diff --git a/MIBS/liebert/LIEBERT-GP-COND-MIB b/MIBS/liebert/LIEBERT-GP-COND-MIB new file mode 100644 index 0000000..dceab33 --- /dev/null +++ b/MIBS/liebert/LIEBERT-GP-COND-MIB @@ -0,0 +1,4816 @@ +LIEBERT-GP-CONDITIONS-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ MODULE-IDENTITY,
+ OBJECT-IDENTITY,
+ OBJECT-TYPE,
+ Gauge32,
+ TimeTicks,
+ Unsigned32
+ FROM SNMPv2-SMI
+ DisplayString
+ FROM SNMPv2-TC
+ lgpConditions,
+ liebertConditionsModuleReg
+ FROM LIEBERT-GP-REGISTRATION-MIB
+ ;
+
+-- =============================================================================
+-- Module Identification and Registration
+-- =============================================================================
+
+liebertGlobalProductsConditionsModule MODULE-IDENTITY
+ LAST-UPDATED "201302120000Z"
+ ORGANIZATION "Liebert Corporation"
+ CONTACT-INFO
+ "Contact: Technical Support
+
+ Postal:
+ Liebert Corporation
+ 1050 Dearborn Drive
+ P.O. Box 29186
+ Columbus OH, 43229
+ US
+
+ Tel: +1 (800) 222-5877
+
+ E-mail: liebert.monitoring@vertivco.com
+ Web: www.vertivco.com
+
+ Author: Gregory M. Hoge"
+
+ DESCRIPTION
+ "The MIB module used to register Liebert SNMP OIDs.
+
+ Copyright 2000-2008,2013 Liebert Corporation. All rights reserved.
+ Reproduction of this document is authorized on the condition
+ that the forgoing copyright notice is included.
+
+ This Specification is supplied 'AS IS' and Liebert Corporation
+ makes no warranty, either express or implied, as to the use,
+ operation, condition, or performance of the Specification."
+
+ REVISION "201302120000Z"
+ DESCRIPTION
+ "Added Surge Protection Device to lgpConditionCondenserTVSSFailure
+ DESCRIPTION"
+
+ REVISION "200811170000Z"
+ DESCRIPTION
+ "Added support for NXL unit."
+
+ REVISION "200807020000Z"
+ DESCRIPTION
+ "o Expanded condtions table with new columns with a set of richer
+ alarm/condition properties.
+ o Added additional reference columns to conditions table to allow the
+ same alarm to be active on multiple instances of an item.
+ "
+
+ REVISION "200801100000Z"
+ DESCRIPTION
+ "Modified contact email address and added lgpNetworkName object."
+
+ REVISION "200705290000Z"
+ DESCRIPTION
+ "Added support for XDF Unit."
+
+ REVISION "200608150000Z"
+ DESCRIPTION
+ "Added support for HP release and a condition for firmware corrupt."
+
+ REVISION "200602220000Z"
+ DESCRIPTION
+ "Added support for Liebert DS Unit."
+
+ ::= { liebertConditionsModuleReg 1 }
+
+-- =============================================================================
+-- lgpConditions - Liebert Conditions Registrations
+-- =============================================================================
+
+lgpConditionsWellKnown OBJECT IDENTIFIER
+ -- STATUS current
+ -- DESCRIPTION
+ -- "Liebert well known conditions are defined by OIDs that reside
+ -- in this sub-tree."
+ ::= { lgpConditions 1 }
+
+lgpConditionsPresent OBJECT-TYPE
+ SYNTAX Gauge32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present number of conditions (rows) in the lgpConditionsTable."
+ ::= { lgpConditions 2 }
+
+lgpConditionsTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF LgpConditionEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of condition table entries. The table contains zero, one,
+ or many rows at any moment, depending upon the number of conditions
+ in effect. The number of rows in the table is given by
+ (lgpConditionsPresent). The table is initially empty at agent startup.
