summaryrefslogtreecommitdiff
path: root/MIBS/riedo/NETTRACK-E3METER-SNMP-MIB
diff options
context:
space:
mode:
authorDavid Leutgeb <david.leutgeb@mannundmouse.com>2023-12-05 12:25:34 +0100
committerDavid Leutgeb <david.leutgeb@mannundmouse.com>2023-12-05 12:25:34 +0100
commit98a672123c7872f6b9b75a9a2b6bb3aea504de6a (patch)
tree9b13bd7f563c3198047bd359195327cf28b3caf0 /MIBS/riedo/NETTRACK-E3METER-SNMP-MIB
downloadmibs-98a672123c7872f6b9b75a9a2b6bb3aea504de6a.tar.gz
mibs-98a672123c7872f6b9b75a9a2b6bb3aea504de6a.zip
Initial commitHEADmain
Diffstat (limited to 'MIBS/riedo/NETTRACK-E3METER-SNMP-MIB')
-rw-r--r--MIBS/riedo/NETTRACK-E3METER-SNMP-MIB1078
1 files changed, 1078 insertions, 0 deletions
diff --git a/MIBS/riedo/NETTRACK-E3METER-SNMP-MIB b/MIBS/riedo/NETTRACK-E3METER-SNMP-MIB
new file mode 100644
index 0000000..aabd7df
--- /dev/null
+++ b/MIBS/riedo/NETTRACK-E3METER-SNMP-MIB
@@ -0,0 +1,1078 @@
+NETTRACK-E3METER-SNMP-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ MODULE-IDENTITY,
+ OBJECT-TYPE,
+ Integer32,
+ enterprises
+ FROM SNMPv2-SMI
+ TEXTUAL-CONVENTION,
+ TruthValue
+ FROM SNMPv2-TC
+ ;
+
+nettrack OBJECT IDENTIFIER
+ ::= { enterprises 21695 }
+
+public OBJECT IDENTIFIER
+ ::= { nettrack 1 }
+
+e3Mib
+ MODULE-IDENTITY
+ LAST-UPDATED "201810090000Z"
+ ORGANIZATION "net-track GmbH"
+ CONTACT-INFO "net-track GmbH
+ Duensstrasse 1
+ 3186 Duedingen
+ Switzerland
+ www.net-track.ch"
+ DESCRIPTION "Management Information for E3METER IPM products
+ www.e3meter.com"
+ REVISION "201810090000Z"
+ DESCRIPTION "Added RCM traps."
+ REVISION "201810080000Z"
+ DESCRIPTION "Added RCM-related stuff."
+ REVISION "201604180000Z"
+ DESCRIPTION "Added e3IpmAlarmTable."
+ REVISION "201602030000Z"
+ DESCRIPTION "Added traps."
+ REVISION "201204120000Z"
+ DESCRIPTION "Added import of TEXTUAL-CONVENTION."
+ REVISION "201111020000Z"
+ DESCRIPTION "Added channel type and channel groups."
+ REVISION "201108190000Z"
+ DESCRIPTION "Added e3IpmChannelName."
+ REVISION "201101260000Z"
+ DESCRIPTION "Corrected some syntax errors for very picky parsers."
+ REVISION "201012060000Z"
+ DESCRIPTION "Added sensor data."
+ REVISION "201010200000Z"
+ DESCRIPTION "Initial version of this MIB module."
