diff --git a/MIBS/poweralert/TRIPPLITE-12X b/MIBS/poweralert/TRIPPLITE-12X new file mode 100644 index 0000000..0a5a357 --- /dev/null +++ b/MIBS/poweralert/TRIPPLITE-12X @@ -0,0 +1,2976 @@ +TRIPPLITE-12X DEFINITIONS ::= BEGIN
+
+IMPORTS
+ TRAP-TYPE
+ FROM RFC-1215
+ DisplayString,
+ TruthValue,
+ TimeStamp,
+ TimeInterval,
+ DateAndTime,
+ AutonomousType,
+ VariablePointer,
+ RowStatus
+ FROM SNMPv2-TC
+ OBJECT-GROUP,
+ NOTIFICATION-GROUP
+ FROM SNMPv2-CONF
+ MODULE-IDENTITY,
+ OBJECT-IDENTITY,
+ OBJECT-TYPE,
+ NOTIFICATION-TYPE,
+ Gauge32,
+ Integer32,
+ IpAddress
+ FROM SNMPv2-SMI
+ PositiveInteger,
+ NonNegativeInteger
+ FROM UPS-MIB
+ tripplite
+ FROM TRIPPLITE;
+
+tlPowerAlert MODULE-IDENTITY
+ LAST-UPDATED "201702281600Z"
+ ORGANIZATION "Tripp Lite"
+ CONTACT-INFO
+ "Software Engineering
+ Tripp Lite
+ 1111 W. 35th St.
+ Chicago, IL 60609"
+ DESCRIPTION
+ "This MIB module defines MIB objects which provide mechanisms for
+ remote management capabilities of Tripplite PowerAlert and related
+ software."
+ REVISION "201702281600Z"
+ "Corrected spelling errors"
+ REVISION "201507290000Z"
+ DESCRIPTION
+ "Removed obsolete legacy PowerAlert 11 sections"
+ REVISION "201410170930Z"
+ DESCRIPTION
+ "Added tlUpsAggregatePowerFactor"
+ REVISION "201409181000Z"
+ DESCRIPTION
+ "Added additional tlUpsInputSource... elements"
+ REVISION "201408060830Z"
+ DESCRIPTION
+ "Added additional elements to tlUpsOutputCircuitTable"
+ REVISION "201405080830Z"
+ DESCRIPTION
+ "Added tlUpsInputSourceSelect"
+ REVISION "201404091000Z"
+ DESCRIPTION
+ "Added missing well known alarms"
+ REVISION "201310301300Z"
+ DESCRIPTION
+ "Consolidated and Released for PAL v12.06.006x"
+
+ ::= { tripplite 90 }
+
+
+--------------------------------------------------------------------------
+-- Enumerations
+--------------------------------------------------------------------------
+
+tlEnumerations OBJECT IDENTIFIER ::= { tripplite 2 }
+
+tlOperatingSystems OBJECT IDENTIFIER ::= { tlEnumerations 1 }
+
+hpux9 OBJECT IDENTIFIER ::= { tlOperatingSystems 1 }
+
+sunos4 OBJECT IDENTIFIER ::= { tlOperatingSystems 2 }
+
+solaris OBJECT IDENTIFIER ::= { tlOperatingSystems 3 }
+
+osf OBJECT IDENTIFIER ::= { tlOperatingSystems 4 }
+
+ultrix OBJECT IDENTIFIER ::= { tlOperatingSystems 5 }
+
+hpux10 OBJECT IDENTIFIER ::= { tlOperatingSystems 6 }
+
+netbsd1 OBJECT IDENTIFIER ::= { tlOperatingSystems 7 }
+
+freebsd OBJECT IDENTIFIER ::= { tlOperatingSystems 8 }
+
+irix OBJECT IDENTIFIER ::= { tlOperatingSystems 9 }
+
+linux OBJECT IDENTIFIER ::= { tlOperatingSystems 10 }
+
+bsdi OBJECT IDENTIFIER ::= { tlOperatingSystems 11 }
+
+openbsd OBJECT IDENTIFIER ::= { tlOperatingSystems 12 }
+
+win32 OBJECT IDENTIFIER ::= { tlOperatingSystems 13 }
+
+hpux11 OBJECT IDENTIFIER ::= { tlOperatingSystems 14 }
+
+win9x OBJECT IDENTIFIER ::= { tlOperatingSystems 50 }
+
+winnt OBJECT IDENTIFIER ::= { tlOperatingSystems 51 }
+
+solspark OBJECT IDENTIFIER ::= { tlOperatingSystems 52 }
+
+solintel OBJECT IDENTIFIER ::= { tlOperatingSystems 53 }
+
+aix OBJECT IDENTIFIER ::= { tlOperatingSystems 54 }
+
+sco OBJECT IDENTIFIER ::= { tlOperatingSystems 55 }
+
+osx OBJECT IDENTIFIER ::= { tlOperatingSystems 56 }
+
+unknown OBJECT IDENTIFIER ::= { tlOperatingSystems 255 }
+
+--------------------------------------------------------------------------
+-- Power Alert System Settings
+--------------------------------------------------------------------------
+-- tlPowerAlert OBJECT IDENTIFIER ::= { tripplite 90 }
+
+tlPASystem OBJECT IDENTIFIER ::= { tlPowerAlert 1 }
+
+tlPAContacts OBJECT IDENTIFIER ::= { tlPASystem 1 }
+
+tlPAEmailContacts OBJECT IDENTIFIER ::= { tlPAContacts 1 }
+
+tlPANumberOfEmailContacts OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number email contacts currently defined."
+ ::= { tlPAEmailContacts 1 }
+
+tlPAEmailContactsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TlPAEmailContactEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list email contact entries. The number of entries is
+ given by the value of tlPANumberOfEmailContacts."
+ ::= { tlPAEmailContacts 2 }
+
+tlPAEmailContactEntry OBJECT-TYPE
+ SYNTAX TlPAEmailContactEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing email contacts information."
+ INDEX { tlPAEmailContactIndex }
+ ::= { tlPAEmailContactsTable 1 }
+
+TlPAEmailContactEntry ::= SEQUENCE {
+ tlPAEmailContactIndex PositiveInteger,
+ tlPAEmailContactRowStatus RowStatus,
+ tlPAEmailContactName DisplayString,
+ tlPAEmailContactAddress DisplayString
+ }
+
+tlPAEmailContactIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This is the index number of the email contact."
+ ::= { tlPAEmailContactEntry 1 }
+
+tlPAEmailContactRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The row status for the tlPAEmailContactTable row"
+ ::= { tlPAEmailContactEntry 2 }
+
+tlPAEmailContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The name of the email contact."
+ ::= { tlPAEmailContactEntry 3 }
+
+tlPAEmailContactAddress OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The address of the email contact."
+ ::= { tlPAEmailContactEntry 4 }
+
+tlPASnmpContacts OBJECT IDENTIFIER ::= { tlPAContacts 2 }
+
+tlPANumberOfSnmpContacts OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number SNMP contacts currently defined."
+ ::= { tlPASnmpContacts 1 }
+
+tlPASnmpContactsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TlPASnmpContactEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list SNMP contact entries. The number of entries is
+ given by the value of tlPANumberOfSnmpContacts."
+ ::= { tlPASnmpContacts 2 }
+
+tlPASnmpContactEntry OBJECT-TYPE
+ SYNTAX TlPASnmpContactEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing SNMP contacts information."
+ INDEX { tlPASnmpContactIndex }
+ ::= { tlPASnmpContactsTable 1 }
+
+TlPASnmpContactEntry ::= SEQUENCE {
+ tlPASnmpContactIndex PositiveInteger,
+ tlPASnmpContactRowStatus RowStatus,
+ tlPASnmpContactName DisplayString,
+ tlPASnmpContactIpAddress DisplayString,
+ tlPASnmpContactPort PositiveInteger,
+ tlPASnmpContactSnmpVersion INTEGER,
+ tlPASnmpContactSecurityName DisplayString,
+ tlPASnmpContactPrivPassword DisplayString,
+ tlPASnmpContactAuthPassword DisplayString
+ }
+
+tlPASnmpContactIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This is the index number of this SNMP contact."
+ ::= { tlPASnmpContactEntry 1 }
+
+tlPASnmpContactRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The row status for the tlPASnmpContactTable row"
+ ::= { tlPASnmpContactEntry 2 }
+
+tlPASnmpContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The name of the SNMP contact."
+ ::= { tlPASnmpContactEntry 3 }
+
+tlPASnmpContactIpAddress OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The IP address of the SNMP contact."
+ ::= { tlPASnmpContactEntry 4 }
+
+tlPASnmpContactPort OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The port of the SNMP contact."
+ ::= { tlPASnmpContactEntry 5 }
+
+tlPASnmpContactSnmpVersion OBJECT-TYPE
+ SYNTAX INTEGER {
+ snmpv1(1),
+ snmpv2c(2),
+ snmpv3(3) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The SNMP contact version to use for sending traps."
+ ::= { tlPASnmpContactEntry 6 }
+
+tlPASnmpContactSecurityName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The SNMP contact security name."
+ ::= { tlPASnmpContactEntry 7 }
+
+tlPASnmpContactPrivPassword OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The SNMP contact priv password to use for sending V3 traps."