+ The agent creates a row in the table each time a condition is detected
+ and deletes that row subject to the following rules:
+
+ Rows are removed from the table based on the following rules:
+ 1. If a condition does not require acknowledgement
+ (see 'lgpConditionAckReq') the condition is removed as soon as
+ the issue clears (see 'lgpConditionCurrentState').
+ 2. If a condition requires acknowledgement (see 'lgpConditionAckReq')
+ the condition is removed as soon as the issue clears
+ (see 'lgpConditionCurrentState') AND the condition is acknowledged
+ (see 'lgpConditionAcknowledged').
+ 3. If the columns 'lgpConditionCurrentState' and
+ 'lgpConditionAcknowledged' are not present for the condition
+ then the condition will be removed as soon as the issue causing
+ the condition clears.
+
+ The agent creates the first row with lgpConditionId equal to 1,
+ and increments the value of 'lgpConditionId' each time a new row is
+ created, wrapping to the first free value greater than or equal to 1
+ when the maximum value of lgpConditionId would otherwise be exceeded.
+ The number of rows in the table at any given time is reflected by
+ the value of 'lgpConditionsPresent'.
+ "
+ ::= { lgpConditions 3 }
+
+ lgpConditionEntry OBJECT-TYPE
+ SYNTAX LgpConditionEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This entry defines the contents of the rows for the table
+ 'lgpConditionsTable'. A row in this table cannot be created
+ or deleted by SNMP operations on columns of the table."
+ INDEX { lgpConditionId }
+ ::= { lgpConditionsTable 1 }
+
+ LgpConditionEntry ::= SEQUENCE {
+ lgpConditionId Unsigned32,
+ lgpConditionDescr OBJECT IDENTIFIER,
+ lgpConditionTime TimeTicks,
+ lgpConditionTableRef OBJECT IDENTIFIER,
+ lgpConditionTableRowRef OBJECT IDENTIFIER,
+ lgpConditionType INTEGER,
+ lgpConditionCurrentState INTEGER,
+ lgpConditionSeverity INTEGER,
+
+ lgpConditionAcknowledged INTEGER,
+ lgpConditionAckReq INTEGER
+ }
+
+ lgpConditionId OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique identifier for a condition. This value must remain
+ constant between agent initializations. This OID is used as
+ an index to identify a row in the table 'lgpConditionsTable'."
+ ::= { lgpConditionEntry 1 }
+
+ lgpConditionDescr OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A reference to a condition description object. The object
+ referenced should not be accessible, but rather be used to provide
+ a unique description."
+ ::= { lgpConditionEntry 2 }
+
+ lgpConditionTime OBJECT-TYPE
+ SYNTAX TimeTicks
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of sysUpTime when the condition occurred (became active)."
+ ::= { lgpConditionEntry 3 }
+
+ lgpConditionTableRef OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object will be included as a varbind in some
+ rows of the table. It is a reference to a table object in
+ the MIB. The value of this object will be the OID of a table
+ that the object that the condition applies to is defined.
+ The table row corresponding to this object will also contain
+ a varbind 'lgpConditionTableRowRef' that will specify which
+ instance (row) in the referenced table the object is defined in.
+
+ Example:
+ TABLE ROW:
+ lgpConditionId 5
+ lgpConditionDescr lgpConditionRcpBranchBreakerOpen
+ lgpConditionTime 393884848
+ lgpConditionTableRef lgpPduRbTable
+ lgpConditionTableRowRef lgpPduRbEntryId.1.4
+ lgpConditionType alarm
+ lgpConditionCurrentState active
+ lgpConditionSeverity major
+ lgpConditionAcknowledged acknowledged
+ lgpConditionAckReq required
+
+ In the above example the breaker opened for a Receptacle branch.
+ The specific receptacle branch is specified by the additional
+ varbind (lgpEventParmTableRowRef). In this case the notification
+ is for the 4th receptacle branch on the 1st PDU in the cluster.