+ ::= { public 10 }
+
+e3Ipm OBJECT IDENTIFIER
+ ::= { e3Mib 7 }
+
+-- ===========================================================================
+-- Textual conventions
+--
+
+Watts ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Watts"
+ SYNTAX INTEGER
+
+VoltAmpereReactives ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Volt-ampere reactives"
+ SYNTAX Integer32
+
+VoltAmperes ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Volt-amperes"
+ SYNTAX Integer32
+
+WattHours ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Watt hours"
+ SYNTAX Integer32
+
+VoltAmpereReactiveHours ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Volt-ampere reactive hours"
+ SYNTAX Integer32
+
+VoltAmpereHours ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Volt-ampere hours"
+ SYNTAX Integer32
+
+MilliAmperes ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Milli-amperes"
+ SYNTAX Integer32
+
+MilliVolts ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Milli-volts"
+ SYNTAX Integer32
+
+MilliHertz ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Milli-hertz"
+ SYNTAX Integer32
+
+DeciDegreesCelsius ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Deci-degrees celsius"
+ SYNTAX Integer32
+
+Permil ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Per mil"
+ SYNTAX INTEGER
+
+-- ===========================================================================
+-- Agent information
+--
+
+e3IpmInfo OBJECT IDENTIFIER
+ ::= { e3Ipm 1 }
+
+e3IpmInfoSerial OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Serial number."
+ ::= { e3IpmInfo 1 }
+
+e3IpmInfoModel OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Model number."
+ ::= { e3IpmInfo 2 }
+
+e3IpmInfoHWVersion OBJECT-TYPE
+ SYNTAX INTEGER {
+ rev-a (0),
+ rev-b (1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Hardware revision."
+ ::= { e3IpmInfo 3 }
+
+e3IpmInfoFWVersion OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Integer representation of the firmware revision
+ (major.minor) represented as a 16 bit integer."
+ ::= { e3IpmInfo 4 }
+
+e3IpmInfoMeters OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of power meters in this IPS."
+ ::= { e3IpmInfo 5 }
+
+-- ===========================================================================
+-- IPM meters
+--
+
+e3IpmMeterTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF E3IpmMeterEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The e3IpmMeterTable holds information related to the
+ powermeters of all IPS nodes."
+ ::= { e3Ipm 2 }
+
+e3IpmMeterEntry OBJECT-TYPE
+ SYNTAX E3IpmMeterEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Holds the information related to one specific powermeter."
+ INDEX { e3IpmMeter }
+ ::= { e3IpmMeterTable 1 }
+
+E3IpmMeterEntry ::= SEQUENCE {
+ e3IpmMeter Integer32,
+ e3IpmEnergyP WattHours,
+ e3IpmEnergyQ VoltAmpereReactiveHours,
+ e3IpmEnergyS VoltAmpereHours,
+ e3IpmPowerP Watts,
+ e3IpmPowerQ VoltAmpereReactives,
+ e3IpmPowerS VoltAmperes,
+ e3IpmUrms MilliVolts,
+ e3IpmIrms MilliAmperes,
+ e3IpmFrequency MilliHertz,
+ e3IpmChannelName OCTET STRING,
+ e3IpmChannelType INTEGER
+ }
+
+e3IpmMeter OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of the powermeter of this IPS."
+ ::= { e3IpmMeterEntry 1 }
+
+e3IpmEnergyP OBJECT-TYPE
+ SYNTAX WattHours
+ UNITS "Wh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Active energy in watt hours."
+ ::= { e3IpmMeterEntry 2 }
+
+e3IpmEnergyQ OBJECT-TYPE
+ SYNTAX VoltAmpereReactiveHours
+ UNITS "varh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Reactive energy in volt-ampere reactives hours."
+ ::= { e3IpmMeterEntry 3 }
+
+e3IpmEnergyS OBJECT-TYPE
+ SYNTAX VoltAmpereHours
+ UNITS "VAh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Apparent energy in volt-ampere hours."
+ ::= { e3IpmMeterEntry 4 }
+
+e3IpmPowerP OBJECT-TYPE
+ SYNTAX Watts
+ UNITS "W"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Active power at a given instant."
+ ::= { e3IpmMeterEntry 5 }
+
+e3IpmPowerQ OBJECT-TYPE
+ SYNTAX VoltAmpereReactives
+ UNITS "var"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Reactive power at a given instant."
+ ::= { e3IpmMeterEntry 6 }
+
+e3IpmPowerS OBJECT-TYPE
+ SYNTAX VoltAmperes
+ UNITS "VA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Apparent power at a given instant."