+ ::= { tlPASnmpContactEntry 8 }
+
+tlPASnmpContactAuthPassword OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The SNMP contact auth password to use for sending V3 traps."
+ ::= { tlPASnmpContactEntry 9 }
+
+--------------------------------------------------------------------------
+-- UPS Device
+--------------------------------------------------------------------------
+
+tlUPS OBJECT IDENTIFIER ::= { tripplite 100 }
+
+tlUpsObjects OBJECT IDENTIFIER ::= { tlUPS 1 }
+
+tlUpsIdent OBJECT IDENTIFIER ::= { tlUpsObjects 1 }
+
+tlUpsIdentUpsSoftwareChecksum OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A checksum for the UPS software."
+ ::= { tlUpsIdent 1 }
+
+tlUpsIdentSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Serial number for the UPS."
+ ::= { tlUpsIdent 2 }
+
+tlUpsIdentID OBJECT-TYPE
+ SYNTAX Integer32 (0..65535)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A user-supplied ID for the UPS."
+ ::= { tlUpsIdent 3 }
+
+tlUpsSnmpCardSerialNum OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Serial number for the UPS."
+ ::= { tlUpsIdent 4 }
+
+tlUpsSelectedDeviceID OBJECT-TYPE
+ SYNTAX Integer32 (0..65535)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The device ID selected to be used for retrieving data for this mib.
+ As the snmp web card has only one device, this is read only for it"
+ ::= { tlUpsIdent 5 }
+
+tlUpsLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The device location string."
+ ::= { tlUpsIdent 6 }
+
+tlUpsBattery OBJECT IDENTIFIER ::= { tlUpsObjects 2 }
+
+tlUpsBatteryAge OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The age of the battery in years. This is equal to
+ the current date minus tlConfigBattReplDate."
+ ::= { tlUpsBattery 1 }
+
+
+tlUpsTemperatureF OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The temperature of the battery, in Farenheight degrees. This is
+ calculated from upsBatteryTemperature, which is in Celsius degrees."
+ ::= { tlUpsBattery 2 }
+
+tlUpsExternalBatteryAge OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The age of external battery in years. This is equal to
+ the current date minus tlConfigExternalBattReplDate."
+ ::= { tlUpsBattery 3 }
+
+tlUpsInput OBJECT IDENTIFIER ::= { tlUpsObjects 3 }
+
+tlUpsInputNumVoltages OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of input voltages. Phase to phase
+ or phase to neutral. This variable indicates the
+ number of rows in the input table."
+ ::= { tlUpsInput 1 }
+
+tlUpsInputVoltageTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TlUpsInputVoltageEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of voltage input table entries. The number of entries
+ is given by the value of tlUpsInputNumVoltages."
+ ::= { tlUpsInput 2 }
+
+tlUpsInputVoltageEntry OBJECT-TYPE
+ SYNTAX TlUpsInputVoltageEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular input voltage."
+ INDEX { tlUpsInputVoltageIndex }
+ ::= { tlUpsInputVoltageTable 1 }
+
+TlUpsInputVoltageEntry ::= SEQUENCE {
+ tlUpsInputVoltageIndex PositiveInteger,
+ tlUpsInputVoltageType NonNegativeInteger,
+ tlUpsInputVoltage NonNegativeInteger
+}
+
+tlUpsInputVoltageIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The input voltage identifier."
+ ::= { tlUpsInputVoltageEntry 1 }
+
+tlUpsInputVoltageType OBJECT-TYPE
+ SYNTAX INTEGER {
+ phaseToNeutral(0),
+ phaseToPhase(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Whether voltage measured is phase to
+ phase or phase to neutral."
+ ::= { tlUpsInputVoltageEntry 2 }
+
+tlUpsInputVoltage OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "RMS Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present input voltage.
+ A value of 6553 indicates Unknown."
+ ::= { tlUpsInputVoltageEntry 3 }
+
+tlUpsInputSourceSelect OBJECT-TYPE
+ SYNTAX INTEGER {
+ inputSourceA(0),
+ inputSourceB(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The determination as to which of two AC input
+ lines is designated as the primary input source.
+ The other is designated as the secondary input
+ source. This value will always return inputSourceA(0)
+ for devices with a single input source. Setting
+ this value is supported only on selected models."
+ ::= { tlUpsInput 3 }
+
+tlUpsPhaseImbalance OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Percentage of imbalance of the 3 phases."
+ ::= { tlUpsInput 4 }
+
+tlUpsInputSourceAvailability OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(0),
+ inputSourceA(1),
+ inputSourceB(2),
+ inputSourceAB(3) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The determination as to which of two AC input lines
+ are available. The agent will return either inputSourceA(1)
+ or inputSourceB(2) if only one line is available, or
+ inputSourceAB(3) if both lines are available. The agent
+ will never return none(0) since the device will be powered
+ off if neither line is available."
+ ::= { tlUpsInput 5 }
+
+tlUpsInputSourceInUse OBJECT-TYPE
+ SYNTAX INTEGER {
+ inputSourceA(0),
+ inputSourceB(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The determination as to which one of two AC input lines is
+ in use."
+ ::= { tlUpsInput 6 }
+
+tlUpsInputSourceTransitionCount OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of times the device transitions between primary and
+ secondary sources. Most devices are limied to 65533 transitions,
+ after which the value will not increment."
+ ::= { tlUpsInput 7 }
+
+tlUpsOutput OBJECT IDENTIFIER ::= { tlUpsObjects 4 }
+
+tlUpsOutputPowerTotal OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The power capacity of the device."
+ ::= { tlUpsOutput 5 }
+
+tlUpsOutputCircuits OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of output circuits. This variable
+ indicates the number of rows in the output circuit table."
+ ::= { tlUpsOutput 6 }
+
+tlUpsOutputCircuitTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TlUpsOutputCircuitEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of output currents table entries. The number of entries
+ is given by the value of tlUpsOutputNumCircuits."
+ ::= { tlUpsOutput 7 }
+
+tlUpsOutputCircuitEntry OBJECT-TYPE
+ SYNTAX TlUpsOutputCircuitEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular output circuit."
+ INDEX { tlUpsOutputCircuitIndex }
+ ::= { tlUpsOutputCircuitTable 1 }
+
+TlUpsOutputCircuitEntry ::= SEQUENCE {
+ tlUpsOutputCircuitIndex PositiveInteger,
+ tlUpsOutputCircuitStatus INTEGER,
+ tlUpsOutputCircuitLoadCurrent NonNegativeInteger,
+ tlUpsOutputCircuitVoltage NonNegativeInteger,
+ tlUpsOutputCircuitPower NonNegativeInteger,
+ tlUpsOutputCircuitPowerFactor NonNegativeInteger
+}
+
+tlUpsOutputCircuitIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "The output circuit identifier."
+ ::= { tlUpsOutputCircuitEntry 1 }
+
+tlUpsOutputCircuitStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ open(0),
+ closed(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Whether the breaker is open or closed."
+ ::= { tlUpsOutputCircuitEntry 2 }
+
+tlUpsOutputCircuitLoadCurrent OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Amperes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present output current in
+ tenths of an amp. A value of 65534 indicates Unknown."
+ ::= { tlUpsOutputCircuitEntry 3 }
+
+tlUpsOutputCircuitVoltage OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "0.1 Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present circuit voltage in
+ tenths of an volt."
+ ::= { tlUpsOutputCircuitEntry 4 }
+
+tlUpsOutputCircuitPower OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The magnitude of the present power in watts.
+ tenths of an amp."
+ ::= { tlUpsOutputCircuitEntry 5 }
+
+tlUpsOutputCircuitPowerFactor OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ UNITS "Percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The power factor of all receptacles in a given circuit as
+ a %."
+ ::= { tlUpsOutputCircuitEntry 6 }
+
+tlUpsAggregatePowerFactor OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS "0.1 Watts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The aggregrate power factor of all phases."
+ ::= { tlUpsOutput 8 }
+
+-- tlUpsBypass [unused] OBJECT IDENTIFIER ::= { tlUpsObjects 5 }
+
+tlUpsAlarm OBJECT IDENTIFIER ::= { tlUpsObjects 6 }
+
+tlUpsAlarmsPresent OBJECT-TYPE
+ SYNTAX Gauge32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present number of active alarm conditions."
+ ::= { tlUpsAlarm 1 }
+
+tlUpsAlarmTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TlUpsAlarmEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of alarm table entries."
+ ::= { tlUpsAlarm 2 }
+
+tlUpsAlarmEntry OBJECT-TYPE
+ SYNTAX TlUpsAlarmEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a particular alarm."
+ INDEX { tlUpsAlarmId }
+ ::= { tlUpsAlarmTable 1 }
+
+TlUpsAlarmEntry ::= SEQUENCE {
+ tlUpsAlarmId PositiveInteger,
+ tlUpsAlarmDescr AutonomousType,
+ tlUpsAlarmTime TimeStamp,
+ tlUpsAlarmDetail DisplayString,
+ tlUpsAlarmDeviceId PositiveInteger,
+ tlUpsAlarmDeviceName DisplayString,
+ tlUpsAlarmLocation DisplayString,
+ tlUpsAlarmGroup INTEGER,
+ tlUpsAlarmIp IpAddress,
+ tlUpsAlarmMac DisplayString
+}
+
+tlUpsAlarmId OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique identifier for an alarm condition."
