntry 2 }
+
+ unit1MsgStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ configChanged(2),
+ error(3),
+ ok(4),
+ alarm(5),
+ warning(6),
+ tooLow(7),
+ tooHigh(8),
+ setOff(9),
+ setOn(10),
+ open(11),
+ closed(12),
+ locked(13),
+ unlRemote(14),
+ unlReaderKeypad(15),
+ unlSNMP(16),
+ unlWEB(17),
+ unlTimer(18),
+ noAccess(19),
+ circuit1 (20),
+ circuit2 (21),
+ lowBatt (22)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual message status
+ 1: not available
+ 2: configuration has changed (sensor new, changed, lost)
+ 3: error
+ 4: OK
+ 5: alarm, e.g. smoke, vibration...
+ 6: warning of analog value, value reached warning threshold
+ 7: analog value too low, value reached low threshold
+ 8: analog value too high, value reached high threshold
+ 9: output is set to OFF
+ 10: output is set to ON
+ 11: door is open
+ 12: door is closed
+ 13: door is locked
+ 14: door is unlocked by remote input, e.g. external cardreader
+ 15: door is unlocked by reader or keypad connected to I2C
+ 16: door is unlocked by SNMP set command (unit1OutputSet)
+ 17: door is unlocked by WEB
+ 18: door is unlocked by timer
+ 19: no access, wrong keycode or cardnumber
+ 20: orientation of PSM-Unit is circuit 1
+ 21: orientation of PSM-Unit is circuit 2
+ 22: battery low, wireless sensor"
+ ::= { cmcTcUnit1MsgEntry 3 }
+
+ unit1MsgRelay OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm relay for this message/alarm
+ 1: no switching of alarm relay
+ 2: switching of alarm relay"
+ ::= { cmcTcUnit1MsgEntry 4 }
+
+ unit1MsgBeeper OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm beeper for this alarm
+ 1: no audible alarm
+ 2: audible alarm"
+ ::= { cmcTcUnit1MsgEntry 5 }
+
+ unit1MsgTrap1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 1 activated"
+ ::= { cmcTcUnit1MsgEntry 6 }
+
+ unit1MsgTrap2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 2 activated"
+ ::= { cmcTcUnit1MsgEntry 7 }
+
+ unit1MsgTrap3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 3 activated"
+ ::= { cmcTcUnit1MsgEntry 8 }
+
+ unit1MsgTrap4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 4 and Event Logging activated"
+ ::= { cmcTcUnit1MsgEntry 9 }
+
+ unit1MsgQuit OBJECT-TYPE
+ SYNTAX INTEGER {
+ auto (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset of this alarm
+ 1: auto
+ 2: manual, alarm needs confirmation, e. g. with 'C' key"
+ ::= { cmcTcUnit1MsgEntry 10 }
+-- table unit 1 END
+
+-- unit2
+ cmcTcUnit2TypeOfDevice OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ unitIO (2),
+ unitAccess (3),
+ unitClimate (4),
+ unitFCS (5),
+ unitRTT (6),
+ unitRCT (7),
+ unitPSM (8),
+ unitPSM8 (9),
+ unitPSMMetered (10),
+ unitIOWireless (11),
+ unitPSM6Schuko (12),
+ unitPSM6C19 (13)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of sensor unit connected to port 2"
+ ::= { cmcTcStatusSensorUnit2 1 }
+
+ cmcTcUnit2Text OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..10))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for sensor unit connected to port 2"
+ ::= { cmcTcStatusSensorUnit2 2 }
+
+ cmcTcUnit2Serial OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Serialnumber of sensor unit connected to port 2"
+ ::= { cmcTcStatusSensorUnit2 3 }
+
+ cmcTcUnit2Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(1),
+ error(2),
+ changed(3),
+ quit(4),
+ timeout(5),
+ detected(6),
+ notAvail(7),
+ lowPower(8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "General Status sensor unit connected to port 2
+ (1) OK
+ (2) error
+ (3) configuration of sensor unit has changed, confirmation required
+ (4) Quit from sensor unit to confirm configuration changes
+ (5) timeout of sensor unit, confirmation required
+ (6) sensor unit detected, needs to be confirmed
+ (8) supply voltage is too low"
+ ::= { cmcTcStatusSensorUnit2 4 }
+
+-- unit 2 table
+
+-- Sensors
+ cmcTcUnit2NumberOfSensors OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of sensors connected to sensor unit 2"
+ ::= { cmcTcStatusUnit2Sensors 1 }
+
+-- table with entry for each sensor available on this unit
+ cmcTcUnit2SensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit2SensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of sensor table"
+ ::= { cmcTcStatusUnit2Sensors 2 }
+
+ cmcTcUnit2SensorEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit2SensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of sensor table"
+ INDEX { unit2SensorIndex }
+ ::= { cmcTcUnit2SensorTable 1 }
+
+ CmcTcUnit2SensorEntry ::=
+ SEQUENCE {
+ unit2SensorIndex
+ INTEGER,
+ unit2SensorType
+ INTEGER,
+ unit2SensorText
+ DisplayString,
+ unit2SensorStatus
+ INTEGER,
+ unit2SensorValue
+ INTEGER,
+ unit2SensorSetHigh
+ INTEGER,
+ unit2SensorSetLow
+ INTEGER,
+ unit2SensorSetWarn
+ INTEGER
+ }
+
+ unit2SensorIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of value entries. Its value ranges
+ between 1 and the value of cmcTcUnit2NumberOfSensors."
+ ::= { cmcTcUnit2SensorEntry 1 }
+
+ unit2SensorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ failure (2),
+ overflow (3),
+ access (4),
+ vibration (5),
+ motion (6),
+ smoke (7),
+ airFlow (8),
+ type6 (9),
+ temperature(10),
+ current4to20(11),
+ humidity(12),
+ userNO (13),
+ userNC (14),
+ lock (15),
+ unlock (16),
+ voltOK (17),
+ voltage (18),
+ fanOK (19),
+ readerKeypad (20),
+ dutyPWM (21),
+ fanStatus (22),
+ leakage (23),
+ warningRTT (24),
+ alarmRTT (25),
+ filterRTT (26),
+ heatflowRCT (27),
+ alarmRCT (28),
+ warningRCT (29),
+ currentPSM (30),
+ statusPSM (31),
+ positionPSM (32),
+ airFlap (33),
+ detACfault (35),
+ detACfirstAlarm (36),
+ detACmainAlarm (37),
+ acoustic (34),
+ rpm11LCP (40),
+ rpm12LCP (41),
+ rpm21LCP (42),
+ rpm22LCP (43),
+ rpm31LCP (44),
+ rpm32LCP (45),
+ rpm41LCP (46),
+ rpm42LCP (47),
+ airTemp11LCP (48),
+ airTemp12LCP (49),
+ airTemp21LCP (50),
+ airTemp22LCP (51),
+ airTemp31LCP (52),
+ airTemp32LCP (53),
+ airTemp41LCP (54),
+ airTemp42LCP (55),
+ temp1LCP (56),
+ temp2LCP (57),
+ waterInTemp (58),
+ waterOutTemp (59),
+ waterFlow (60),
+ fanSpeed (61),
+ valve (62),
+ statusLCP (63),
+ waterDelta (64),
+ valveActual (65),
+ contrTemp2 (66),
+ condensateDuration (67),
+ condensateCycles (68),
+ totalKWhPSM (72),
+ totalKWPSM (73),
+ frequencyPSM (74),
+ voltagePSM (75),
+ voltStatusPSM (76),
+ amperePSM (77),
+ ampStatusPSM (78),
+ kWPSM (79),
+ kWhPSM (80),
+ kWhTempPSM (81),
+ temperatureWL (100),
+ temperature1WL (101),
+ humidityWL (102),
+ accessWL (103),
+ userNOWL (104),
+ userNCWL (105),
+ analogWL (106)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex]
+ 1: no sensor connected
+ 2: sensor failure
+ 3: value overflow
+ 4: sensor type 1, access sensor
+ 5: sensor type 2, vibration sensor
+ 6: sensor type 3, motion sensor
+ 7: sensor type 4, smoke sensor
+ 8: sensor type 5, air flow sensor
+ 9: sensor type 6, reserved
+ 10: sensor type 7, temperature sensor
+ 11: sensor type 8, 4..20mA sensor
+ 12: sensor type 9, humidity sensor
+ 13: user sensor with normally opened contact
+ 14: user sensor with normally closed contact
+ 15: door locked sensor from locking device
+ 16: remote unlock sensor (e.g. external keypad)
+ 17: voltage sensor, indicates status of main voltage
+ 18: voltage value
+ 19: fan status
+ 20: cardreader or keypad, connected to I2C port
+ 21: duty cycle of fan, FCS-Unit
+ 22: status of fan, FCS-Unit
+ 23: leakage sensor
+ 24: warning, RittalTopTherm(RTT)-Unit
+ 25: alarm, RittalTopTherm-Unit
+ 26: temperature difference filter monitor, RTT-Unit
+ 27: heatflow RCT-Unit
+ 28: alarm RCT-Unit
+ 29: warning RCT-Unit
+ 30: actual current*10, PSM-Unit
+ 31: status PSM-Unit
+ 32: position PSM-Unit, normal/reversed = circuit 1/2
+ 33: air Flap
+ 34: acoustic sensor
+ 35: DET-AC fault (extinguisher)
+ 36: DET-AC first alarm (extinguisher)
+ 37: DET-AC main alarm (extinguisher)
+ 40-47: RPM Fan 1.1 - Fan 4.2, LCP
+ 48-55: Air temperature 1.1 - 4.2, LCP