+ ::= { e3IpmMeterEntry 7 }
+
+e3IpmUrms OBJECT-TYPE
+ SYNTAX MilliVolts
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "RMS voltage at a given instant."
+ ::= { e3IpmMeterEntry 8 }
+
+e3IpmIrms OBJECT-TYPE
+ SYNTAX MilliAmperes
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "RMS current at a given instant."
+ ::= { e3IpmMeterEntry 9 }
+
+e3IpmFrequency OBJECT-TYPE
+ SYNTAX MilliHertz
+ UNITS "mHz"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Frequency measured a given instant."
+ ::= { e3IpmMeterEntry 10 }
+
+e3IpmChannelName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(0..15))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel name."
+ ::= { e3IpmMeterEntry 11 }
+
+e3IpmChannelType OBJECT-TYPE
+ SYNTAX INTEGER {
+ live-wire (0),
+ neutral-wire (1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel type: For neutral wire channels, only I_rms will
+ contain meaningful values."
+ ::= { e3IpmMeterEntry 12 }
+
+-- ===========================================================================
+-- IPM sensors
+--
+
+e3IpmSensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF E3IpmSensorEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The e3IpmSensorTable holds information related to the
+ sensor of this IPM."
+ ::= { e3Ipm 3 }
+
+e3IpmSensorEntry OBJECT-TYPE
+ SYNTAX E3IpmSensorEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Holds the information related to one specific sensor."
+ INDEX { e3IpmSensor }
+ ::= { e3IpmSensorTable 1 }
+
+E3IpmSensorEntry ::= SEQUENCE {
+ e3IpmSensor Integer32,
+ e3IpmSensorType INTEGER,
+ e3IpmSensorVersion OCTET STRING,
+ e3IpmSensorTemperatureCelsius DeciDegreesCelsius,
+ e3IpmSensorHumidity Permil
+ }
+
+e3IpmSensor OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Sensor port number."
+ ::= { e3IpmSensorEntry 1 }
+
+e3IpmSensorType OBJECT-TYPE
+ SYNTAX INTEGER {
+ none (0),
+ temp (1),
+ temp-humidity (2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Sensor type."
+ ::= { e3IpmSensorEntry 2 }
+
+e3IpmSensorVersion OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(0..15))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Sensor version."
+ ::= { e3IpmSensorEntry 3 }
+
+e3IpmSensorTemperatureCelsius OBJECT-TYPE
+ SYNTAX DeciDegreesCelsius
+ UNITS "deg-C/10"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Temperature in tenth degrees."
+ ::= { e3IpmSensorEntry 4 }
+
+e3IpmSensorHumidity OBJECT-TYPE
+ SYNTAX Permil
+ UNITS "/1000"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Relative humidity in per mil."
+ ::= { e3IpmSensorEntry 5 }
+
+-- ===========================================================================
+-- IPM predefined channel groups
+--
+
+e3IpmPGroupTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF E3IpmPGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The e3IpmPGroupTable holds information related to predefined
+ channel groups."
+ ::= { e3Ipm 4 }
+
+e3IpmPGroupEntry OBJECT-TYPE
+ SYNTAX E3IpmPGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Holds the information related to one specific group."
+ INDEX { e3IpmPGroup }
+ ::= { e3IpmPGroupTable 1 }
+
+E3IpmPGroupEntry ::= SEQUENCE {
+ e3IpmPGroup Integer32,
+ e3IpmPGName OCTET STRING,
+ e3IpmPGMembers Integer32,
+ e3IpmPGEnergyP WattHours,
+ e3IpmPGEnergyQ VoltAmpereReactiveHours,
+ e3IpmPGEnergyS VoltAmpereHours,
+ e3IpmPGPowerP Watts,
+ e3IpmPGPowerQ VoltAmpereReactives,
+ e3IpmPGPowerS VoltAmperes,
+ e3IpmPGIrms MilliAmperes
+ }
+
+e3IpmPGroup OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Predefined channel group number."