+ ::= { tlUpsAlarmEntry 1 }
+
+tlUpsAlarmDescr OBJECT-TYPE
+ SYNTAX AutonomousType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A description of the alarm condition."
+ ::= { tlUpsAlarmEntry 2 }
+
+tlUpsAlarmTime OBJECT-TYPE
+ SYNTAX TimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of sysUpTime when the alarm condition was detected."
+ ::= { tlUpsAlarmEntry 3 }
+
+tlUpsAlarmDetail OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A textual description of the alarm condition."
+ ::= { tlUpsAlarmEntry 4 }
+
+tlUpsAlarmDeviceId OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A numeric identifier for the device on which the alarm is active."
+ ::= { tlUpsAlarmEntry 5 }
+
+tlUpsAlarmDeviceName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A string identifier for the device on which the alarm is active."
+ ::= { tlUpsAlarmEntry 6 }
+
+tlUpsAlarmLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The location of the device on which the alarm is active."
+ ::= { tlUpsAlarmEntry 7 }
+
+tlUpsAlarmGroup OBJECT-TYPE
+ SYNTAX INTEGER {
+ critical(1),
+ warning(2),
+ info(3),
+ status(4),
+ offline(5),
+ custom(6) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The category/group of this alarm."
+ ::= { tlUpsAlarmEntry 8 }
+
+tlUpsAlarmIp OBJECT-TYPE
+ SYNTAX IpAddress
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The originating IP address associated with this alarm."
+ ::= { tlUpsAlarmEntry 9 }
+
+tlUpsAlarmMac OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The originating mac address associated with this alarm."
+ ::= { tlUpsAlarmEntry 10 }
+
+tlUpsWellKnownAlarms OBJECT IDENTIFIER ::= { tlUpsAlarm 3 }
+
+tlUpsAlarmPrimaryPowerOutage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The primary power source is not present."
+ ::= { tlUpsWellKnownAlarms 1 }
+
+tlUpsAlarmSecondaryPowerOutage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The secondary power source is not present."
+ ::= { tlUpsWellKnownAlarms 2 }
+
+tlUpsAlarmLoadLevelAboveThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The load level is above the designated threshold."
+ ::= { tlUpsWellKnownAlarms 3 }
+
+tlUpsAlarmOutputCurrentChanged OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output current changed from its last known value."
+ ::= { tlUpsWellKnownAlarms 4 }
+
+tlUpsAlarmBatteryAgeAboveThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more batteries have been determined to require
+ replacement."
+ ::= { tlUpsWellKnownAlarms 5 }
+
+tlUpsAlarmLoadOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The load is off."
+ ::= { tlUpsWellKnownAlarms 6 }
+
+tlUpsAlarmUserDefined OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A user-defined event is in alarm."
+ ::= { tlUpsWellKnownAlarms 7 }
+
+tlUpsAlarmBatteryBad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more batteries have been determined to require
+ replacement."
+ ::= { tlUpsWellKnownAlarms 8 }
+
+tlUpsAlarmOnBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS is drawing power from the batteries."
+ ::= { tlUpsWellKnownAlarms 9 }
+
+tlUpsAlarmLowBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The remaining battery run-time is less than or equal
+ to upsConfigLowBattTime."
+ ::= { tlUpsWellKnownAlarms 10 }
+
+tlUpsAlarmDepletedBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS will be unable to sustain the present load
+ when and if the utility power is lost."
+ ::= { tlUpsWellKnownAlarms 11 }
+
+tlUpsAlarmTempBad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A temperature is out of tolerance."
+ ::= { tlUpsWellKnownAlarms 12 }
+
+tlUpsAlarmInputBad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An input condition is out of tolerance."
+ ::= { tlUpsWellKnownAlarms 13 }
+
+tlUpsAlarmOutputBad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An output condition (other than OutputOverload) is
+ out of tolerance."
+ ::= { tlUpsWellKnownAlarms 14 }
+
+tlUpsAlarmOutputOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output load exceeds the UPS output capacity."
+ ::= { tlUpsWellKnownAlarms 15 }
+
+tlUpsAlarmOnBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Bypass is presently engaged on the UPS."
+ ::= { tlUpsWellKnownAlarms 16 }
+
+tlUpsAlarmBypassBad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Bypass is out of tolerance."
+ ::= { tlUpsWellKnownAlarms 17 }
+
+tlUpsAlarmOutputOffAsRequested OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS has shutdown as requested, i.e., the output
+ is off."
+ ::= { tlUpsWellKnownAlarms 18 }
+
+tlUpsAlarmUpsOffAsRequested OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The entire UPS has shutdown as commanded."
+ ::= { tlUpsWellKnownAlarms 19 }
+
+tlUpsAlarmChargerFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An uncorrected problem has been detected within the
+ UPS charger subsystem."
+ ::= { tlUpsWellKnownAlarms 20 }
+
+tlUpsAlarmUpsOutputOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output of the UPS is in the off state."
+ ::= { tlUpsWellKnownAlarms 21 }
+
+tlUpsAlarmUpsSystemOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS system is in the off state."
+ ::= { tlUpsWellKnownAlarms 22 }
+
+tlUpsAlarmFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The failure of one or more fans in the UPS has been
+ detected."
+ ::= { tlUpsWellKnownAlarms 23 }
+
+tlUpsAlarmFuseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The failure of one or more fuses has been detected."
+ ::= { tlUpsWellKnownAlarms 24 }
+
+tlUpsAlarmGeneralFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A general fault in the UPS has been detected."
+ ::= { tlUpsWellKnownAlarms 25 }
+
+tlUpsAlarmDiagnosticTestFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The result of the last diagnostic test indicates a
+ failure."
+ ::= { tlUpsWellKnownAlarms 26 }
+
+tlUpsAlarmCommunicationsLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A problem has been encountered in the communications
+ between the agent and the UPS."
+ ::= { tlUpsWellKnownAlarms 27 }
+
+tlUpsAlarmAwaitingPower OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS output is off and the UPS is awaiting the
+ return of input power."
+ ::= { tlUpsWellKnownAlarms 28 }
+
+tlUpsAlarmShutdownPending OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A upsShutdownAfterDelay countdown is underway."
+ ::= { tlUpsWellKnownAlarms 29 }
+
+tlUpsAlarmShutdownImminent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS will turn off power to the load in less than
+ 5 seconds; this may be either a timed shutdown or a
+ low battery shutdown."
+ ::= { tlUpsWellKnownAlarms 30 }
+
+tlUpsAlarmTestInProgress OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A test is in progress, as initiated and indicated by
+ the Test Group. Tests initiated via other
+ implementation-specific mechanisms can indicate the
+ presence of the testing in the alarm table, if
+ desired, via a OBJECT-IDENTITY macro in the MIB
+ document specific to that implementation and are
+ outside the scope of this OBJECT-IDENTITY."
+ ::= { tlUpsWellKnownAlarms 31 }
+
+tlUpsAlarmCircuitBreaker1Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Circuit breakers #1 is open."
+ ::= { tlUpsWellKnownAlarms 32 }
+
+tlUpsAlarmCircuitBreaker2Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Circuit breakers #2 is open."
+ ::= { tlUpsWellKnownAlarms 33 }
+
+tlUpsAlarmCircuitBreaker3Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Circuit breakers #3 is open."
+ ::= { tlUpsWellKnownAlarms 34 }
+
+tlUpsAlarmCircuitBreaker4Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Circuit breakers #4 is open."
+ ::= { tlUpsWellKnownAlarms 35 }
+
+tlUpsAlarmCircuitBreaker5Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Circuit breakers #5 is open."
+ ::= { tlUpsWellKnownAlarms 36 }
+
+tlUpsAlarmCircuitBreaker6Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Circuit breakers #6 is open."
+ ::= { tlUpsWellKnownAlarms 37 }
+
+tlUpsAlarmCircuitBreaker7Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Circuit breakers #7 is open."
+ ::= { tlUpsWellKnownAlarms 38 }
+
+tlUpsAlarmCircuitBreaker8Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Circuit breakers #8 is open."
+ ::= { tlUpsWellKnownAlarms 39 }
+
+tlUpsAlarmCurrent1AboveThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output current on line 1 exceeds load limits."
+ ::= { tlUpsWellKnownAlarms 40 }
+
+tlUpsAlarmCurrent2AboveThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output current on line 2 exceeds load limits."
+ ::= { tlUpsWellKnownAlarms 41 }
+
+tlUpsAlarmCurrent3AboveThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The output current on line 3 exceeds load limits."
+ ::= { tlUpsWellKnownAlarms 42 }
+
+tlUpsAlarmRuntimeBelowWarningLevel OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery seconds remaining is below warning level."
+ ::= { tlUpsWellKnownAlarms 43 }
+
+tlUpsAlarmBusStartVoltageLow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter start up bus voltage is too low."
+ ::= { tlUpsWellKnownAlarms 44 }
+
+tlUpsAlarmBusOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter bus voltage is too high."