+ 56,57: actual temperature 1,2, LCP
+ 58: water inlet temperature, LCP
+ 59: water outlet temperature, LCP
+ 60: water flow
+ 61: fan speed (desired value)
+ 62: status valve, LCP
+ 63: status LCP
+ 64: temperature difference water temperatures
+ 65: control temperature 1, LCP
+ 66: control temperature 2, LCP
+ 67: condensate pump, duration, LCP
+ 68: condensate pump, cycles, LCP
+ 72: total energy*10 (kWh), PSM
+ 73: total power*10 (kW), PSM
+ 74: frequency*10 (Hz), PSM
+ 75: voltage*10 (V), PSM
+ 76: voltage status, PSM
+ 77: current*10 (A), PSM
+ 78: current status, PSM
+ 79: power*10 (kW) per phase, PSM
+ 80: energy*10 (kWh) per phase, PSM
+ 81: temporary energy*10 (kWh) per phase, PSM
+ 100: temperature sensor, wireless
+ 101: temperature sensor (combi), wireless
+ 102: humidity sensor, wireless
+ 103: access sensor, wireless
+ 104: user sensor with normally opened contact, wireless
+ 105: user sensor with normally closed contact, wireless
+ 106: analog sensor 4..20mA, wireless"
+ ::= { cmcTcUnit2SensorEntry 2 }
+
+ unit2SensorText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each sensor (entry in the table)"
+ ::= { cmcTcUnit2SensorEntry 3 }
+
+ unit2SensorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ off(5),
+ on(6),
+ warning(7),
+ tooLow(8),
+ tooHigh(9)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the sensor"
+ ::= { cmcTcUnit2SensorEntry 4 }
+
+ unit2SensorValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Value of sensor"
+ ::= { cmcTcUnit2SensorEntry 5 }
+
+ unit2SensorSetHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for high setpoint of sensor"
+ ::= { cmcTcUnit2SensorEntry 6 }
+
+ unit2SensorSetLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for low setpoint of sensor,
+ also used as alarm delay"
+ ::= { cmcTcUnit2SensorEntry 7 }
+
+ unit2SensorSetWarn OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for warning setpoint of sensor,
+ also used as fan threshold"
+ ::= { cmcTcUnit2SensorEntry 8 }
+
+-- table END
+
+-- Outputs
+ cmcTcUnit2NumberOfOutputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of outputs available on sensor unit 2"
+ ::= { cmcTcStatusUnit2Outputs 1 }
+
+-- table with entry for each output available on this unit
+
+ cmcTcUnit2OutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit2OutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of output table"
+ ::= { cmcTcStatusUnit2Outputs 2 }
+
+ cmcTcUnit2OutputEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit2OutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of output table"
+ INDEX { unit2OutputIndex }
+ ::= { cmcTcUnit2OutputTable 1 }
+
+ CmcTcUnit2OutputEntry ::=
+ SEQUENCE {
+ unit2OutputIndex
+ INTEGER,
+ unit2OutputType
+ INTEGER,
+ unit2OutputText
+ DisplayString,
+ unit2OutputStatus
+ INTEGER,
+ unit2OutputValue
+ INTEGER,
+ unit2OutputSet
+ INTEGER,
+ unit2OutputConfig
+ INTEGER,
+ unit2OutputDelay
+ INTEGER,
+ unit2OutputTimeoutAction
+ INTEGER
+ }
+
+ unit2OutputIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of output entries. Its value ranges
+ between 1 and the value of cmcTcUnit2NumberOfOutputs."
+ ::= { cmcTcUnit2OutputEntry 1 }
+
+ unit2OutputType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ failure (2),
+ overflow (3),
+ doorLock (4),
+ univLock1 (5),
+ univLock2 (6),
+ fan (7),
+ fanSpeedContr (8),
+ universalOut (9),
+ roomLock(10),
+ powerOut(11),
+ doorLockMaster(12),
+ doorLockFRi (13),
+ setpoint (14),
+ setpointTimax (15),
+ hysteresisRCT (16),
+ commandRCT (17),
+ relayPSM (18),
+ setHighPSM (19),
+ setLowPSM (20),
+ setpointRTT (21),
+ setTimaxRTT (22),
+ powerOut1(23),
+ controlModeLCP (30),
+ minFanSpeedLCP (31),
+ minDeltaTLCP (32),
+ maxDeltaTLCP (33),
+ kPLCP (34),
+ kILCP (35),
+ kDLCP (36),
+ flowRateLCP(37),
+ cwValueLCP (38),
+ deltaTLCP (39),
+ ctrModLCP (40),
+ voltHighPSM (42),
+ voltLowPSM (43),
+ ampHighPSM (44),
+ ampLowPSM (45),
+ commandPSM (46)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of output which is connected to sensor unit 2 to output[unit2OutputIndex]
+ 1: no output connected
+ 2: output failure
+ 3: value overflow
+ 4: output type 1, door locking TS8,Ergoform
+ 5: output type 2, universal lock 1, lock with power
+ 6: output type 3, universal lock 2, unlock with power
+ 7: output type 4, fan relay
+ 8: output type 5, fan controlled
+ 9: output type 6, universal relay output
+ 10: output type 7, room door lock
+ 11: output type 8, power output
+ 12: output type 9, door lock with Master key
+ 13: output type 10, door lock FR(i)
+ 14: setpoint (FCS, RTT)
+ 15: setpoint temperature monitoring (RTT)
+ 16: hysteresis of setpoint (RCT)
+ 17: command for remote control of RCT
+ 18: relay PSM, 1=On, 0=Off
+ 19: high setpoint current monitoring PSM
+ 20: low setpoint current monitoring PSM
+ 21: setpoint temperature RTT
+ 22: setpoint temperature monitoring RTT
+ 23: power output 20A
+ 30: control mode LCP
+ 31: min fan speed (fan control) LCP
+ 32: min delta T (fan control) LCP
+ 33: max delta T (fan control) LCP
+ 34: PID controller, KP, LCP
+ 35: PID controller, KI, LCP
+ 36 PID controller, KD, LCP
+ 37 flowrate flowmeter, LCP
+ 38: cw value of water (default: 4187) LCP
+ 39: deltaT, LCP
+ 40: control mode, LCP
+ 42: setpoint high voltage PSM
+ 43: setpoint low voltage PSM
+ 44: setpoint high current PSM
+ 45: setpoint low current PSM
+ 46: command PSM"
+ ::= { cmcTcUnit2OutputEntry 2 }
+
+
+ unit2OutputText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each output (entry in the table)"
+ ::= { cmcTcUnit2OutputEntry 3 }
+
+ unit2OutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ off(5),
+ on(6),
+ setOff(7),
+ setOn(8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the output"
+ ::= { cmcTcUnit2OutputEntry 4 }
+
+ unit2OutputValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Signed value for output"
+ ::= { cmcTcUnit2OutputEntry 5 }
+
+ unit2OutputSet OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2),
+ lock (3),
+ unlock (4),
+ unlockDelay (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Command for output"
+ ::= { cmcTcUnit2OutputEntry 6 }
+
+ unit2OutputConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ disRemote (1),
+ enRemote (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration for output
+ 1: disable remote control (e.g. keypad)
+ 2: enable remote control "
+ ::= { cmcTcUnit2OutputEntry 7 }
+
+ unit2OutputDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unsigned Value for delay,
+ after this time the output will fall into the previous state"
+ ::= { cmcTcUnit2OutputEntry 8 }
+
+ unit2OutputTimeoutAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ stay (1),
+ off (2),
+ on (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "State for output if timeout (RS422) occurs"
+ ::= { cmcTcUnit2OutputEntry 9 }
+
+-- Alarms
+
+ cmcTcUnit2NumberOfMsgs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of alarms that can be created with sensor unit 2"
+ ::= { cmcTcStatusUnit2Msg 1 }
+
+-- table with entry for each alarm available on this unit
+
+ cmcTcUnit2MsgTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit2MsgEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of message table"
+ ::= { cmcTcStatusUnit2Msg 2 }
+
+ cmcTcUnit2MsgEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit2MsgEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of message table"
+ INDEX { unit2MsgIndex }
+ ::= { cmcTcUnit2MsgTable 1 }
+
+ CmcTcUnit2MsgEntry ::=
+ SEQUENCE {
+ unit2MsgIndex
+ INTEGER,
+ unit2MsgText
+ DisplayString,
+ unit2MsgStatus
+ INTEGER,
+ unit2MsgRelay
+ INTEGER,
+ unit2MsgBeeper
+ INTEGER,
+ unit2MsgTrap1
+ INTEGER,
+ unit2MsgTrap2
+ INTEGER,
+ unit2MsgTrap3
+ INTEGER,
+ unit2MsgTrap4
+ INTEGER,
+ unit2MsgQuit
+ INTEGER
+ }
+
+ unit2MsgIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of alarm entries. Its value ranges
+ between 1 and the value of cmcTcUnit2NumberOfMsgs."