+ ::= { e3IpmPGroupEntry 1 }
+
+e3IpmPGName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(0..15))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group name."
+ ::= { e3IpmPGroupEntry 2 }
+
+e3IpmPGMembers OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A bit set specifying the channels which are
+ members of this channel group. If bit 0 is set,
+ this means that channel CH1 is member of this
+ group. Bit 1 stands for CH2 and so on."
+ ::= { e3IpmPGroupEntry 3 }
+
+e3IpmPGEnergyP OBJECT-TYPE
+ SYNTAX WattHours
+ UNITS "Wh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group active energy in watt hours."
+ ::= { e3IpmPGroupEntry 4 }
+
+e3IpmPGEnergyQ OBJECT-TYPE
+ SYNTAX VoltAmpereReactiveHours
+ UNITS "varh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group reactive energy in volt-ampere reactives hours."
+ ::= { e3IpmPGroupEntry 5 }
+
+e3IpmPGEnergyS OBJECT-TYPE
+ SYNTAX VoltAmpereHours
+ UNITS "VAh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group apparent energy in volt-ampere hours."
+ ::= { e3IpmPGroupEntry 6 }
+
+e3IpmPGPowerP OBJECT-TYPE
+ SYNTAX Watts
+ UNITS "W"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group active power at a given instant."
+ ::= { e3IpmPGroupEntry 7 }
+
+e3IpmPGPowerQ OBJECT-TYPE
+ SYNTAX VoltAmpereReactives
+ UNITS "var"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group reactive power at a given instant."
+ ::= { e3IpmPGroupEntry 8 }
+
+e3IpmPGPowerS OBJECT-TYPE
+ SYNTAX VoltAmperes
+ UNITS "VA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group apparent power at a given instant."
+ ::= { e3IpmPGroupEntry 9 }
+
+e3IpmPGIrms OBJECT-TYPE
+ SYNTAX MilliAmperes
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group RMS current at a given instant."
+ ::= { e3IpmPGroupEntry 10 }
+
+-- ===========================================================================
+-- IPM user defined channel groups
+--
+
+e3IpmUGroupTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF E3IpmUGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The e3IpmUGroupTable holds information related to user
+ defined channel groups."
+ ::= { e3Ipm 5 }
+
+e3IpmUGroupEntry OBJECT-TYPE
+ SYNTAX E3IpmUGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Holds the information related to one specific group."
+ INDEX { e3IpmUGroup }
+ ::= { e3IpmUGroupTable 1 }
+
+E3IpmUGroupEntry ::= SEQUENCE {
+ e3IpmUGroup Integer32,
+ e3IpmUGName OCTET STRING,
+ e3IpmUGMembers Integer32,
+ e3IpmUGEnergyP WattHours,
+ e3IpmUGEnergyQ VoltAmpereReactiveHours,
+ e3IpmUGEnergyS VoltAmpereHours,
+ e3IpmUGPowerP Watts,
+ e3IpmUGPowerQ VoltAmpereReactives,
+ e3IpmUGPowerS VoltAmperes,
+ e3IpmUGIrms MilliAmperes
+ }
+
+e3IpmUGroup OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "User defined channel group number."
+ ::= { e3IpmUGroupEntry 1 }
+
+e3IpmUGName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(0..15))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group name."
+ ::= { e3IpmUGroupEntry 2 }
+
+e3IpmUGMembers OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A bit set specifying the channels which are
+ members of this channel group. If bit 0 is set,
+ this means that channel CH1 is member of this
+ group. Bit 1 stands for CH2 and so on. If no
+ members are configured, the group is inactive."
+ ::= { e3IpmUGroupEntry 3 }
+
+e3IpmUGEnergyP OBJECT-TYPE
+ SYNTAX WattHours
+ UNITS "Wh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group active energy in watt hours."
+ ::= { e3IpmUGroupEntry 4 }
+
+e3IpmUGEnergyQ OBJECT-TYPE
+ SYNTAX VoltAmpereReactiveHours
+ UNITS "varh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group reactive energy in volt-ampere reactives hours."