+ ::= { tlUpsWellKnownAlarms 45 }
+
+tlUpsAlarmBusUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter bus voltage is too low."
+ ::= { tlUpsWellKnownAlarms 46 }
+
+tlUpsAlarmBusVoltageUnbalanced OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter bus voltage is not balanced."
+ ::= { tlUpsWellKnownAlarms 47 }
+
+tlUpsAlarmInverterSoftStartBad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter bus voltage cannot reach desired voltage within a
+ specified duration."
+ ::= { tlUpsWellKnownAlarms 48 }
+
+tlUpsAlarmInverterOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter voltage is too high."
+ ::= { tlUpsWellKnownAlarms 49 }
+
+tlUpsAlarmInverterUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter voltage is too low."
+ ::= { tlUpsWellKnownAlarms 50 }
+
+tlUpsAlarmInverterCircuitBad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter output is shorted."
+ ::= { tlUpsWellKnownAlarms 51 }
+
+tlUpsAlarmBatteryOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery voltage is too high."
+ ::= { tlUpsWellKnownAlarms 52 }
+
+tlUpsAlarmBatteryUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery voltage is too low."
+ ::= { tlUpsWellKnownAlarms 53 }
+
+tlUpsAlarmSiteWiringFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The utility input wiring is faulty."
+ ::= { tlUpsWellKnownAlarms 54 }
+
+tlUpsAlarmOverTemperatureProtection OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The over temperature protection is activated."
+ ::= { tlUpsWellKnownAlarms 55 }
+
+tlUpsAlarmOverCharged OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The UPS is over charged."
+ ::= { tlUpsWellKnownAlarms 56 }
+
+tlUpsAlarmEPOActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The EPO is currently activate."
+ ::= { tlUpsWellKnownAlarms 57 }
+
+tlUpsAlarmBypassFrequencyBad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The bypass frequency is out of tolerance."
+ ::= { tlUpsWellKnownAlarms 58 }
+
+tlUpsAlarmExternalSmartBatteryAgeAboveThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more external smart batteries have been determined to require
+ replacement."
+ ::= { tlUpsWellKnownAlarms 59 }
+
+tlUpsAlarmExternalNonSmartBatteryAgeAboveThreshold OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more external non-smart batteries have been determined to require
+ replacement."
+ ::= { tlUpsWellKnownAlarms 60 }
+
+tlUpsAlarmSmartBatteryCommLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Communications with the smart batteries was lost."
+ ::= { tlUpsWellKnownAlarms 61 }
+
+tlUpsAlarmSourceAOutage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Input power source A is not present."
+ ::= { tlUpsWellKnownAlarms 62 }
+
+tlUpsAlarmSourceBOutage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Input power source B is not present."
+ ::= { tlUpsWellKnownAlarms 63 }
+
+tlUpsAlarmWatchdogReset OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The internal watchdog triggered a reset of the device."
+ ::= { tlUpsWellKnownAlarms 64 }
+
+tlUpsAlarmDevName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "The name of the device, tlDevName, corresponding to the device that is
+ associated with this alarm."
+ ::= { tlUpsAlarm 7 }
+
+tlUpsAlarmDevLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "The location of the device, tlDevLocation, corresponding to the device
+ that is associated with this alarm."
+ ::= { tlUpsAlarm 8 }
+
+tlUpsAlarmCategory OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "The category, tlDevEvtCategory, of this alarm."
+ ::= { tlUpsAlarm 9 }
+
+tlUpsTest OBJECT IDENTIFIER ::= { tlUpsObjects 7 }
+
+tlUpsTestDate OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The date of the last self-test run on the ups, in the
+ format YYYYMMDD."
+ ::= { tlUpsTest 1 }
+
+tlUpsTestResultsDetail OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Result of the last self-test run on the ups."
+ ::= { tlUpsTest 2 }
+
+tlUpsControl OBJECT IDENTIFIER ::= { tlUpsObjects 8 }
+
+tlUpsWatchdogSupported OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates whether or not this UPS supports a watchdog reboot."
+ ::= { tlUpsControl 1 }
+
+
+tlUpsWatchdogSecsBeforeReboot OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The maximum number of seconds that can expire between polls that
+ the engine makes to the UPS for data. If this time runs out, then
+ the UPS will cycle its outputs. Set this to zero to turns disable
+ this feature."
+ ::= { tlUpsControl 2 }
+
+tlUpsWellKnownControls OBJECT IDENTIFIER ::= { tlUpsControl 3 }
+
+tlUpsControlSelfTest OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Set to TRUE to initiate Self Test"
+ ::= { tlUpsWellKnownControls 1 }
+
+tlUpsControlRamp OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Set to TRUE to initiate Ramp"
+ ::= { tlUpsWellKnownControls 2 }
+
+tlUpsControlShed OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Set to TRUE to initiate Shed"
+ ::= { tlUpsWellKnownControls 3 }
+
+tlUpsControlUpsOn OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Set to TRUE to turn UPS on"
+ ::= { tlUpsWellKnownControls 4 }
+
+tlUpsControlUpsOff OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Set to TRUE to turn UPS off"
+ ::= { tlUpsWellKnownControls 5 }
+
+tlUpsConfig OBJECT IDENTIFIER ::= { tlUpsObjects 9 }
+
+tlUpsConfigBattReplDate OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The date on which the battery was last replaced, in the format
+ YYYYMMDD."
+ ::= { tlUpsConfig 1 }
+
+-- Deprecated, interface no longer supported.
+--
+-- tlUpsConfigTftpGetAddr OBJECT-TYPE
+-- SYNTAX IpAddress
+-- MAX-ACCESS read-write
+-- STATUS current
+-- DESCRIPTION
+-- "The IP address of the TFTP server you wish to acquire a config ini file from, non persistent, 0.0.0.0 when empty"
+-- ::= { tlUpsConfig 2 }
+--
+-- tlUpsConfigTftpGetAcction OBJECT-TYPE
+-- SYNTAX INTEGER {
+-- get(1),
+-- getting(2),
+-- idle(3) }
+-- MAX-ACCESS read-write
+-- STATUS current
+-- DESCRIPTION
+-- "setting this entry to get(1) will start a down load from the specified address, during the download this entry
+-- will read getting(2), when finished, the card will reboot to the new ini supplied parms. At all other times this
+-- entry will read idle(3)"
+-- ::= { tlUpsConfig 3 }
+
+tlUpsConfigDisplayUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ english(0),
+ metric(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Selects English or Metric display for all readings. This selection may not
+ be available on all devices. Further, some devices may support this selection,
+ but not via a software selector. In this latter case, selections must be
+ performed on the device itself."
+ ::= { tlUpsConfig 4 }
+
+tlUpsConfigExternalBattReplDate OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The date on which the external battery was last replaced, in the format
+ YYYYMMDD."
+ ::= { tlUpsConfig 5 }
+
+tlUpsOutlet OBJECT IDENTIFIER ::= { tlUpsObjects 10 }
+
+tlUpsOutletNumOutlets OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of available Outlets in this device."
+ ::= { tlUpsOutlet 1 }
+
+tlUpsOutletTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TlUpsOutletEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of all device Outlets for all devices."
+ ::= { tlUpsOutlet 2 }
+
+tlUpsOutletEntry OBJECT-TYPE
+ SYNTAX TlUpsOutletEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing Outlet information applicable to a particular
+ device managed by this agent."
+ INDEX {
+ tlUpsOutletIndex }
+ ::= { tlUpsOutletTable 1 }
+
+TlUpsOutletEntry ::= SEQUENCE {
+ tlUpsOutletIndex PositiveInteger,
+ tlUpsOutletState INTEGER,
+ tlUpsOutletType Integer32,
+ tlUpsOutletControl INTEGER,
+ tlUpsOutletName DisplayString,
+ tlUpsOutletRampAction INTEGER,
+ tlUpsOutletRampDataType INTEGER,
+ tlUpsOutletRampData Integer32,
+ tlUpsOutletShedAction INTEGER,
+ tlUpsOutletShedDataType INTEGER,
+ tlUpsOutletShedData Integer32,
+ tlUpsOutletGroupNdx Integer32,
+ tlUpsOutletCurrent PositiveInteger,
+ tlUpsOutletPower PositiveInteger }
+
+tlUpsOutletIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This is the index number of this Outlet for the device
+ indicated by tlDeviceIndex."
+ ::= { tlUpsOutletEntry 1 }
+
+tlUpsOutletState OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(0),
+ off(1),
+ on(2) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current state of the Outlet."
+ ::= { tlUpsOutletEntry 2 }
+
+tlUpsOutletType OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This is a bit field that indicates the type of this Outlet.
+ When 0, the outlet is not controllable and has none of the
+ other features indicated in the bit map. When non-zero,
+ the features present for this outlet can be interpreted with the
+ definition.
+
+ Bit Display
+ 0 Reserved, may be 1 or 0
+ 1 Controllable
+ 2
+ 3
+ 4
+ 5
+ 6
+ 7
+ 8
+ 9
+ 10
+ 11
+ 12
+ 13
+ 14
+ 15
+ "
+ ::= { tlUpsOutletEntry 3 }
+
+tlUpsOutletControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOff(1),
+ turnOn(2),
+ cycle(3) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Controls the state of the Outlet."