+ ::= { cmcTcUnit2MsgEntry 1 }
+
+ unit2MsgText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each message (entry in the table)"
+ ::= { cmcTcUnit2MsgEntry 2 }
+
+ unit2MsgStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ configChanged(2),
+ error(3),
+ ok(4),
+ alarm(5),
+ warning(6),
+ tooLow(7),
+ tooHigh(8),
+ setOff(9),
+ setOn(10),
+ open(11),
+ closed(12),
+ locked(13),
+ unlRemote(14),
+ unlReaderKeypad(15),
+ unlSNMP(16),
+ unlWEB(17),
+ unlTimer(18),
+ noAccess(19),
+ circuit1 (20),
+ circuit2 (21),
+ lowBatt (22)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual message status
+ 1: not available
+ 2: configuration has changed (sensor new, changed, lost)
+ 3: error
+ 4: OK
+ 5: alarm, e.g. smoke, vibration...
+ 6: warning of analog value, value reached warning threshold
+ 7: analog value too low, value reached low threshold
+ 8: analog value too high, value reached high threshold
+ 9: output is set to OFF
+ 10: output is set to ON
+ 11: door is open
+ 12: door is closed
+ 13: door is locked
+ 14: door is unlocked by remote input, e.g. external cardreader
+ 15: door is unlocked by reader or keypad connected to I2C
+ 16: door is unlocked by SNMP set command (unit1OutputSet)
+ 17: door is unlocked by WEB
+ 18: door is unlocked by timer
+ 19: no access, wrong keycode or cardnumber
+ 20: orientation of PSM-Unit is circuit 1
+ 21: orientation of PSM-Unit is circuit 2
+ 22: battery low, wireless sensor"
+ ::= { cmcTcUnit2MsgEntry 3 }
+
+ unit2MsgRelay OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm relay for this alarm
+ 2: no switching of alarm relay
+ 1: switching of alarm relay"
+ ::= { cmcTcUnit2MsgEntry 4 }
+
+ unit2MsgBeeper OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm beeper for this alarm
+ 2: no audible alarm
+ 1: audible alarm"
+ ::= { cmcTcUnit2MsgEntry 5 }
+
+ unit2MsgTrap1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 1 activated"
+ ::= { cmcTcUnit2MsgEntry 6 }
+
+ unit2MsgTrap2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 2 activated"
+ ::= { cmcTcUnit2MsgEntry 7 }
+
+ unit2MsgTrap3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 3 activated"
+ ::= { cmcTcUnit2MsgEntry 8 }
+
+ unit2MsgTrap4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 4 and Event Logging activated"
+ ::= { cmcTcUnit2MsgEntry 9 }
+
+ unit2MsgQuit OBJECT-TYPE
+ SYNTAX INTEGER {
+ auto (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset of this alarm
+ 1: auto
+ 2: manual, alarm needs confirmation, e. g. with 'C' key"
+ ::= { cmcTcUnit2MsgEntry 10 }
+-- table END
+
+-- unit 3
+ cmcTcUnit3TypeOfDevice OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ unitIO (2),
+ unitAccess (3),
+ unitClimate (4),
+ unitFCS (5),
+ unitRTT (6),
+ unitRCT (7),
+ unitPSM (8),
+ unitPSM8 (9),
+ unitPSMMetered (10),
+ unitIOWireless (11),
+ unitPSM6Schuko (12),
+ unitPSM6C19 (13)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of sensor unit connected to port 3"
+ ::= { cmcTcStatusSensorUnit3 1 }
+
+ cmcTcUnit3Text OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..10))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for sensor unit connected to port 3"
+ ::= { cmcTcStatusSensorUnit3 2 }
+
+ cmcTcUnit3Serial OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Serialnumber of sensor unit connected to port 3"
+ ::= { cmcTcStatusSensorUnit3 3 }
+
+ cmcTcUnit3Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(1),
+ error(2),
+ changed(3),
+ quit(4),
+ timeout(5),
+ detected(6),
+ notAvail(7),
+ lowPower(8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "General Status sensor unit connected to port 3
+ (1) OK
+ (2) error, e. g. value overflow
+ (3) configuration of sensor unit has changed, confirmation required
+ (4) Quit from sensor unit to confirm configuration changes
+ (5) timeout of sensor unit, confirmation required to unload this unit
+ (6) sensor unit detected, needs to be confirmed
+ (7) unit is not available
+ (8) supply voltage is too low"
+ ::= { cmcTcStatusSensorUnit3 4 }
+
+-- Sensors
+ cmcTcUnit3NumberOfSensors OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of sensors connected to sensor unit 3"
+ ::= { cmcTcStatusUnit3Sensors 1 }
+
+-- table with entry for each sensor available on this unit
+
+ cmcTcUnit3SensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit3SensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of sensor table"
+ ::= { cmcTcStatusUnit3Sensors 2 }
+
+ cmcTcUnit3SensorEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit3SensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of sensor table"
+ INDEX { unit3SensorIndex }
+ ::= { cmcTcUnit3SensorTable 1 }
+
+ CmcTcUnit3SensorEntry ::=
+ SEQUENCE {
+ unit3SensorIndex
+ INTEGER,
+ unit3SensorType
+ INTEGER,
+ unit3SensorText
+ DisplayString,
+ unit3SensorStatus
+ INTEGER,
+ unit3SensorValue
+ INTEGER,
+ unit3SensorSetHigh
+ INTEGER,
+ unit3SensorSetLow
+ INTEGER,
+ unit3SensorSetWarn
+ INTEGER
+ }
+
+ unit3SensorIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of value entries. Its value ranges
+ between 1 and the value of cmcTcUnit3NumberOfSensors."
+ ::= { cmcTcUnit3SensorEntry 1 }
+
+ unit3SensorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ failure (2),
+ overflow (3),
+ access (4),
+ vibration (5),
+ motion (6),
+ smoke (7),
+ airFlow (8),
+ type6 (9),
+ temperature(10),
+ current4to20(11),
+ humidity(12),
+ userNO (13),
+ userNC (14),
+ lock (15),
+ unlock (16),
+ voltOK (17),
+ voltage (18),
+ fanOK (19),
+ readerKeypad (20),
+ dutyPWM (21),
+ fanStatus (22),
+ leakage (23),
+ warningRTT (24),
+ alarmRTT (25),
+ filterRTT (26),
+ heatflowRCT (27),
+ alarmRCT (28),
+ warningRCT (29),
+ currentPSM (30),
+ statusPSM (31),
+ positionPSM (32),
+ airFlap (33),
+ acoustic (34),
+ detACfault (35),
+ detACfirstAlarm (36),
+ detACmainAlarm (37),
+ rpm11LCP (40),
+ rpm12LCP (41),
+ rpm21LCP (42),
+ rpm22LCP (43),
+ rpm31LCP (44),
+ rpm32LCP (45),
+ rpm41LCP (46),
+ rpm42LCP (47),
+ airTemp11LCP (48),
+ airTemp12LCP (49),
+ airTemp21LCP (50),
+ airTemp22LCP (51),
+ airTemp31LCP (52),
+ airTemp32LCP (53),
+ airTemp41LCP (54),
+ airTemp42LCP (55),
+ temp1LCP (56),
+ temp2LCP (57),
+ waterInTemp (58),
+ waterOutTemp (59),
+ waterFlow (60),
+ fanSpeed (61),
+ valve (62),
+ statusLCP (63),
+ waterDelta (64),
+ valveActual (65),
+ contrTemp2 (66),
+ condensateDuration (67),
+ condensateCycles (68),
+ totalKWhPSM (72),
+ totalKWPSM (73),
+ frequencyPSM (74),
+ voltagePSM (75),
+ voltStatusPSM (76),
+ amperePSM (77),
+ ampStatusPSM (78),
+ kWPSM (79),
+ kWhPSM (80),
+ kWhTempPSM (81),
+ temperatureWL (100),
+ temperature1WL (101),
+ humidityWL (102),
+ accessWL (103),
+ userNOWL (104),
+ userNCWL (105),
+ analogWL (106)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex]
+ 1: no sensor connected
+ 2: sensor failure
+ 3: value overflow
+ 4: sensor type 1, access sensor
+ 5: sensor type 2, vibration sensor
+ 6: sensor type 3, motion sensor
+ 7: sensor type 4, smoke sensor
+ 8: sensor type 5, air flow sensor
+ 9: sensor type 6, reserved
+ 10: sensor type 7, temperature sensor
+ 11: sensor type 8, 4..20mA sensor
+ 12: sensor type 9, humidity sensor
+ 13: user sensor with normally opened contact
+ 14: user sensor with normally closed contact
+ 15: door locked sensor from locking device
+ 16: remote unlock sensor (e.g. external keypad)
+ 17: voltage sensor, indicates status of main voltage
+ 18: voltage value
+ 19: fan status
+ 20: cardreader or keypad, connected to I2C port
+ 21: duty cycle of fan, FCS-Unit
+ 22: status of fan, FCS-Unit
+ 23: leakage sensor
+ 24: warning, RittalTopTherm(RTT)-Unit
+ 25: alarm, RittalTopTherm-Unit
+ 26: temperature difference filter monitor, RTT-Unit
+ 27: heatflow RCT-Unit
+ 28: alarm RCT-Unit
+ 29: warning RCT-Unit
+ 30: actual current*10, PSM-Unit
+ 31: status PSM-Unit
+ 32: position PSM-Unit, normal/reversed = circuit 1/2
+ 33: air Flap
+ 34: acoustic sensor
+ 35: DET-AC fault (extinguisher)
+ 36: DET-AC first alarm (extinguisher)