+ ::= { e3IpmUGroupEntry 5 }
+
+e3IpmUGEnergyS OBJECT-TYPE
+ SYNTAX VoltAmpereHours
+ UNITS "VAh"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group apparent energy in volt-ampere hours."
+ ::= { e3IpmUGroupEntry 6 }
+
+e3IpmUGPowerP OBJECT-TYPE
+ SYNTAX Watts
+ UNITS "W"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group active power at a given instant."
+ ::= { e3IpmUGroupEntry 7 }
+
+e3IpmUGPowerQ OBJECT-TYPE
+ SYNTAX VoltAmpereReactives
+ UNITS "var"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group reactive power at a given instant."
+ ::= { e3IpmUGroupEntry 8 }
+
+e3IpmUGPowerS OBJECT-TYPE
+ SYNTAX VoltAmperes
+ UNITS "VA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group apparent power at a given instant."
+ ::= { e3IpmUGroupEntry 9 }
+
+e3IpmUGIrms OBJECT-TYPE
+ SYNTAX MilliAmperes
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Channel group RMS current at a given instant."
+ ::= { e3IpmUGroupEntry 10 }
+
+-- ===========================================================================
+-- IPM Alarm Settings
+--
+
+e3IpmAlarmTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF E3IpmAlarmTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Holds alarm settings."
+ ::= { e3Ipm 6 }
+
+e3IpmAlarmTableEntry OBJECT-TYPE
+ SYNTAX E3IpmAlarmTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Holds alarm settings for one specific measured value."
+ INDEX { e3IpmAlarmIndex }
+ ::= { e3IpmAlarmTable 1 }
+
+E3IpmAlarmTableEntry ::= SEQUENCE {
+ e3IpmAlarmIndex INTEGER,
+ e3IpmAlarmState INTEGER,
+ e3IpmAlarmCritLowSet TruthValue,
+ e3IpmAlarmCritLow Integer32,
+ e3IpmAlarmWarnLowSet TruthValue,
+ e3IpmAlarmWarnLow Integer32,
+ e3IpmAlarmWarnHighSet TruthValue,
+ e3IpmAlarmWarnHigh Integer32,
+ e3IpmAlarmCritHighSet TruthValue,
+ e3IpmAlarmCritHigh Integer32
+ }
+
+e3IpmAlarmIndex OBJECT-TYPE
+ SYNTAX INTEGER {
+ current-l1 (0),
+ current-l2 (1),
+ current-l3 (2),
+ current-n (3),
+ temp-int (4),
+ temp-ext1 (5),
+ temp-ext2 (6),
+ rh-ext1 (7),
+ rh-ext2 (8)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Defines the alarm described by the current entry. There
+ are alarms for the current of all phases, for the
+ temperature and the relative humidity."
+ ::= { e3IpmAlarmTableEntry 1 }
+
+e3IpmAlarmState OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical-low (0),
+ warn-low (1),
+ normal (2),
+ warn-high (3),
+ critical-high (4),
+ unknown (5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Shows this alarm entries' state. If no alarm settings
+ are defined, the state is unknown."
+ ::= { e3IpmAlarmTableEntry 2 }
+
+e3IpmAlarmCritLowSet OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "True if a 'critical low' alarm level for the current
+ entry is defined, false otherwise."
+ ::= { e3IpmAlarmTableEntry 3 }
+
+e3IpmAlarmCritLow OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The 'critical low' alarm level for the current entry
+ in hundredths of the relevant unit (i.e. amperes, degrees
+ celsius and %RH). If no alarm level is configured, this
+ reads 0."
+ ::= { e3IpmAlarmTableEntry 4 }
+
+e3IpmAlarmWarnLowSet OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "True if a 'warn low' alarm level for the current
+ entry is defined, false otherwise."