+ ::= { tlUpsOutletEntry 4 }
+
+tlUpsOutletName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A string identifying the devices attached to the
+ output(s) of the device."
+ ::= { tlUpsOutletEntry 5 }
+
+
+tlUpsOutletRampAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ remainOff(0),
+ turnOnAfterDelay(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The ramp action to take on the Outlet."
+ ::= { tlUpsOutletEntry 6 }
+
+tlUpsOutletRampDataType OBJECT-TYPE
+ SYNTAX INTEGER {
+ delayInSeconds(0)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The type of data associated with ramp action."
+ ::= { tlUpsOutletEntry 7 }
+
+tlUpsOutletRampData OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The data value associated with type of ramp data."
+ ::= { tlUpsOutletEntry 8 }
+
+tlUpsOutletShedAction OBJECT-TYPE
+ SYNTAX INTEGER {
+ remainOn(0),
+ turnOffAfterDelay(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The shed action to take on the Outlet."
+ ::= { tlUpsOutletEntry 9 }
+
+tlUpsOutletShedDataType OBJECT-TYPE
+ SYNTAX INTEGER {
+ delayInSeconds(0)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The type of data associated with shed action."
+ ::= { tlUpsOutletEntry 10 }
+
+tlUpsOutletShedData OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The data value associated with type of shed data."
+ ::= { tlUpsOutletEntry 11 }
+
+tlUpsOutletGroupNdx OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "tlUpsOutletGroupIndex of corresponding outlet group, or 0 if ungrouped."
+ ::= { tlUpsOutletEntry 12 }
+
+tlUpsOutletCurrent OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS "0.1 RMS Amp"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of this outlet's current, represented as 0.1A."
+ ::= { tlUpsOutletEntry 13 }
+
+tlUpsOutletPower OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of this outlet's power in watts."
+ ::= { tlUpsOutletEntry 14 }
+
+
+tlUpsOutletGroup OBJECT IDENTIFIER ::= { tlUpsObjects 11 }
+
+tlUpsOutletNumOutletGroups OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The number of available Outlet Groups in this device."
+ ::= { tlUpsOutletGroup 1 }
+
+tlUpsOutletGroupTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TlUpsOutletGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of device outlet group entries. The number of entries is
+ given by the value of tlUpsOutletNumOutletGroups."
+ ::= { tlUpsOutletGroup 2 }
+
+tlUpsOutletGroupEntry OBJECT-TYPE
+ SYNTAX TlUpsOutletGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing outlet group information applicable
+ to a particular device managed by this agent"
+ INDEX { tlUpsOutletGroupIndex }
+ ::= { tlUpsOutletGroupTable 1 }
+
+TlUpsOutletGroupEntry ::= SEQUENCE {
+ tlUpsOutletGroupIndex PositiveInteger,
+ tlUpsOutletGroupRowStatus RowStatus,
+ tlUpsOutletGroupName DisplayString,
+ tlUpsOutletGroupDesc DisplayString,
+ tlUpsOutletGroupState INTEGER,
+ tlUpsOutletGroupControl INTEGER }
+
+tlUpsOutletGroupIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This is the index number of this load group for the device."
+ ::= { tlUpsOutletGroupEntry 1 }
+
+tlUpsOutletGroupRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Row status for the tlUpsOutletGroupTable"
+ ::= { tlUpsOutletGroupEntry 2 }
+
+tlUpsOutletGroupName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The name of this outlet group."
+ ::= { tlUpsOutletGroupEntry 3 }
+
+tlUpsOutletGroupDesc OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A description for this outlet group."
+ ::= { tlUpsOutletGroupEntry 4 }
+
+tlUpsOutletGroupState OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(0),
+ off(1),
+ on(2),
+ mixed(3) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current state of the outlet group."
+ ::= { tlUpsOutletGroupEntry 5 }
+
+tlUpsOutletGroupControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOff(1),
+ turnOn(2),
+ cycle(3) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Controls the state of every outlet associated with the group."
+ ::= { tlUpsOutletGroupEntry 6 }
+
+tlUpsMainOutlet OBJECT IDENTIFIER ::= { tlUpsObjects 12 }
+
+tlUpsMainOutletState OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(0),
+ off(1),
+ on(2),
+ mixed(3) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current state of the main output of the device."
+ ::= { tlUpsMainOutlet 1 }
+
+
+tlUpsMainOutletControllable OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates if this device has controllable outlets"
+ ::= { tlUpsMainOutlet 2 }
+
+tlUpsMainOutletControl OBJECT-TYPE
+ SYNTAX INTEGER {
+ idle(0),
+ turnOff(1),
+ turnOn(2),
+ cycle(3) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Controls the state of the main outlet of the device."
+ ::= { tlUpsMainOutlet 3 }
+
+tlUpsEnvironment OBJECT IDENTIFIER ::= { tlUpsObjects 13 }
+
+tlUpsTemperature OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ambient temperature. The measurement returned will either be in
+ units of Celsius (C) or Fahrenheit (F) depending upon whether Metric
+ or English was selected for the reading by tlUpsConfigDisplayUnits."
+ ::= { tlUpsEnvironment 1 }
+
+
+---------------------------------------------------------------
+-- UPS traps
+---------------------------------------------------------------
+
+tlUpsTraps OBJECT IDENTIFIER ::= { tlUPS 2 }
+
+tlUpsTrapAlarmEntryAddedV1 TRAP-TYPE
+ ENTERPRISE tlUpsTraps
+ VARIABLES { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
+ tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
+ DESCRIPTION
+ "This trap is sent each time an alarm is inserted into
+ to the alarm table."
+ --#SUMMARY "UPS Alarm: %s - %s."
+ --#ARGUMENTS {6, 2}
+ --#SEVERITY WARNING
+ ::= 3
+
+tlUpsTrapAlarmEntryAdded NOTIFICATION-TYPE
+ OBJECTS { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
+ tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
+ STATUS current
+ DESCRIPTION
+ "This trap is sent each time an alarm is inserted into
+ to the alarm table."
+ --#SUMMARY "UPS Alarm: %s - %s."
+ --#ARGUMENTS {6, 2}
+ --#SEVERITY WARNING
+ ::= { tlUpsTraps 3 }
+
+tlUpsTrapAlarmEntryRemovedV1 TRAP-TYPE
+ ENTERPRISE tlUpsTraps
+ VARIABLES { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
+ tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
+ DESCRIPTION
+ "This trap is sent each time an alarm is removed from
+ the alarm table."
+ --#SUMMARY "UPS Alarm: %s - %s."
+ --#ARGUMENTS {6, 2}
+ --#SEVERITY WARNING
+ ::= 4
+
+tlUpsTrapAlarmEntryRemoved NOTIFICATION-TYPE
+ OBJECTS { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
+ tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
+ STATUS current
+ DESCRIPTION
+ "This trap is sent each time an alarm is removed from
+ the alarm table."
+ --#SUMMARY "UPS Alarm: %s - %s."
+ --#ARGUMENTS {6, 2}
+ --#SEVERITY WARNING
+ ::= { tlUpsTraps 4 }
+
+--------------------------------------------------------------------------
+--------------------------------------------------------------------------
+-- begin new traps
+--------------------------------------------------------------------------
+--------------------------------------------------------------------------
+
+tlUpsTrapSystemStartup NOTIFICATION-TYPE
+ STATUS current
+ DESCRIPTION
+ "Used to inform another entity of an engine's startup. The varbinds that follow are:
+
+ OBJ1 = tlEngineType
+ Obj1Value = The type of engine providing this data
+ OBJ2 = tlEngineSoftwareVersion
+ Obj2Value = The current version of the engine
+ OBJ3 = tlEngineMACAddr
+ Obj3Value = The MAC address of the engine
+ OBJ4 = tlUpsSnmpCardSerialNum
+ Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC]
+
+ --- if this trap is extended, place all static OIDs above this mark. all objects below
+ --- the number of devices (tlNumDevices) is explicit as per device for enumeration by
+ --- the target receiver
+
+ OBJ5 = tlNumDevices
+ Obj5Value = The number of devices attached
+
+ --- The following objects will be replicated per each device:
+
+ OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device
+ Obj6Value = The device's manufacturer
+ OBJ7 = The OID for an entry of tlDevModel, indexed by device
+ Obj7Value = The device's model name
+ OBJ8 = The OID for an entry of tlDevName, indexed by device
+ Obj8Value = The device's display name
+ OBJ9 = The OID for an entry of tlDevLocation, indexed by device
+ Obj9Value = The device's location
+ OBJ10 = The OID for an entry of tlDevRegion, indexed by device
+ Obj10Value= The device's region
+ OBJ11 = The OID for an entry of tlDevProtocol, indexed by device
+ Obj11Value= The device's protocol (display string format)
+ "
+ ::= { tlUpsTraps 5 }
+
+tlUpsTrapSystemShutdown NOTIFICATION-TYPE
+ STATUS current
+ DESCRIPTION
+ "Used to inform another entity of an engine's startup. The varbinds that follow are:
+
+ OBJ1 = tlEngineType
+ Obj1Value = The type of engine providing this data
+ OBJ2 = tlEngineSoftwareVersion
+ Obj2Value = The current version of the engine
+ OBJ3 = tlEngineMACAddr
+ Obj3Value = The MAC address of the engine
+ OBJ4 = tlUpsSnmpCardSerialNum
+ Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC]
+
+ --- if this trap is extended, place all static OIDs above this mark. all objects below
+ --- the number of devices (tlNumDevices) is explicit as per device for enumeration by
+ --- the target receiver
+
+ OBJ5 = tlNumDevices
+ Obj5Value = The number of devices attached
+
+ --- The following objects will be replicated per each device:
+
+ OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device
+ Obj6Value = The device's manufacturer
+ OBJ7 = The OID for an entry of tlDevModel, indexed by device
+ Obj7Value = The device's model name
+ OBJ8 = The OID for an entry of tlDevName, indexed by device
+ Obj8Value = The device's display name
+ OBJ9 = The OID for an entry of tlDevLocation, indexed by device
+ Obj9Value = The device's location
+ OBJ10 = The OID for an entry of tlDevRegion, indexed by device
+ Obj10Value= The device's region
+ OBJ11 = The OID for an entry of tlDevProtocol, indexed by device
+ Obj11Value= The device's protocol (display string format)
+ "
+ ::= { tlUpsTraps 6 }
+
+--------------------------------------------------------------------------
+--------------------------------------------------------------------------
+--- end new traps
+--------------------------------------------------------------------------
+--------------------------------------------------------------------------
+--------------------------------------------------------------------------
+-- EnviroSense Device
+--------------------------------------------------------------------------
+
+tlEnviroSense OBJECT IDENTIFIER ::= { tripplite 101 }
+
+tlEnvEnvironment OBJECT IDENTIFIER ::= { tlEnviroSense 1 }
+
+tlEnvTemperatureData OBJECT IDENTIFIER ::= { tlEnvEnvironment 1 }
+
+tlEnvTemperatureC OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ambient temperature (C)."