+ 37: DET-AC main alarm (extinguisher)
+ 40-47: RPM Fan 1.1 - Fan 4.2, LCP
+ 48-55: Air temperature 1.1 - 4.2, LCP
+ 56,57: actual temperature 1,2, LCP
+ 58: water inlet temperature, LCP
+ 59: water outlet temperature, LCP
+ 60: water flow
+ 61: fan speed (desired value)
+ 62: status valve, LCP
+ 63: status LCP
+ 64: temperature difference water temperatures
+ 65: control temperature 1, LCP
+ 66: control temperature 2, LCP
+ 67: condensate pump, duration, LCP
+ 68: condensate pump, cycles, LCP
+ 72: total energy*10 (kWh), PSM
+ 73: total power*10 (kW), PSM
+ 74: frequency*10 (Hz), PSM
+ 75: voltage*10 (V), PSM
+ 76: voltage status, PSM
+ 77: current*10 (A), PSM
+ 78: current status, PSM
+ 79: power*10 (kW) per phase, PSM
+ 80: energy*10 (kWh) per phase, PSM
+ 81: temporary energy*10 (kWh) per phase, PSM
+ 100: temperature sensor, wireless
+ 101: temperature sensor (combi), wireless
+ 102: humidity sensor, wireless
+ 103: access sensor, wireless
+ 104: user sensor with normally opened contact, wireless
+ 105: user sensor with normally closed contact, wireless
+ 106: analog sensor 4..20mA, wireless"
+ ::= { cmcTcUnit3SensorEntry 2 }
+
+
+ unit3SensorText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each sensor (entry in the table)"
+ ::= { cmcTcUnit3SensorEntry 3 }
+
+ unit3SensorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ off(5),
+ on(6),
+ warning(7),
+ tooLow(8),
+ tooHigh(9)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the sensor"
+ ::= { cmcTcUnit3SensorEntry 4 }
+
+ unit3SensorValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Value of sensor"
+ ::= { cmcTcUnit3SensorEntry 5 }
+
+ unit3SensorSetHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for high setpoint of sensor"
+ ::= { cmcTcUnit3SensorEntry 6 }
+
+ unit3SensorSetLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for low setpoint of sensor"
+ ::= { cmcTcUnit3SensorEntry 7 }
+
+ unit3SensorSetWarn OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for warning setpoint of sensor,
+ also used as fan threshold"
+ ::= { cmcTcUnit3SensorEntry 8 }
+-- table END
+
+-- Outputs
+ cmcTcUnit3NumberOfOutputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of outputs available on sensor unit 3"
+ ::= { cmcTcStatusUnit3Outputs 1 }
+
+-- table with entry for each output available on this unit
+
+ cmcTcUnit3OutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit3OutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of output table"
+ ::= { cmcTcStatusUnit3Outputs 2 }
+
+ cmcTcUnit3OutputEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit3OutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of output table"
+ INDEX { unit3OutputIndex }
+ ::= { cmcTcUnit3OutputTable 1 }
+
+ CmcTcUnit3OutputEntry ::=
+ SEQUENCE {
+ unit3OutputIndex
+ INTEGER,
+ unit3OutputType
+ INTEGER,
+ unit3OutputText
+ DisplayString,
+ unit3OutputStatus
+ INTEGER,
+ unit3OutputValue
+ INTEGER,
+ unit3OutputSet
+ INTEGER,
+ unit3OutputConfig
+ INTEGER,
+ unit3OutputDelay
+ INTEGER,
+ unit3OutputTimeoutAction
+ INTEGER
+ }
+
+ unit3OutputIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of output entries. Its value ranges
+ between 1 and the value of cmcTcUnit3NumberOfOutputs."
+ ::= { cmcTcUnit3OutputEntry 1 }
+
+ unit3OutputType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ failure (2),
+ overflow (3),
+ doorLock (4),
+ univLock1 (5),
+ univLock2 (6),
+ fan (7),
+ fanSpeedContr (8),
+ universalOut (9),
+ roomLock(10),
+ powerOut(11),
+ doorLockMaster(12),
+ doorLockFRi (13),
+ setpoint (14),
+ setpointTimax (15),
+ hysteresisRCT (16),
+ commandRCT (17),
+ relayPSM (18),
+ setHighPSM (19),
+ setLowPSM (20),
+ setpointRTT (21),
+ setTimaxRTT (22),
+ powerOut1(23),
+ controlModeLCP (30),
+ minFanSpeedLCP (31),
+ minDeltaTLCP (32),
+ maxDeltaTLCP (33),
+ kPLCP (34),
+ kILCP (35),
+ kDLCP (36),
+ flowRateLCP(37),
+ cwValueLCP (38),
+ deltaTLCP (39),
+ ctrModLCP (40),
+ voltHighPSM (42),
+ voltLowPSM (43),
+ ampHighPSM (44),
+ ampLowPSM (45),
+ commandPSM (46)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of output which is connected to sensor unit 3 to output[unit3OutputIndex]
+ 1: no output connected
+ 2: output failure
+ 3: value overflow
+ 4: output type 1, door locking TS8,Ergoform
+ 5: output type 2, universal lock 1, lock with power
+ 6: output type 3, universal lock 2, unlock with power
+ 7: output type 4, fan relay
+ 8: output type 5, fan controlled
+ 9: output type 6, universal relay output
+ 10: output type 7, room door lock
+ 11: output type 8, power output
+ 12: output type 9, door lock with Master key
+ 13: output type 10, door lock FR(i)
+ 14: setpoint (FCS, RTT)
+ 15: setpoint temperature monitoring (RTT)
+ 16: hysteresis of setpoint (RCT)
+ 17: command for remote control of RCT
+ 18: relay PSM, 1=On, 0=Off
+ 19: high setpoint current monitoring PSM
+ 20: low setpoint current monitoring PSM
+ 21: setpoint temperature RTT
+ 22: setpoint temperature monitoring RTT
+ 23: power output 20A
+ 30: control mode LCP
+ 31: min fan speed (fan control) LCP
+ 32: min delta T (fan control) LCP
+ 33: max delta T (fan control) LCP
+ 34: PID controller, KP, LCP
+ 35: PID controller, KI, LCP
+ 36 PID controller, KD, LCP
+ 37 flowrate flowmeter, LCP
+ 38: cw value of water (default: 4187) LCP
+ 39: deltaT, LCP
+ 40: control mode, LCP
+ 42: setpoint high voltage PSM
+ 43: setpoint low voltage PSM
+ 44: setpoint high current PSM
+ 45: setpoint low current PSM
+ 46: command PSM"
+ ::= { cmcTcUnit3OutputEntry 2 }
+
+
+ unit3OutputText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each output (entry in the table)"
+ ::= { cmcTcUnit3OutputEntry 3 }
+
+ unit3OutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ off(5),
+ on(6),
+ setOff(7),
+ setOn(8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the output"
+ ::= { cmcTcUnit3OutputEntry 4 }
+
+ unit3OutputValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for output"
+ ::= { cmcTcUnit3OutputEntry 5 }
+
+ unit3OutputSet OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2),
+ lock (3),
+ unlock (4),
+ unlockDelay (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Command for output"
+ ::= { cmcTcUnit3OutputEntry 6 }
+
+ unit3OutputConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ disRemote (1),
+ enRemote (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration for output
+ 1: disable remote control (e.g. keypad)
+ 2: enable remote control "
+ ::= { cmcTcUnit3OutputEntry 7 }
+
+ unit3OutputDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unsigned Value for delay,
+ after this time the output will fall into the previous state"
+ ::= { cmcTcUnit3OutputEntry 8 }
+
+ unit3OutputTimeoutAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ stay (1),
+ off (2),
+ on (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "State for output if timeout (RS422) occurs"
+ ::= { cmcTcUnit3OutputEntry 9 }
+
+
+-- Msgs
+
+ cmcTcUnit3NumberOfMsgs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of alarms that can be created with sensor unit 3"
+ ::= { cmcTcStatusUnit3Msg 1 }
+
+-- table with entry for each alarm available on this unit
+
+ cmcTcUnit3MsgTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit3MsgEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of message table"
+ ::= { cmcTcStatusUnit3Msg 2 }
+
+ cmcTcUnit3MsgEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit3MsgEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of message table"
+ INDEX { unit3MsgIndex }
+ ::= { cmcTcUnit3MsgTable 1 }
+
+ CmcTcUnit3MsgEntry ::=
+ SEQUENCE {
+ unit3MsgIndex
+ INTEGER,
+ unit3MsgText
+ DisplayString,
+ unit3MsgStatus
+ INTEGER,
+ unit3MsgRelay
+ INTEGER,
+ unit3MsgBeeper
+ INTEGER,
+ unit3MsgTrap1
+ INTEGER,
+ unit3MsgTrap2
+ INTEGER,
+ unit3MsgTrap3
+ INTEGER,
+ unit3MsgTrap4
+ INTEGER,
+ unit3MsgQuit
+ INTEGER
+ }
+
+ unit3MsgIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of alarm entries. Its value ranges
+ between 1 and the value of cmcTcUnit3NumberOfMsgs."