+ "
+ ::= { lgpConditionEntry 5 }
+
+ lgpConditionTableRowRef OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This is a reference to the (cell) in the table specified by the
+ companion varbind (lgpConditionTableRef) in this condition.
+ The row in the table where this cell exists represents the object
+ that this condition applies to.
+
+ Example:
+ TABLE ROW:
+ lgpConditionId 5
+ lgpConditionDescr lgpConditionRcpBranchBreakerOpen
+ lgpConditionTime 393884848
+ lgpConditionTableRef lgpPduRbTable
+ lgpConditionTableRowRef lgpPduRbEntryId.1.4
+ lgpConditionType
+ lgpConditionCurrentState active
+ lgpConditionSeverity major
+ lgpConditionAcknowledged acknowledged
+ lgpConditionAckReq required
+
+ The table containing the definition of the receptacle branch
+ (lgpPduRbTable) is given by the varbind (lgpConditionTableRef)
+
+ The specific receptacle branch (instance) is specified by the
+ varbind (lgpConditionTableRowRef). In this case the condition
+ is for the 4th receptacle branch on the 1st PDU in the PDU cluster.
+
+ If one wanted to retrieve the serial number for this
+ receptacle branch the OID would be: lgpPduRbEntrySerialNum.1.4.
+ "
+ ::= { lgpConditionEntry 6 }
+
+ lgpConditionType OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ not-specified(0),
+ message(2),
+ warning(4),
+ alarm(6),
+ fault(8)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The type of condition in this row in the table."
+ ::= { lgpConditionEntry 10 }
+
+ lgpConditionCurrentState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ active(1),
+ inactive(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indication of the current state of the event. If the state
+ is 'active' then the condition currently exists. If the
+ state is 'inactive' then the condition no longer exists (i.e.
+ the situation causing the condition has cleared or been
+ resolved). The behavior of some devices is to remove
+ the condition from this table when the condition clears.
+ The behavior of other devices is to leave the condition
+ entry in the table until the condition is acknowledged (
+ see lgpConditionAcknowledged and lgpConditionAckReq)."
+ ::= { lgpConditionEntry 12 }
+
+ lgpConditionSeverity OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ not-applicable(0),
+ minor(3),
+ major(6),
+ critical(9)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This represents the relative severity of the condition."
+ ::= { lgpConditionEntry 14 }
+
+ lgpConditionAcknowledged OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ notAcknowledged(1),
+ acknowledged(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "This indicates if the condition has been acknowledged.
+ If the value is 'notAcknowledged' then the condition has
+ not been acknowledged. If the value is 'acknowledged'
+ then the condition has been acknowledged. Writing a value
+ of 'acknowledged' to this object acknowledges the condition
+ and the value will be changed to 'acknowledged'.
+
+ If the current state of the condition is 'active'
+ (see lgpConditionCurrentState) the condition will, for all
+ devices remain in the table regardless of the state of the
+ 'lgpConditionAcknowledged' object.
+
+ If the 'lgpConditionAckReq' is 'notRequired' or this column
+ does not exist for the row then this object has no affect on
+ the duration the condition stays in the lgpConditionsTable.
+
+ If the 'lgpConditionAckReq' is 'required' then the condition
+ will remain in the condition table until both the
+ 'lgpConditionCurrentState' is 'inactive' AND
+ 'lgpConditionAcknowledged' is 'acknowledged'.
+ "
+ ::= { lgpConditionEntry 18 }
+
+ lgpConditionAckReq OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ required(1),
+ notRequired(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This indicates if the corresponding condition does or does not
+ require user acknowledgement. Conditions that require
+ user acknowledgement will have a value of 'required'. Those
+ conditions that do not require user acknowledgement will have
+ a value of 'notRequired' or in some devices the column may
+ not be present at all.