+ ::= { tlEnvTemperatureData 1 }
+
+tlEnvTemperatureF OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ambient temperature (F)."
+ ::= { tlEnvTemperatureData 2 }
+
+tlEnvTemperatureLowLimit OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The lower alarm limit for ambient temperature (F)."
+ ::= { tlEnvTemperatureData 3 }
+
+tlEnvTemperatureHighLimit OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The upper alarm limit for ambient temperature (F)."
+ ::= { tlEnvTemperatureData 4 }
+
+tlEnvTemperatureInAlarm OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates whether or not temperature is in alarm."
+ ::= { tlEnvTemperatureData 5 }
+
+tlEnvHumidityData OBJECT IDENTIFIER ::= { tlEnvEnvironment 2 }
+
+tlEnvHumidity OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ambient humidity (%)."
+ ::= { tlEnvHumidityData 1 }
+
+tlEnvHumidityLowLimit OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The lower alarm limit for ambient humidity (%)."
+ ::= { tlEnvHumidityData 2 }
+
+tlEnvHumidityHighLimit OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The upper alarm limit for ambient humidity (%)."
+ ::= { tlEnvHumidityData 3 }
+
+tlEnvHumidityInAlarm OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates whether or not humidity is in alarm."
+ ::= { tlEnvHumidityData 4 }
+
+tlEnvContacts OBJECT IDENTIFIER ::= { tlEnviroSense 2 }
+
+tlEnvContactTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TlEnvContactEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A table of contacts."
+ ::= { tlEnvContacts 1 }
+
+tlEnvContactEntry OBJECT-TYPE
+ SYNTAX TlEnvContactEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a particular contact."
+ INDEX {
+ tlEnvContactIndex }
+ ::= { tlEnvContactTable 1 }
+
+TlEnvContactEntry ::= SEQUENCE {
+ tlEnvContactIndex PositiveInteger,
+ tlEnvContactName DisplayString,
+ tlEnvContactStatus INTEGER,
+ tlEnvContactConfig INTEGER }
+
+tlEnvContactIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The table row index for the contact."
+ ::= { tlEnvContactEntry 1 }
+
+tlEnvContactName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The name or description of the contact."
+ ::= { tlEnvContactEntry 2 }
+
+tlEnvContactStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ normal(0),
+ alarm(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current status of the contact."
+ ::= { tlEnvContactEntry 3 }
+
+tlEnvContactConfig OBJECT-TYPE
+ SYNTAX INTEGER {
+ normallyOpen(0),
+ normallyClosed(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The configuration of the contact."
+ ::= { tlEnvContactEntry 4 }
+
+
+--------------------------------------------------------------------------
+-- KVM over IP Device
+--------------------------------------------------------------------------
+
+-- this is a 3rd party MIB structure located at { tripplite 102 }
+
+--------------------------------------------------------------------------
+-- SR Cooling Device
+--------------------------------------------------------------------------
+
+tlCooling OBJECT IDENTIFIER ::= { tripplite 103 }
+
+tlCoolingEnvironment OBJECT IDENTIFIER ::= { tlCooling 1 }
+
+tlCoolingIdent OBJECT IDENTIFIER ::= { tlCoolingEnvironment 1 }
+
+tlCoolingModel OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The model name for the AC Unit."
+ ::= { tlCoolingIdent 1}
+
+tlCoolingManufacturer OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The manufacturer of the AC Unit."
+ ::= { tlCoolingIdent 2 }
+
+tlCoolingSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The serial number of the AC unit."
+ ::= { tlCoolingIdent 3 }
+
+tlCoolingFirmwareVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The firmware version of the AC Unit."
+ ::= { tlCoolingIdent 4 }
+
+tlCoolingHostSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The hardware version of the AC unit."
+ ::= { tlCoolingIdent 5 }
+
+tlCoolingName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The user defined name for the AC Unit."
+ ::= { tlCoolingIdent 6 }
+
+tlCoolingLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The user defined location of the AC Unit."
+ ::= { tlCoolingIdent 7 }
+
+tlCoolingStatus OBJECT IDENTIFIER ::= { tlCoolingEnvironment 2 }
+
+tlCoolingCondOutletTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The condenser outlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 1 }
+
+tlCoolingCondInletTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The condenser inlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 2 }
+
+tlCoolingRefrigerantTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The temperature of the refrigerant in the suction line. This is displayed in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 3 }
+
+tlCoolingEvapSurfaceTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The surface temperature of the evaporator in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 4}
+
+tlCoolingSuctionPressure OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The pressure of the compressor suction line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 5}
+
+tlCoolingDischargePressure OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The pressure of the compressor discharge line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 6}
+
+tlCoolingEvapFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(0),
+ low(1),
+ medLow(2),
+ med (3),
+ medHi (4),
+ hi (5) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current speed of the evaporator fan."
+ ::= { tlCoolingStatus 7}
+
+tlCoolingCondFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER {
+ off(0),
+ low(1),
+ hi (2) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current speed of the condenser fan."
+ ::= { tlCoolingStatus 8}
+
+tlCoolingCompFrequency OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The operating frequency of the compressor in tenths of Arms."
+ ::= { tlCoolingStatus 9}
+
+tlCoolingEEVPercentage OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The opening percentage of the EEV."
+ ::= { tlCoolingStatus 10}
+
+tlCoolingUnitCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The the total current draw of the unit in tenths of Arms."
+ ::= { tlCoolingStatus 11}
+
+tlCoolingFanCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Thethe current draw of the Evaporator and Condenser fans in tents of Arms."
+ ::= { tlCoolingStatus 12 }
+
+tlCoolingCompCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The operating current of the compressor in Arms."
+ ::= { tlCoolingStatus 13}
+
+tlCoolingReturnAirTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The return air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 14 }
+
+tlCoolingSuctionTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The temperature of the compressor suction line in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 15 }
+
+tlCoolingSupplyAirTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The supply air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
+ ::= { tlCoolingStatus 16 }
+
+tlCoolingRunTimes OBJECT IDENTIFIER ::= { tlCoolingEnvironment 3 }
+
+tlCoolingAirFilterRunHours OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total hours the air filter has been under operation."
+ ::= { tlCoolingRunTimes 1 }
+
+tlCoolingEvapFanRunDays OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total days the evaporator fan has been under operation."
+ ::= { tlCoolingRunTimes 2 }
+
+tlCoolingCondFanRunDays OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total days the condenser fan has been under operation."
+ ::= { tlCoolingRunTimes 3 }
+
+tlCoolingCompressorRunDays OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total days the compressor has been under operation."
+ ::= { tlCoolingRunTimes 4 }
+
+tlCoolingCondPumpRunDays OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total days the condensate pump has been under operation."
+ ::= { tlCoolingRunTimes 5 }
+
+tlCoolingAtomizerRunDays OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total days the atomizer has been under operation."
+ ::= { tlCoolingRunTimes 6 }
+
+tlCoolingConfig OBJECT IDENTIFIER ::= { tlCoolingEnvironment 4 }
+
+tlCoolingOnOff OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOffUnit(0),
+ turnOnUnit(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Turn the unit off or on."
+ ::= { tlCoolingConfig 1 }
+
+tlCoolingSetPointTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The set point temperature the unit will control the temperature to in tenths of degrees in Celsius or Fahrenheit based upon tleCoolDisplayUnits."