+ ::= { cmcTcUnit3MsgEntry 1 }
+
+ unit3MsgText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each message (entry in the table)"
+ ::= { cmcTcUnit3MsgEntry 2 }
+
+ unit3MsgStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ configChanged(2),
+ error(3),
+ ok(4),
+ alarm(5),
+ warning(6),
+ tooLow(7),
+ tooHigh(8),
+ setOff(9),
+ setOn(10),
+ open(11),
+ closed(12),
+ locked(13),
+ unlRemote(14),
+ unlReaderKeypad(15),
+ unlSNMP(16),
+ unlWEB(17),
+ unlTimer(18),
+ noAccess(19),
+ circuit1 (20),
+ circuit2 (21),
+ lowBatt (22)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual message status
+ 1: not available
+ 2: configuration has changed (sensor new, changed, lost)
+ 3: error
+ 4: OK
+ 5: alarm, e.g. smoke, vibration...
+ 6: warning of analog value, value reached warning threshold
+ 7: analog value too low, value reached low threshold
+ 8: analog value too high, value reached high threshold
+ 9: output is set to OFF
+ 10: output is set to ON
+ 11: door is open
+ 12: door is closed
+ 13: door is locked
+ 14: door is unlocked by remote input, e.g. external cardreader
+ 15: door is unlocked by reader or keypad connected to I2C
+ 16: door is unlocked by SNMP set command (unit1OutputSet)
+ 17: door is unlocked by WEB
+ 18: door is unlocked by timer
+ 19: no access, wrong keycode or cardnumber
+ 20: orientation of PSM-Unit is circuit 1
+ 21: orientation of PSM-Unit is circuit 2
+ 22: battery low, wireless sensor"
+ ::= { cmcTcUnit3MsgEntry 3 }
+
+ unit3MsgRelay OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm relay for this alarm
+ 1: no switching of alarm relay
+ 2: switching of alarm relay"
+ ::= { cmcTcUnit3MsgEntry 4 }
+
+ unit3MsgBeeper OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm beeper for this alarm
+ 1: no audible alarm
+ 2: audible alarm"
+ ::= { cmcTcUnit3MsgEntry 5 }
+
+ unit3MsgTrap1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 1 activated"
+ ::= { cmcTcUnit3MsgEntry 6 }
+
+ unit3MsgTrap2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 2 activated"
+ ::= { cmcTcUnit3MsgEntry 7 }
+
+ unit3MsgTrap3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 3 activated"
+ ::= { cmcTcUnit3MsgEntry 8 }
+
+ unit3MsgTrap4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 4 and Event Logging activated"
+ ::= { cmcTcUnit3MsgEntry 9 }
+
+ unit3MsgQuit OBJECT-TYPE
+ SYNTAX INTEGER {
+ auto (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset of this alarm
+ 1: auto
+ 2: manual, alarm needs confirmation, e. g. with 'C' key"
+ ::= { cmcTcUnit3MsgEntry 10 }
+-- table END
+
+-- unit4
+ cmcTcUnit4TypeOfDevice OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ unitIO (2),
+ unitAccess (3),
+ unitClimate (4),
+ unitFCS (5),
+ unitRTT (6),
+ unitRCT (7),
+ unitPSM (8),
+ unitPSM8 (9),
+ unitPSMMetered (10),
+ unitIOWireless (11),
+ unitPSM6Schuko (12),
+ unitPSM6C19 (13)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of sensor unit connected to port 4"
+ ::= { cmcTcStatusSensorUnit4 1 }
+
+ cmcTcUnit4Text OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..10))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for sensor unit connected to port 4"
+ ::= { cmcTcStatusSensorUnit4 2 }
+
+ cmcTcUnit4Serial OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Serialnumber of sensor unit connected to port 4"
+ ::= { cmcTcStatusSensorUnit4 3 }
+
+ cmcTcUnit4Status OBJECT-TYPE
+ SYNTAX INTEGER {
+ ok(1),
+ error(2),
+ changed(3),
+ quit(4),
+ timeout(5),
+ detected(6),
+ notAvail(7),
+ lowPower(8)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "General Status sensor unit connected to port 4
+ (1) OK
+ (2) error, e. g. value overflow
+ (3) configuration of sensor unit has changed, confirmation required
+ (4) Quit from sensor unit to confirm configuration changes
+ (5) timeout of sensor unit, confirmation required to unload this unit
+ (6) sensor unit detected, needs to be confirmed
+ (7) unit is not available
+ (8) supply voltage is too low"
+
+ ::= { cmcTcStatusSensorUnit4 4 }
+
+-- Sensors
+ cmcTcUnit4NumberOfSensors OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of sensors connected to sensor unit 4"
+ ::= { cmcTcStatusUnit4Sensors 1 }
+
+-- table with entry for each sensor available on this unit
+
+ cmcTcUnit4SensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit4SensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of sensor table"
+ ::= { cmcTcStatusUnit4Sensors 2 }
+
+ cmcTcUnit4SensorEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit4SensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of sensor table"
+ INDEX { unit4SensorIndex }
+ ::= { cmcTcUnit4SensorTable 1 }
+
+ CmcTcUnit4SensorEntry ::=
+ SEQUENCE {
+ unit4SensorIndex
+ INTEGER,
+ unit4SensorType
+ INTEGER,
+ unit4SensorText
+ DisplayString,
+ unit4SensorStatus
+ INTEGER,
+ unit4SensorValue
+ INTEGER,
+ unit4SensorSetHigh
+ INTEGER,
+ unit4SensorSetLow
+ INTEGER,
+ unit4SensorSetWarn
+ INTEGER
+ }
+
+ unit4SensorIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of value entries. Its value ranges
+ between 1 and the value of cmcTcUnit4NumberOfSensors."
+ ::= { cmcTcUnit4SensorEntry 1 }
+
+ unit4SensorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ failure (2),
+ overflow (3),
+ access (4),
+ vibration (5),
+ motion (6),
+ smoke (7),
+ airFlow (8),
+ type6 (9),
+ temperature(10),
+ current4to20(11),
+ humidity(12),
+ userNO (13),
+ userNC (14),
+ lock (15),
+ unlock (16),
+ voltOK (17),
+ voltage (18),
+ fanOK (19),
+ readerKeypad (20),
+ dutyPWM (21),
+ fanStatus (22),
+ leakage (23),
+ warningRTT (24),
+ alarmRTT (25),
+ filterRTT (26),
+ heatflowRCT (27),
+ alarmRCT (28),
+ warningRCT (29),
+ currentPSM (30),
+ statusPSM (31),
+ positionPSM (32),
+ airFlap (33),
+ acoustic (34),
+ detACfault (35),
+ detACfirstAlarm (36),
+ detACmainAlarm (37),
+ rpm11LCP (40),
+ rpm12LCP (41),
+ rpm21LCP (42),
+ rpm22LCP (43),
+ rpm31LCP (44),
+ rpm32LCP (45),
+ rpm41LCP (46),
+ rpm42LCP (47),
+ airTemp11LCP (48),
+ airTemp12LCP (49),
+ airTemp21LCP (50),
+ airTemp22LCP (51),
+ airTemp31LCP (52),
+ airTemp32LCP (53),
+ airTemp41LCP (54),
+ airTemp42LCP (55),
+ temp1LCP (56),
+ temp2LCP (57),
+ waterInTemp (58),
+ waterOutTemp (59),
+ waterFlow (60),
+ fanSpeed (61),
+ valve (62),
+ statusLCP (63),
+ waterDelta (64),
+ valveActual (65),
+ contrTemp2 (66),
+ condensateDuration (67),
+ condensateCycles (68),
+ totalKWhPSM (72),
+ totalKWPSM (73),
+ frequencyPSM (74),
+ voltagePSM (75),
+ voltStatusPSM (76),
+ amperePSM (77),
+ ampStatusPSM (78),
+ kWPSM (79),
+ kWhPSM (80),
+ kWhTempPSM (81),
+ temperatureWL (100),
+ temperature1WL (101),
+ humidityWL (102),
+ accessWL (103),
+ userNOWL (104),
+ userNCWL (105),
+ analogWL (106)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex]
+ 1: no sensor connected
+ 2: sensor failure
+ 3: value overflow
+ 4: sensor type 1, access sensor
+ 5: sensor type 2, vibration sensor
+ 6: sensor type 3, motion sensor
+ 7: sensor type 4, smoke sensor
+ 8: sensor type 5, air flow sensor
+ 9: sensor type 6, reserved
+ 10: sensor type 7, temperature sensor
+ 11: sensor type 8, 4..20mA sensor
+ 12: sensor type 9, humidity sensor
+ 13: user sensor with normally opened contact
+ 14: user sensor with normally closed contact
+ 15: door locked sensor from locking device
+ 16: remote unlock sensor (e.g. external keypad)
+ 17: voltage sensor, indicates status of main voltage
+ 18: voltage value
+ 19: fan status
+ 20: cardreader or keypad, connected to I2C port
+ 21: duty cycle of fan, FCS-Unit
+ 22: status of fan, FCS-Unit
+ 23: leakage sensor
+ 24: warning, RittalTopTherm(RTT)-Unit
+ 25: alarm, RittalTopTherm-Unit
+ 26: temperature difference filter monitor, RTT-Unit
+ 27: heatflow RCT-Unit
+ 28: alarm RCT-Unit
+ 29: warning RCT-Unit
+ 30: actual current*10, PSM-Unit
+ 31: status PSM-Unit
+ 32: position PSM-Unit, normal/reversed = circuit 1/2
+ 33: air Flap
+ 34: acoustic sensor
+ 35: DET-AC fault (extinguisher)
+ 36: DET-AC first alarm (extinguisher)
+ 37: DET-AC main alarm (extinguisher)