+ ::= { e3IpmAlarmTableEntry 5 }
+
+e3IpmAlarmWarnLow OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The 'warn low' alarm level for the current entry
+ in hundredths of the relevant unit (i.e. amperes, degrees
+ celsius and %RH). If no alarm level is configured, this
+ reads 0."
+ ::= { e3IpmAlarmTableEntry 6 }
+
+e3IpmAlarmWarnHighSet OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "True if a 'warn high' alarm level for the current
+ entry is defined, false otherwise."
+ ::= { e3IpmAlarmTableEntry 7 }
+
+e3IpmAlarmWarnHigh OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The 'warn high' alarm level for the current entry
+ in hundredths of the relevant unit (i.e. amperes, degrees
+ celsius and %RH). If no alarm level is configured, this
+ reads 0."
+ ::= { e3IpmAlarmTableEntry 8 }
+
+e3IpmAlarmCritHighSet OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "True if a 'critical high' alarm level for the current
+ entry is defined, false otherwise."
+ ::= { e3IpmAlarmTableEntry 9 }
+
+e3IpmAlarmCritHigh OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The 'critical high' alarm level for the current entry
+ in hundredths of the relevant unit (i.e. amperes, degrees
+ celsius and %RH). If no alarm level is configured, this
+ reads 0."
+ ::= { e3IpmAlarmTableEntry 10 }
+
+-- ===========================================================================
+-- IPM RCM Data
+--
+
+e3IpmRcmTable OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Table holding all residual current monitoring (RCM)
+ data of this IPS."
+ ::= { e3Ipm 7 }
+
+e3IpmRcmTableEntry OBJECT-TYPE
+ SYNTAX E3IpmRcmTableEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "One entry in the RCM table."
+ INDEX { e3IpmRcmChannel }
+ ::= { e3IpmRcmTable 1 }
+
+E3IpmRcmTableEntry ::= SEQUENCE {
+ e3IpmRcmChannel Integer32,
+ e3IpmRcmAcLimit MilliAmperes,
+ e3IpmRcmDcLimit MilliAmperes,
+ e3IpmRcmStatus Integer32,
+ e3IpmRcmAc MilliAmperes,
+ e3IpmRcmDc MilliAmperes
+ }
+
+e3IpmRcmChannel OBJECT-TYPE
+ SYNTAX INTEGER {
+ total(0)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "RCM channel: 0 (total) is the total of all phases in this IPS."
+ ::= { e3IpmRcmTableEntry 1 }
+
+e3IpmRcmAcLimit OBJECT-TYPE
+ SYNTAX MilliAmperes
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The factory configured AC RCM limit. Any measurement
+ higher than this limit is considered a critical problem."
+ ::= { e3IpmRcmTableEntry 2 }
+
+e3IpmRcmDcLimit OBJECT-TYPE
+ SYNTAX MilliAmperes
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The factory configured DC RCM limit. Any measurement
+ higher than this limit is considered a critical problem."
+ ::= { e3IpmRcmTableEntry 3 }
+
+e3IpmRcmStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(0),
+ valid(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Status of the RcmAc/RcmDc data. If the residual
+ current cannot be measured, 0 (unknown) is signalled
+ here, otherwise 1 (valid)."
+ ::= { e3IpmRcmTableEntry 4 }
+
+e3IpmRcmAc OBJECT-TYPE
+ SYNTAX MilliAmperes
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The latest AC RCM measurement."
+ ::= { e3IpmRcmTableEntry 5 }
+
+e3IpmRcmDc OBJECT-TYPE
+ SYNTAX MilliAmperes
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The latest DC RCM measurement."
+ ::= { e3IpmRcmTableEntry 6 }
+
+-- ===========================================================================
+-- IPM Traps
+--
+
+e3IpmTraps OBJECT IDENTIFIER
+ ::= { e3Mib 8 }
+
+-- Current
+
+e3IpmCurrentCritLow NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmCurrentCritLow is triggered when the current
+ on the given channel is less than or equal to the configured
+ critical low threshold."