+ ::= { tlCoolingConfig 2 }
+
+tlCoolingAutoStart OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(0),
+ enabled(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Specified if the unit should start automatically on power up."
+ ::= { tlCoolingConfig 3 }
+
+tlCoolingFanSpeedOverride OBJECT-TYPE
+ SYNTAX INTEGER {
+ autoFanSpeed(0),
+ low(1),
+ medLow(2),
+ med(3),
+ medHi(4),
+ hi(5) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Speed of evaporator fan set by the user."
+ ::= { tlCoolingConfig 4 }
+
+tlCoolingControlType OBJECT-TYPE
+ SYNTAX INTEGER {
+ returnAirTemp(0),
+ remoteTemperature(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Which temperature to be used as a control point."
+ ::= { tlCoolingConfig 5 }
+
+tlCoolingCurrentRemoteTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The external remote temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlCoolingDisplayUnits"
+ ::= { tlCoolingConfig 6 }
+
+tlCoolingDisplayUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ metric(0),
+ english(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Selects English or Metric display for all readings."
+ ::= { tlCoolingConfig 7 }
+
+tlCoolingBeepOnKey OBJECT-TYPE
+ SYNTAX INTEGER {
+ noBeep(0),
+ beepOn(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Indicates if the display sounds a beep when a key is pressed."
+ ::= { tlCoolingConfig 8 }
+
+tlCoolingOutputRelaySource OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(0),
+ allAlarmsAndWarnings(1),
+ criticalAlarmsOnly(2) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The alarm level that causes the ouput relay to activate."
+ ::= { tlCoolingConfig 9 }
+
+tlCoolingOffOnLeak OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOff(0),
+ alarmOnly(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Indicates if the unit should stop cooling when leak input is activated."
+ ::= { tlCoolingConfig 10 }
+
+tlCoolingOffOnInputContact OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOff(0),
+ alarmOnly(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Indicates if the unit should stop cooling when input contact is activated."
+ ::= { tlCoolingConfig 11 }
+
+tlCoolingInputContactType OBJECT-TYPE
+ SYNTAX INTEGER {
+ ncRelay(0),
+ noRelay(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The input contact type."
+ ::= { tlCoolingConfig 12 }
+
+tlCoolingOutputRelayDefault OBJECT-TYPE
+ SYNTAX INTEGER {
+ nc(0),
+ no(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Type of contact to make when output relay is activated."
+ ::= { tlCoolingConfig 13 }
+
+tlCoolingAirFilterInterval OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The number of weeks before the air filter needs to be changed."
+ ::= { tlCoolingConfig 14 }
+
+tlCoolingWaterLeakContactType OBJECT-TYPE
+ SYNTAX INTEGER {
+ noRelay(0),
+ ncRelay(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The input contact type."
+ ::= { tlCoolingConfig 15 }
+
+tlCoolingThresholds OBJECT IDENTIFIER ::= { tlCoolingEnvironment 5 }
+
+tlCoolingMaxAirFilterRunHours OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The maximum interval for air filter run hours before warning is annunciated."
+ ::= { tlCoolingThresholds 1 }
+
+tlCoolingEnableAirFilterAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(0),
+ enabled(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "When enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded."
+ ::= { tlCoolingThresholds 2 }
+
+tlCoolingMaxSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Maximum allowed supply air temperature before firing an alarm."
+ ::= { tlCoolingThresholds 3 }
+
+tlCoolingMinSupplyTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Minimum allowed supply air temperature allowed before firing an alarm."
+ ::= { tlCoolingThresholds 4 }
+
+tlCoolingTempDiffAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Maximum allowed air temperature deviation from set allowed before firing an alarm."
+ ::= { tlCoolingThresholds 5 }
+
+tlCoolingMaxReturnAirTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "When enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded."
+ ::= { tlCoolingThresholds 6 }
+
+tlCoolingAlarm OBJECT IDENTIFIER ::= { tlCooling 6 }
+
+tlCoolingWellKnownAlarms OBJECT IDENTIFIER ::= { tlCoolingAlarm 3 }
+
+tlCoolingSupplyAirSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The supply air sensor is in fault."
+ ::= { tlCoolingWellKnownAlarms 1 }
+
+tlCoolingReturnAirSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The return air sensor is in fault."
+ ::= { tlCoolingWellKnownAlarms 2 }
+
+tlCoolingCondenserInletAirSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser inlet air sensor is in fault."
+ ::= { tlCoolingWellKnownAlarms 3 }
+
+tlCoolingCondenserOutletAirSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser outlet air sensor is in fault."
+ ::= { tlCoolingWellKnownAlarms 4 }
+
+tlCoolingSuctionTemperatureSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The suction temperature sensor is in fault."
+ ::= { tlCoolingWellKnownAlarms 5 }
+
+tlCoolingEvaporatorTemperatureSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The evaporator temperature sensor is in fault."
+ ::= { tlCoolingWellKnownAlarms 6 }
+
+tlCoolingAirFilterClogged OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The air filter is clogged."
+ ::= { tlCoolingWellKnownAlarms 7 }
+
+tlCoolingAirFilterRunHoursViolation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The air filter run hours was violated."
+ ::= { tlCoolingWellKnownAlarms 8 }
+
+tlCoolingSuctionPressureSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The suction pressure sensor is in fault."
+ ::= { tlCoolingWellKnownAlarms 9 }
+
+tlCoolingInverterCommunicationsFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter communications is in fault."
+ ::= { tlCoolingWellKnownAlarms 10 }
+
+tlCoolingRemoteShutdownViaInputContact OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A remote shutdown was triggerd by an input contact."
+ ::= { tlCoolingWellKnownAlarms 11 }
+
+tlCoolingCondensatePumpFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condensate pump is in fault."
+ ::= { tlCoolingWellKnownAlarms 12 }
+
+tlCoolingLowRefrigerantStartupFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The low refrigerant startup is in fault."
+ ::= { tlCoolingWellKnownAlarms 13 }
+
+tlCoolingCondenserFanFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser fan is in fault."
+ ::= { tlCoolingWellKnownAlarms 14 }
+
+tlCoolingCondenserFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser has failed."
+ ::= { tlCoolingWellKnownAlarms 15 }
+
+tlCoolingEvaporatorCoolingFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The evaporator cooling is in fault."
+ ::= { tlCoolingWellKnownAlarms 16 }
+
+tlCoolingReturnAirTempHigh OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The return air temperature is high."
+ ::= { tlCoolingWellKnownAlarms 17 }
+
+tlCoolingSupplyAirTempHigh OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The supply air temperature is high."
+ ::= { tlCoolingWellKnownAlarms 18 }
+
+tlCoolingEvaporatorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The evaporator has failed."
+ ::= { tlCoolingWellKnownAlarms 19 }
+
+tlCoolingEvaporatorFreezeUp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The evaporator is frozen."
+ ::= { tlCoolingWellKnownAlarms 20 }
+
+tlCoolingDischargePressureHigh OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The discharge pressure is high."
+ ::= { tlCoolingWellKnownAlarms 21 }
+
+tlCoolingPressureGaugeFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The pressure gauge has failed."
+ ::= { tlCoolingWellKnownAlarms 22 }
+
+tlCoolingDischargePressurePersistentHigh OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The discharge pressure is persistently high."
+ ::= { tlCoolingWellKnownAlarms 23 }
+
+tlCoolingSuctionPressureLowStartFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Cannot start due to low suction pressure."
+ ::= { tlCoolingWellKnownAlarms 24 }
+
+tlCoolingSuctionPressureLow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The suction pressure is low."
+ ::= { tlCoolingWellKnownAlarms 25 }
+
+tlCoolingSuctionPressurePersistentLow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The suction pressure is persistently low."
+ ::= { tlCoolingWellKnownAlarms 26 }
+
+tlCoolingStartupLinePressureImbalance OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The startup line pressure is in imbalance."
+ ::= { tlCoolingWellKnownAlarms 27 }
+
+tlCoolingCompressorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The compressor has failed."
+ ::= { tlCoolingWellKnownAlarms 28 }
+
+tlCoolingCurrentLimit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The current is out of range."
+ ::= { tlCoolingWellKnownAlarms 29 }
+
+tlCoolingWaterLeak OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Water is leaking."
+ ::= { tlCoolingWellKnownAlarms 30 }
+
+tlCoolingFanUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The fan is under current."
+ ::= { tlCoolingWellKnownAlarms 31 }
+
+tlCoolingFanOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The fan is over current."
+ ::= { tlCoolingWellKnownAlarms 32 }
+
+tlCoolingDischargePressureSensorFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The discharge pressure sensor is in fault."
+ ::= { tlCoolingWellKnownAlarms 33 }
+
+tlCoolingWaterFull OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Water is Full."
+ ::= { tlCoolingWellKnownAlarms 34 }
+
+tlCoolingAutoCoolingOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Automatic cooling was activated to lower the temperature below the
+ remote set point."
+ ::= { tlCoolingWellKnownAlarms 35 }
+
+tlCoolingPowerButtonPressed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Power button was pressed on the front panel."
+ ::= { tlCoolingWellKnownAlarms 36 }
+
+tlCoolingDisconnectedFromDevice OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The device communications is disconnected."