+ 40-47: RPM Fan 1.1 - Fan 4.2, LCP
+ 48-55: Air temperature 1.1 - 4.2, LCP
+ 56,57: actual temperature 1,2, LCP
+ 58: water inlet temperature, LCP
+ 59: water outlet temperature, LCP
+ 60: water flow
+ 61: fan speed (desired value)
+ 62: status valve, LCP
+ 63: status LCP
+ 64: temperature difference water temperatures
+ 65: control temperature 1, LCP
+ 66: control temperature 2, LCP
+ 67: condensate pump, duration, LCP
+ 68: condensate pump, cycles, LCP
+ 72: total energy*10 (kWh), PSM
+ 73: total power*10 (kW), PSM
+ 74: frequency*10 (Hz), PSM
+ 75: voltage*10 (V), PSM
+ 76: voltage status, PSM
+ 77: current*10 (A), PSM
+ 78: current status, PSM
+ 79: power*10 (kW) per phase, PSM
+ 80: energy*10 (kWh) per phase, PSM
+ 81: temporary energy*10 (kWh) per phase, PSM
+ 100: temperature sensor, wireless
+ 101: temperature sensor (combi), wireless
+ 102: humidity sensor, wireless
+ 103: access sensor, wireless
+ 104: user sensor with normally opened contact, wireless
+ 105: user sensor with normally closed contact, wireless
+ 106: analog sensor 4..20mA, wireless"
+ ::= { cmcTcUnit4SensorEntry 2 }
+
+
+ unit4SensorText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each sensor (entry in the table)"
+ ::= { cmcTcUnit4SensorEntry 3 }
+
+ unit4SensorStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ off(5),
+ on(6),
+ warning(7),
+ tooLow(8),
+ tooHigh(9)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the sensor"
+ ::= { cmcTcUnit4SensorEntry 4 }
+
+ unit4SensorValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Value of sensor"
+ ::= { cmcTcUnit4SensorEntry 5 }
+
+ unit4SensorSetHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for high setpoint of sensor"
+ ::= { cmcTcUnit4SensorEntry 6 }
+
+ unit4SensorSetLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for low setpoint of sensor"
+ ::= { cmcTcUnit4SensorEntry 7 }
+
+ unit4SensorSetWarn OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for warning setpoint of sensor,
+ also used as fan threshold"
+ ::= { cmcTcUnit4SensorEntry 8 }
+
+-- table END
+
+-- Outputs
+ cmcTcUnit4NumberOfOutputs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of outputs available on sensor unit 4"
+ ::= { cmcTcStatusUnit4Outputs 1 }
+
+-- table with entry for each output available on this unit
+
+ cmcTcUnit4OutputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit4OutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of output table"
+ ::= { cmcTcStatusUnit4Outputs 2 }
+
+ cmcTcUnit4OutputEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit4OutputEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of output table"
+ INDEX { unit4OutputIndex }
+ ::= { cmcTcUnit4OutputTable 1 }
+
+ CmcTcUnit4OutputEntry ::=
+ SEQUENCE {
+ unit4OutputIndex
+ INTEGER,
+ unit4OutputType
+ INTEGER,
+ unit4OutputText
+ DisplayString,
+ unit4OutputStatus
+ INTEGER,
+ unit4OutputValue
+ INTEGER,
+ unit4OutputSet
+ INTEGER,
+ unit4OutputConfig
+ INTEGER,
+ unit4OutputDelay
+ INTEGER,
+ unit4OutputTimeoutAction
+ INTEGER
+ }
+
+ unit4OutputIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of output entries. Its value ranges
+ between 1 and the value of cmcTcUnit4NumberOfOutputs."
+ ::= { cmcTcUnit4OutputEntry 1 }
+
+ unit4OutputType OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail (1),
+ failure (2),
+ overflow (3),
+ doorLock (4),
+ univLock1 (5),
+ univLock2 (6),
+ fan (7),
+ fanSpeedContr (8),
+ universalOut (9),
+ roomLock(10),
+ powerOut(11),
+ doorLockMaster(12),
+ doorLockFRi (13),
+ setpoint (14),
+ setpointTimax (15),
+ hysteresisRCT (16),
+ commandRCT (17),
+ relayPSM (18),
+ setHighPSM (19),
+ setLowPSM (20),
+ setpointRTT (21),
+ setTimaxRTT (22),
+ powerOut1(23),
+ controlModeLCP (30),
+ minFanSpeedLCP (31),
+ minDeltaTLCP (32),
+ maxDeltaTLCP (33),
+ kPLCP (34),
+ kILCP (35),
+ kDLCP (36),
+ flowRateLCP(37),
+ cwValueLCP (38),
+ deltaTLCP (39),
+ ctrModLCP (40),
+ voltHighPSM (42),
+ voltLowPSM (43),
+ ampHighPSM (44),
+ ampLowPSM (45),
+ commandPSM (46)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Type of output which is connected to sensor unit 4 to output[unit4OutputIndex]
+ 1: no output connected
+ 2: output failure
+ 3: value overflow
+ 4: output type 1, door locking TS8,Ergoform
+ 5: output type 2, universal lock 1, lock with power
+ 6: output type 3, universal lock 2, unlock with power
+ 7: output type 4, fan relay
+ 8: output type 5, fan controlled
+ 9: output type 6, universal relay output
+ 10: output type 7, room door lock
+ 11: output type 8, power output
+ 12: output type 9, door lock with Master key
+ 13: output type 10, door lock FR(i)
+ 14: setpoint (FCS, RTT)
+ 15: setpoint temperature monitoring (RTT)
+ 16: hysteresis of setpoint (RCT)
+ 17: command for remote control of RCT
+ 18: relay PSM, 1=On, 0=Off
+ 19: high setpoint current monitoring PSM
+ 20: low setpoint current monitoring PSM
+ 21: setpoint temperature RTT
+ 22: setpoint temperature monitoring RTT
+ 23: power output 20A
+ 30: control mode LCP
+ 31: min fan speed (fan control) LCP
+ 32: min delta T (fan control) LCP
+ 33: max delta T (fan control) LCP
+ 34: PID controller, KP, LCP
+ 35: PID controller, KI, LCP
+ 36 PID controller, KD, LCP
+ 37 flowrate flowmeter, LCP
+ 38: cw value of water (default: 4187) LCP
+ 39: deltaT, LCP
+ 40: control mode, LCP
+ 42: setpoint high voltage PSM
+ 43: setpoint low voltage PSM
+ 44: setpoint high current PSM
+ 45: setpoint low current PSM
+ 46: command PSM"
+ ::= { cmcTcUnit4OutputEntry 2 }
+
+
+ unit4OutputText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each output (entry in the table)"
+ ::= { cmcTcUnit4OutputEntry 3 }
+
+ unit4OutputStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ off(5),
+ on(6),
+ setOff(7),
+ setOn(8)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the output"
+ ::= { cmcTcUnit4OutputEntry 4 }
+
+ unit4OutputValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for output"
+ ::= { cmcTcUnit4OutputEntry 5 }
+
+ unit4OutputSet OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (1),
+ on (2),
+ lock (3),
+ unlock (4),
+ unlockDelay (5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Command for output"
+ ::= { cmcTcUnit4OutputEntry 6 }
+
+ unit4OutputConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ disRemote (1),
+ enRemote (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Configuration for output
+ 1: disable remote control (e.g. keypad)
+ 2: enable remote control "
+ ::= { cmcTcUnit4OutputEntry 7 }
+
+ unit4OutputDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unsigned Value for delay,
+ after this time the output will fall into the previous state"
+ ::= { cmcTcUnit4OutputEntry 8 }
+
+ unit4OutputTimeoutAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ stay (1),
+ off (2),
+ on (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "State for output if timeout (RS422) occurs"
+ ::= { cmcTcUnit4OutputEntry 9 }
+
+
+-- Msgs
+
+ cmcTcUnit4NumberOfMsgs OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of alarms that can be created with sensor unit 4"
+ ::= { cmcTcStatusUnit4Msg 1 }
+
+-- table with entry for each alarm available on this unit
+
+ cmcTcUnit4MsgTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcUnit4MsgEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of message table"
+ ::= { cmcTcStatusUnit4Msg 2 }
+
+ cmcTcUnit4MsgEntry OBJECT-TYPE
+ SYNTAX CmcTcUnit4MsgEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of message table"
+ INDEX { unit4MsgIndex }
+ ::= { cmcTcUnit4MsgTable 1 }
+
+ CmcTcUnit4MsgEntry ::=
+ SEQUENCE {
+ unit4MsgIndex
+ INTEGER,
+ unit4MsgText
+ DisplayString,
+ unit4MsgStatus
+ INTEGER,
+ unit4MsgRelay
+ INTEGER,
+ unit4MsgBeeper
+ INTEGER,
+ unit4MsgTrap1
+ INTEGER,
+ unit4MsgTrap2
+ INTEGER,
+ unit4MsgTrap3
+ INTEGER,
+ unit4MsgTrap4
+ INTEGER,
+ unit4MsgQuit
+ INTEGER
+ }
+
+ unit4MsgIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of alarm entries. Its value ranges
+ between 1 and the value of cmcTcUnit4NumberOfMsgs."