+ ::= { e3IpmTraps 1 }
+
+e3IpmCurrentWarnLow NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmCurrentWarnLow is triggered when the current
+ on the given channel is less than or equal to the configured
+ warn low threshold."
+ ::= { e3IpmTraps 2 }
+
+e3IpmCurrentNormal NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmCurrentNormal is triggered when the current
+ on the given channel is not outside any configured
+ limits."
+ ::= { e3IpmTraps 3 }
+
+e3IpmCurrentWarnHigh NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmCurrentWarnHigh is triggered when the current
+ on the given channel is greater than or equal to the
+ configured warn high threshold."
+ ::= { e3IpmTraps 4 }
+
+e3IpmCurrentCritHigh NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmCurrentCritHigh is triggered when the current
+ on the given channel is greater than or equal to the
+ configured critical high threshold."
+ ::= { e3IpmTraps 5 }
+
+-- Temperature
+
+e3IpmTempCritLow NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmTempCritLow is triggered when the temperature
+ on the given sensor is less than or equal to the configured
+ critical low threshold."
+ ::= { e3IpmTraps 6 }
+
+e3IpmTempWarnLow NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmTempWarnLow is triggered when the temperature
+ on the given sensor is less than or equal to the configured
+ warn low threshold."
+ ::= { e3IpmTraps 7 }
+
+e3IpmTempNormal NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmTempNormal is triggered when the temperature
+ on the given sensor is not outside any configured
+ limits."
+ ::= { e3IpmTraps 8 }
+
+e3IpmTempWarnHigh NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmTempWarnHigh is triggered when the temperature
+ on the given sensor is greater than or equal to the
+ configured warn high threshold."
+ ::= { e3IpmTraps 9 }
+
+e3IpmTempCritHigh NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmTempCritHigh is triggered when the temperature
+ on the given sensor is greater than or equal to the
+ configured critical high threshold."
+ ::= { e3IpmTraps 10 }
+
+-- Relative Humidity
+
+e3IpmRHCritLow NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRHCritLow is triggered when the relative humidity
+ on the given sensor is less than or equal to the configured
+ critical low threshold."
+ ::= { e3IpmTraps 11 }
+
+e3IpmRHWarnLow NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRHWarnLow is triggered when the relative humidity
+ on the given sensor is less than or equal to the configured
+ warn low threshold."
+ ::= { e3IpmTraps 12 }
+
+e3IpmRHNormal NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRHNormal is triggered when the relative humidity
+ on the given sensor is not outside any configured
+ limits."
+ ::= { e3IpmTraps 13 }
+
+e3IpmRHWarnHigh NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRHWarnHigh is triggered when the relative humidity
+ on the given sensor is greater than or equal to the
+ configured warn high threshold."
+ ::= { e3IpmTraps 14 }
+
+e3IpmRHCritHigh NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRHCritHigh is triggered when the relative humidity
+ on the given sensor is greater than or equal to the
+ configured critical high threshold."
+ ::= { e3IpmTraps 15 }
+
+-- RCM Alarms
+
+e3IpmRcmAcNormal NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmAc }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRcmAcNormal is triggered when the AC part of
+ the residual current falls below the
+ factory-configured limit."
+ ::= { e3IpmTraps 16 }
+
+e3IpmRcmAcCritHigh NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmAc }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRcmAcCritHigh is triggered when the AC part
+ of the residual current is greater than the
+ factory-configured limit."
+ ::= { e3IpmTraps 17 }
+
+e3IpmRcmDcNormal NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmDc }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRcmDcNormal is triggered when the DC part of
+ the residual current falls below the
+ factory-configured limit."
+ ::= { e3IpmTraps 18 }
+
+e3IpmRcmDcCritHigh NOTIFICATION-TYPE
+ OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmDc }
+ STATUS current
+ DESCRIPTION
+ "The e3IpmRcmDcCritHigh is triggered when the DC part
+ of the residual current is greater than the
+ factory-configured limit."
+ ::= { e3IpmTraps 19 }
+
+END