+ ::= { tlCoolingWellKnownAlarms 37 }
+
+
+--------------------------------------------------------------------------
+-- SRCOOLNET Device
+--------------------------------------------------------------------------
+
+tlSrCoolNet OBJECT IDENTIFIER ::= { tripplite 104}
+
+tlSrCoolNetData OBJECT IDENTIFIER ::= { tlSrCoolNet 1 }
+
+tlSrCoolNetIdent OBJECT IDENTIFIER ::= { tlSrCoolNetData 1 }
+
+tlSrCoolNetModel OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The model name for the device attached to the SRCOOLNET."
+ ::= { tlSrCoolNetIdent 1}
+
+tlSrCoolNetManufacturer OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The manufacturer of the AC Unit."
+ ::= { tlSrCoolNetIdent 2 }
+
+tlSrCoolNetSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The serial number of the SRCOOLNET device."
+ ::= { tlSrCoolNetIdent 3 }
+
+tlSrCoolNetHostSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The software version of the SRCOOLNET device."
+ ::= { tlSrCoolNetIdent 4 }
+
+tlSrCoolNetName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The user defined name for the AC Unit."
+ ::= { tlSrCoolNetIdent 5 }
+
+tlSrCoolNetLocation OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The user defined location of the AC Unit."
+ ::= { tlSrCoolNetIdent 6 }
+
+tlSrCoolNetStatus OBJECT IDENTIFIER ::= { tlSrCoolNetData 2 }
+
+tlSrCoolNetMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (0),
+ idle (1),
+ cooling (2),
+ unknown (3),
+ dehumidifying (4),
+ defrost (5),
+ notconnected(6) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current mode of SRCOOLNET."
+ ::= { tlSrCoolNetStatus 1}
+
+tlSrCoolNetFanSpeed OBJECT-TYPE
+ SYNTAX INTEGER {
+ off (0),
+ low (1),
+ med (2),
+ hi (3) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current speed of the fan."
+ ::= { tlSrCoolNetStatus 2}
+
+tlSrCoolNetReturnAirTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The return air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlSrCoolNetDisplayUnits."
+ ::= { tlSrCoolNetStatus 3 }
+
+tlSrCoolNetWaterFull OBJECT-TYPE
+ SYNTAX INTEGER {
+ waterNotFull(0),
+ waterFull(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates the water reservoir is full or not full."
+ ::= { tlSrCoolNetStatus 4 }
+
+tlSrCoolNetCurrentRemoteTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The EnviroSense temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlSrCoolNetDisplayUnits.
+ Only available if EnviroSense is connected to SRCOOLNET."
+ ::= { tlSrCoolNetStatus 5 }
+
+ tlSrCoolNetDisplayUnits OBJECT-TYPE
+ SYNTAX INTEGER {
+ metric(0),
+ english(1) }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Selects English or Metric display for all readings. AC unit must be manually configured to match this setting."
+ ::= { tlSrCoolNetStatus 6 }
+
+
+tlSrCoolNetConfig OBJECT IDENTIFIER ::= { tlSrCoolNetData 3 }
+
+tlSrCoolNetOnOff OBJECT-TYPE
+ SYNTAX INTEGER {
+ turnOffUnit(0),
+ turnOnUnit (1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Turn the unit off or on."
+ ::= { tlSrCoolNetConfig 1 }
+
+tlSrCoolSetMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ cooling(0),
+ dehumidifying (1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Set the operating mode of cooling unit. Unit must be ON to set mode."
+ ::= { tlSrCoolNetConfig 2 }
+
+tlSrCoolNetSetPointTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The local set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits."
+ ::= { tlSrCoolNetConfig 3 }
+
+tlSrCoolNetRemoteSetPointTemp OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The remote set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits.
+ Only available when EnviroSense is connected to SRCOOLNET."
+ ::= { tlSrCoolNetConfig 4 }
+
+tlSrCoolNetFanSpeedSetting OBJECT-TYPE
+ SYNTAX INTEGER {
+ auto(0),
+ low(1),
+ med(2),
+ high(3) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Set the fan speed of the AC unit."
+ ::= { tlSrCoolNetConfig 5 }
+
+tlSrCoolNetRemoteSetpointEnable OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Use remote temperature setpoint for control point versus return air temp. Only available when EnviroSense is connected
+ to SRCOOLNET."
+ ::= { tlSrCoolNetConfig 6 }
+
+tlSrCoolNetFanAlwaysOn OBJECT-TYPE
+ SYNTAX INTEGER {
+ disable(0),
+ enable(1) }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Leave fans on when not cooling. Only available when EnviroSense is connected to SRCOOLNET."
+ ::= { tlSrCoolNetConfig 7 }
+
+
+
+tlSrCoolNetAlarm OBJECT IDENTIFIER ::= { tlSrCoolNet 2 }
+
+tlSrCoolNetWellKnownAlarms OBJECT IDENTIFIER ::= { tlSrCoolNetAlarm 1 }
+
+tlSrCoolNetWaterFullAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Water reservoir full."
+ ::= { tlSrCoolNetWellKnownAlarms 1 }
+
+--------------------------------------------------------------------------
+-- Conformance definitions
+--------------------------------------------------------------------------
+
+tlConformance OBJECT IDENTIFIER ::= { tripplite 20 }
+
+tlCompliances OBJECT IDENTIFIER ::= { tlConformance 1 }
+
+tlGroups OBJECT IDENTIFIER ::= { tlConformance 2 }
+
+tlSubsetGroups OBJECT IDENTIFIER ::= { tlGroups 1 }
+
+tlBasicGroups OBJECT IDENTIFIER ::= { tlGroups 2 }
+
+tlFullGroups OBJECT IDENTIFIER ::= { tlGroups 3 }
+
+tlUpsFullGroups OBJECT IDENTIFIER ::= { tlFullGroups 100 }
+
+tlUpsFullIdentGroup OBJECT-GROUP
+ OBJECTS {
+ tlUpsIdentUpsSoftwareChecksum,
+ tlUpsIdentSerialNum,
+ tlUpsIdentID,
+ tlUpsSelectedDeviceID }
+ STATUS current
+ DESCRIPTION
+ "The tlUpsFullIdentGroup defines objects which are common to the Ident
+ group of fully compliant Tripplite UPS's"
+ ::= { tlUpsFullGroups 1 }
+
+tlUpsFullBatteryGroup OBJECT-GROUP
+ OBJECTS {
+ tlUpsBatteryAge,
+ tlUpsTemperatureF }
+ STATUS current
+ DESCRIPTION
+ "The tlUpsFullBatteryGroup defines objects which are common to the Battery
+ group of fully compliant Tripplite UPS's"
+ ::= { tlUpsFullGroups 2 }
+
+tlUpsFullAlarmGroup OBJECT IDENTIFIER ::= { tlUpsFullGroups 6 }
+
+tlUpsFullAlarmObjsGroup OBJECT-GROUP
+ OBJECTS {
+ tlUpsAlarmDevName,
+ tlUpsAlarmDevLocation,
+ tlUpsAlarmCategory }
+ STATUS current
+ DESCRIPTION
+ "The tlUpsFullAlarmObjsGroup defines objects which are common to
+ the Alarm group of fully compliant Tripplite UPS's"
+ ::= { tlUpsFullAlarmGroup 1 }
+
+--tlUpsFullAlarmsGroup NOTIFICATION-GROUP
+-- NOTIFICATIONS { }
+-- STATUS current
+-- DESCRIPTION
+-- "The tlUpsFullAlarmGroup defines notifications which are
+-- common to the Alarm group of fully compliant Tripplite UPS's"
+-- ::= { tlUpsFullAlarmGroup 2 }
+
+tlUpsFullTestGroup OBJECT-GROUP
+ OBJECTS {
+ tlUpsTestDate,
+ tlUpsTestResultsDetail }
+ STATUS current
+ DESCRIPTION
+ "The tlUpsFullTestGroup defines objects which are common to the Test
+ group of fully compliant Tripplite UPS's"
+ ::= { tlUpsFullGroups 7 }
+
+tlUpsFullControlGroup OBJECT-GROUP
+ OBJECTS {
+ tlUpsWatchdogSupported,
+ tlUpsWatchdogSecsBeforeReboot }
+ STATUS current
+ DESCRIPTION
+ "The tlUpsFullControlGroup defines objects which are common to the Control
+ group of fully compliant Tripplite UPS's"
+ ::= { tlUpsFullGroups 8 }
+
+tlUpsFullConfigGroup OBJECT-GROUP
+ OBJECTS {
+ tlUpsConfigBattReplDate }
+ STATUS current
+ DESCRIPTION
+ "The tlUpsFullConfigGroup defines objects which are common to the Config
+ group of fully compliant Tripplite UPS's"
+ ::= { tlUpsFullGroups 9 }
+
+tlUpsFullOutletGroup OBJECT-GROUP
+ OBJECTS {
+ tlUpsOutletNumOutlets }
+ STATUS current
+ DESCRIPTION
+ "The tlUpsFullOutletGroup defines objects which are common to the Outlet
+ group of fully compliant Tripplite UPS's"
+ ::= { tlUpsFullGroups 10 }
+
+
+END
|