+ ::= { cmcTcUnit4MsgEntry 1 }
+
+ unit4MsgText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each message (entry in the table)"
+ ::= { cmcTcUnit4MsgEntry 2 }
+
+ unit4MsgStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ configChanged(2),
+ error(3),
+ ok(4),
+ alarm(5),
+ warning(6),
+ tooLow(7),
+ tooHigh(8),
+ setOff(9),
+ setOn(10),
+ open(11),
+ closed(12),
+ locked(13),
+ unlRemote(14),
+ unlReaderKeypad(15),
+ unlSNMP(16),
+ unlWEB(17),
+ unlTimer(18),
+ noAccess(19),
+ circuit1 (20),
+ circuit2 (21),
+ lowBatt (22)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual message status
+ 1: not available
+ 2: configuration has changed (sensor new, changed, lost)
+ 3: error
+ 4: OK
+ 5: alarm, e.g. smoke, vibration...
+ 6: warning of analog value, value reached warning threshold
+ 7: analog value too low, value reached low threshold
+ 8: analog value too high, value reached high threshold
+ 9: output is set to OFF
+ 10: output is set to ON
+ 11: door is open
+ 12: door is closed
+ 13: door is locked
+ 14: door is unlocked by remote input, e.g. external cardreader
+ 15: door is unlocked by reader or keypad connected to I2C
+ 16: door is unlocked by SNMP set command (unit1OutputSet)
+ 17: door is unlocked by WEB
+ 18: door is unlocked by timer
+ 19: no access, wrong keycode or cardnumber
+ 20: orientation of PSM-Unit is circuit 1
+ 21: orientation of PSM-Unit is circuit 2
+ 22: battery low, wireless sensor"
+ ::= { cmcTcUnit4MsgEntry 3 }
+
+ unit4MsgRelay OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm relay for this alarm
+ 1: no switching of alarm relay
+ 2: switching of alarm relay"
+ ::= { cmcTcUnit4MsgEntry 4 }
+
+ unit4MsgBeeper OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm beeper for this alarm
+ 1: no audible alarm
+ 2: audible alarm"
+ ::= { cmcTcUnit4MsgEntry 5 }
+
+ unit4MsgTrap1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 1 activated"
+ ::= { cmcTcUnit4MsgEntry 6 }
+
+ unit4MsgTrap2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 2 activated"
+ ::= { cmcTcUnit4MsgEntry 7 }
+
+ unit4MsgTrap3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 3 activated"
+ ::= { cmcTcUnit4MsgEntry 8 }
+
+ unit4MsgTrap4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 4 and Event Logging activated"
+ ::= { cmcTcUnit4MsgEntry 9 }
+
+ unit4MsgQuit OBJECT-TYPE
+ SYNTAX INTEGER {
+ auto (1),
+ manual (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset of this alarm
+ 1: auto
+ 2: manual, alarm needs confirmation, e. g. with 'C' key"
+ ::= { cmcTcUnit4MsgEntry 10 }
+-- table END
+
+
+--Status extension unit
+ cmcTcValuesRelay OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm relay for alarm ext. unit(s)
+ 1: no switching of alarm relay
+ 2: switching of alarm relay"
+ ::= { cmcTcStatusExtUnit 1 }
+
+ cmcTcValuesBeeper OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup of Alarm beeper for alarm ext. unit(s)
+ 1: no audible alarm
+ 2: audible alarm"
+ ::= { cmcTcStatusExtUnit 2 }
+
+ cmcTcValuesTrap1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 1 activated"
+ ::= { cmcTcStatusExtUnit 3 }
+
+ cmcTcValuesTrap2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 2 activated"
+ ::= { cmcTcStatusExtUnit 4 }
+
+ cmcTcValuesTrap3 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 3 activated"
+ ::= { cmcTcStatusExtUnit 5 }
+
+ cmcTcValuesTrap4 OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable (1),
+ enable (2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Trap receiver 4 and Event Logging activated"
+ ::= { cmcTcStatusExtUnit 6 }
+
+ cmcTcNumberOfValues OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of values availabel on extension units connected to the CMC"
+ ::= { cmcTcStatusExtUnit 7 }
+
+-- table with entry for each value available on extension units
+ cmcTcValuesTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcValuesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of values-table"
+ ::= { cmcTcStatusExtUnit 8 }
+
+ cmcTcValuesEntry OBJECT-TYPE
+ SYNTAX CmcTcValuesEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of values-table"
+ INDEX { valuesIndex }
+ ::= { cmcTcValuesTable 1 }
+
+ CmcTcValuesEntry ::=
+ SEQUENCE {
+ valuesIndex
+ INTEGER,
+ valuesText
+ DisplayString,
+ valuesStatus
+ INTEGER,
+ valuesValue
+ INTEGER,
+ valuesSetHigh
+ INTEGER,
+ valuesSetLow
+ INTEGER
+ }
+
+ valuesIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of value entries. Its value ranges
+ between 1 and the value of cmcTcNumberOfValues."
+ ::= { cmcTcValuesEntry 1 }
+
+
+ valuesText OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..20))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Descriptional text for each value (entry in the table)
+ of the extension card"
+ ::= { cmcTcValuesEntry 2 }
+
+ valuesStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ notAvail(1),
+ lost(2),
+ changed(3),
+ ok(4),
+ tooLow(5),
+ tooHigh(6),
+ error(7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the value of the extension card"
+ ::= { cmcTcValuesEntry 3 }
+
+ valuesValue OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Value of sensor"
+ ::= { cmcTcValuesEntry 4 }
+
+ valuesSetHigh OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for high setpoint of sensor"
+ ::= { cmcTcValuesEntry 5 }
+
+ valuesSetLow OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Value for low setpoint of sensor"
+ ::= { cmcTcValuesEntry 6 }
+-- table END
+
+
+--setupGeneral-group
+ cmcTcSetTempUnit OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Unit of all temperature values and setpoints, Celsius or Fahrenheit"
+ ::= { cmcTcSetupGeneral 1 }
+
+ cmcTcSetBeeper OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(1),
+ on(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Audible alarm in CMC-TC unit:
+ (2): beeper is on
+ (1): beeper is off (general)"
+ ::= { cmcTcSetupGeneral 2 }
+
+
+ cmcTcQuitRelay OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable acknowledging currently active alarm relay
+ (with 'C' on CMC-TC)."
+ ::= { cmcTcSetupGeneral 3 }
+
+
+ cmcTcLogicRelay OBJECT-TYPE
+ SYNTAX INTEGER {
+ closeAtAlarm(1),
+ openAtAlarm(2),
+ off(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Logic of alarm relay:
+ (1) Relay will pick up in case of an alarm
+ (2) Relay will release in case of an alarm
+ (3) Relay off (general)"
+ ::= { cmcTcSetupGeneral 4 }
+
+ cmcTcWebAccess OBJECT-TYPE
+ SYNTAX INTEGER {
+ viewOnly(1),
+ fullAccess(2),
+ off(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Web access via HTTP:
+ (1) view only
+ (2) full Access, read and set
+ (3) Web disabled (general)"
+ ::= { cmcTcSetupGeneral 5 }
+
+
+-- SetupClock
+ cmcTcSetupDate OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..10))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "actual Date in format DD.MM.YYYY"
+ ::= { cmcTcSetupGeneral 6 }
+
+ cmcTcSetupTime OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..8))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)"
+ ::= { cmcTcSetupGeneral 7 }
+
+-- table for timer function
+
+ cmcTcTimerNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of value-table entries=number of outlets available on this unit"
+ ::= { cmcTcTimerTable1 1 }
+
+ cmcTcTimerTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcTimerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Headline of status-table"
+ ::= { cmcTcTimerTable1 2 }
+
+ cmcTcTimerEntry OBJECT-TYPE
+ SYNTAX CmcTcTimerEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of timer-table"
+ INDEX { cmcTcTimerIndex }
+ ::= { cmcTcTimerTable 1 }
+
+ CmcTcTimerEntry ::=
+ SEQUENCE {
+ cmcTcTimerIndex
+ INTEGER,
+ cmcTcTimerStatus
+ INTEGER,
+ cmcTcTimerDayOfWeek
+ INTEGER,
+ cmcTcTimeOn
+ DisplayString,
+ cmcTcTimeOff
+ DisplayString,
+ cmcTcTimeControl
+ INTEGER,
+ cmcTcTimerFunction
+ INTEGER
+ }
+
+ cmcTcTimerIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the list of timer entries. Its value ranges
+ between 1 and the value of cmcTcTimerNumber."
+ ::= { cmcTcTimerEntry 1 }
+
+ cmcTcTimerStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ switchedOff(1),
+ switchedOn(2),
+ noTime(3)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Actual status of the timer"
+ ::= { cmcTcTimerEntry 2 }
+
+ cmcTcTimerDayOfWeek OBJECT-TYPE
+ SYNTAX INTEGER {
+ sun(1),
+ mon(2),
+ tue(3) ,
+ wed(4),
+ thu(5),
+ fri(6),
+ sat(7),
+ sat-sun(8),
+ mon-fri(9),
+ mon-sun(10)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Selection of day of week for timer to switch"
+ ::= { cmcTcTimerEntry 3 }
+
+ cmcTcTimeOn OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..5))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Time to switch on current function,
+ Format: HH:MM"
+ ::= { cmcTcTimerEntry 4 }
+
+ cmcTcTimeOff OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..5))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Time to switch off current function,
+ Format: HH:MM"
+ ::= { cmcTcTimerEntry 5 }
+
+ cmcTcTimeControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Control via RTC"
+ ::= { cmcTcTimerEntry 6 }
+
+ cmcTcTimerFunction OBJECT-TYPE
+ SYNTAX INTEGER {
+ disKeypad1-1 (1),
+ disKeypad2-1 (2),
+ disKeypad1-2 (3),
+ disKeypad2-2 (4),
+ disKeypad1-3 (5),
+ disKeypad2-3 (6),
+ disKeypad1-4 (7),
+ disKeypad2-4 (8),
+ unlDoor1-1 (9),
+ unlDoor2-1 (10),
+ unlDoor1-2 (11),
+ unlDoor2-2 (12),
+ unlDoor1-3 (13),
+ unlDoor2-3 (14),
+ unlDoor1-4 (15),
+ unlDoor2-5 (16),
+ disTrapRec1 (17),
+ disTrapRec2 (18),
+ disTrapRec3 (19),
+ disTrapRec4 (20),
+ disSMS (21),
+ schedule1 (22),
+ schedule2 (23),
+ schedule3 (24),
+ schedule4 (25),
+ disSMS1 (26),
+ disSMS2 (27),
+ disSMS3 (28),
+ disSMS4 (29)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Function which is controlled via timer
+ 1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled
+ 2: unlock via keypad 2 on unit 1 or remote input lock 2 is disabled
+ 3 unlock via keypad 1 on unit 2 or remote input lock 1 is disabled
+ 4: unlock via keypad 2 on unit 2 or remote input lock 2 is disabled
+ 5: unlock via keypad 1 on unit 3 or remote input lock 1 is disabled
+ 6: unlock via keypad 2 on unit 3 or remote input lock 2 is disabled
+ 7: unlock via keypad 1 on unit 4 or remote input lock 1 is disabled
+ 8: unlock via keypad 2 on unit 4 or remote input lock 2 is disabled
+ 9: Lock of door 1 on unit 1 will be unlocked
+ 10: Lock of door 2 on unit 1 will be unlocked
+ 11: Lock of door 1 on unit 2 will be unlocked
+ 12: Lock of door 2 on unit 2 will be unlocked
+ 13: Lock of door 1 on unit 3 will be unlocked
+ 14: Lock of door 2 on unit 3 will be unlocked
+ 15: Lock of door 1 on unit 4 will be unlocked
+ 16: Lock of door 2 on unit 4 will be unlocked
+ 17-20: sending Traps to this Trap receiver will be disabled
+ 21: sending SMS will be disabled generally
+ 22-25: Scheduled alarm off
+ 26-29: sending SMS to phone number 1..4 will be disabled"
+ ::= { cmcTcTimerEntry 7 }
+
+
+
+--cmcTcTrapTable-group
+
+ cmcTcTraptableNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Number of trapTable entries. The number of trap-receiver"
+ ::= { cmcTcTraps 1 }
+
+ cmcTcTrapTableTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF CmcTcTrapTableEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of trap-receiver entries"
+ ::= { cmcTcTraps 2 }
+
+ cmcTcTrapTableEntry OBJECT-TYPE
+ SYNTAX CmcTcTrapTableEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "Entries of trapTable"
+ INDEX { trapIndex }
+ ::= { cmcTcTrapTableTable 1 }
+
+ CmcTcTrapTableEntry ::=
+ SEQUENCE {
+ trapIndex
+ INTEGER,
+ trapStatus
+ INTEGER,
+ trapIPaddress
+ DisplayString
+ }
+
+ trapIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "Index for the trap-receiver-table. Its value ranges between
+ 1 and the value of traptableNumber "
+ ::= { cmcTcTrapTableEntry 1 }
+
+ trapStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ enabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable trap receiver"
+ ::= { cmcTcTrapTableEntry 2 }
+
+ trapIPaddress OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "IP-address of trap-receiver"
+ ::= { cmcTcTrapTableEntry 3 }
+
+
+--cmcTcControl-group (Added in Version 1.1)
+ cmcTcQuitUnit OBJECT-TYPE
+ SYNTAX INTEGER {
+ noQuit(1),
+ quit(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Command to quit (acknowledge) alarms of CMC-TC unit.
+ Setting to 'quit' (2) will have same result as pressing 'C' on Units.
+ Variable is automatically set back to 'noQuit' (1)."
+ ::= { cmcTcControl 1 }
+
+
+--Traps
+ alarmSensorUnit1 TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ unit1MsgIndex, unit1MsgText, unit1MsgStatus, unit1SensorValue }
+ DESCRIPTION
+ "Alarm of sensor unit 1"
+--
+--#TYPE "Sensor unit alarm"
+--#SUMMARY "Location: %s, Alarm[%s]: %s, Status: %s, from: %s, contact %s"
+--#ARGUMENTS {3,4,6,5,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 1
+
+ alarmSensorUnit2 TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ unit2MsgIndex, unit2MsgText, unit2MsgStatus, unit2SensorValue }
+ DESCRIPTION
+ "Alarm of sensor unit 2"
+--
+--#TYPE "Sensor unit alarm"
+--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
+--#ARGUMENTS {3,4,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 2
+
+
+ alarmSensorUnit3 TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ unit3MsgIndex, unit3MsgText, unit3MsgStatus, unit3SensorValue }
+ DESCRIPTION
+ "Alarm of sensor unit 3"
+--
+--#TYPE "Sensor unit alarm"
+--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
+--#ARGUMENTS {3,4,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 3
+
+ alarmSensorUnit4 TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ unit4MsgIndex, unit4MsgText, unit4MsgStatus, unit4SensorValue }
+ DESCRIPTION
+ "Alarm of sensor unit 4"
+--
+--#TYPE "Sensor unit alarm"
+--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
+--#ARGUMENTS {3,4,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 4
+
+
+ alarmUnit1 TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ cmcTcUnit1Text, cmcTcUnit1Status }
+ DESCRIPTION
+ "Alarm of unit 1"
+--
+--#TYPE "Unit alarm"
+--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s"
+--#ARGUMENTS {3,4,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 5
+
+ alarmUnit2 TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ cmcTcUnit2Text, cmcTcUnit2Status }
+ DESCRIPTION
+ "Alarm of unit 2"
+--
+--#TYPE "Unit alarm"
+--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s"
+--#ARGUMENTS {3,4,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 6
+
+
+ alarmUnit3 TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ cmcTcUnit3Text, cmcTcUnit3Status }
+ DESCRIPTION
+ "Alarm of unit 3"
+--
+--#TYPE "Unit alarm"
+--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s"
+--#ARGUMENTS {3,4,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 7
+
+
+ alarmUnit4 TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ cmcTcUnit4Text, cmcTcUnit4Status }
+ DESCRIPTION
+ "Alarm of unit 4"
+--
+--#TYPE "Unit alarm"
+--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s"
+--#ARGUMENTS {3,4,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 8
+
+
+ alarmValues TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysContact, sysName, sysLocation,
+ valuesIndex, valuesText, valuesStatus }
+ DESCRIPTION
+ "Alarm of values measured by external card"
+--
+--#TYPE "Values alarm"
+--#SUMMARY "Location: %s, Message: %s, Status: %s from: %s, contact %s"
+--#ARGUMENTS {3,5,6,2,1}
+--#SEVERITY MAJOR
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 9
+
+ configChanged TRAP-TYPE
+ ENTERPRISE cmcTc
+ VARIABLES { sysDescr, sysContact, sysName, sysLocation }
+ DESCRIPTION
+ "The configuration of the cmc has changed,
+ this trap is send if new setup is saved.
+ Configuration can be changed by Terminal, Telnet, Web or SNMP
+ *** NOT IMPLEMENTED *** "
+--
+--#TYPE "Configuration is changed"
+--#SUMMARY "Location: %s, Configuration of %s, unit %s has changed, contact %s"
+--#ARGUMENTS {3,2,0,1}
+--#SEVERITY INFORMATIONAL
+--#TIMEINDEX 6
+--#STATE OPERATIONAL
+--
+ ::= 10
+
+
+ END
+
|