+
+ If a condition requires acknowledgement it will remain in the
+ table until both the 'lgpConditionCurrentState' and
+ 'lgpConditionAcknowledged' are 'inactive' and 'acknowledged'
+ respectively (see lgpConditionAcknowledged).
+
+ If a condition does not require acknowledgement it will
+ be removed from the table as soon as its
+ 'lgpConditionCurrentState' is 'inactive'.
+ "
+ ::= { lgpConditionEntry 19 }
+
+-- =============================================================================
+-- lgpConditionControl - Condition Control Group
+-- =============================================================================
+
+lgpConditionControl OBJECT IDENTIFIER
+ -- STATUS current
+ -- DESCRIPTION
+ -- "Items under this sub-tree allow the user to control actions
+ -- associated with conditions."
+ ::= { lgpConditions 4 }
+
+ lgpConditionControlEventReset OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ noAction(1),
+ resetAll(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Event Reset Command. This command will reset all of the
+ device's events. On some units, when an event is activated, a
+ 'set' field is also marked and maintained even when the event has
+ become inactive. The 'set' field is only cleared when the user
+ clears it and the event is no longer active. This item will clear
+ the 'set' field for all events that are not active."
+ ::= { lgpConditionControl 1 }
+
+ lgpConditionControlEventAck OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ noAction(1),
+ ackAll(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Event Acknowledge Command. This command will acknowledge all of the
+ device's events."
+ ::= { lgpConditionControl 2 }
+
+lgpConditionControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF LgpConditionControlEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of condition control table entries. The table contains zero, one,
+ or many rows at any moment, depending upon the number of conditions that
+ are controllable by the unit. This table does not necessarily contain all
+ conditions supported by the unit. This table only contains conditions that
+ are end-user modifiable."
+ ::= { lgpConditionControl 20 }
+
+ lgpConditionControlEntry OBJECT-TYPE
+ SYNTAX LgpConditionControlEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This entry defines the contents of the rows for the table
+ 'lgpConditionControlTable'. A row in this table cannot be created
+ or deleted by user initiated SNMP operations on columns of the table."
+ INDEX { lgpConditionControlIndex }
+ ::= { lgpConditionControlTable 1 }
+
+ LgpConditionControlEntry ::= SEQUENCE {
+ lgpConditionControlIndex Unsigned32,
+ lgpConditionControlDescr OBJECT IDENTIFIER,
+ lgpConditionControlEnableStatus INTEGER,
+ lgpConditionControlType INTEGER,
+ lgpConditionControlEnableCapability INTEGER
+ }
+
+ lgpConditionControlIndex OBJECT-TYPE
+ SYNTAX Unsigned32
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This is the index indicating the nth element of the table."
+ ::= { lgpConditionControlEntry 1 }
+
+ lgpConditionControlDescr OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A reference to an Object Identifier (OID) representing a unique
+ condition. The referenced OID is used solely for identification
+ purposes.
+
+ The object identifier referenced here will be the same object
+ identifier referenced in the lgpConditionsTable (column:
+ lgpConditionDescr) when the condition is activated."
+ ::= { lgpConditionControlEntry 2 }
+
+ lgpConditionControlEnableStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ not-specified(0),
+ enabled(1),
+ disabled(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The value in this column determines if the device is currently
+ capable of generating this event. If the value is 'enabled' then
+ the event will be generated if the condition indicated by
+ lgpConditionControlDescr becomes active. If the value is
+ 'disabled' the device will never generate the event. This value is
+ stored on the managed device.
+ Some devices do not allow write access to some entries in this
+ column. The 'lgpConditionControlEnableCapability' column indicates
+ whether this entry can be written."
+ ::= { lgpConditionControlEntry 3 }
+
+ lgpConditionControlType OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ not-specified(0),
+ message(2),
+ warning(4),
+ alarm(6),
+ fault(8)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The 'type' assigned or configured for this condition. The value
+ assigned to the condition here is displayed in the
+ lgpConditionsTable (column: lgpConditionType). For some units this
+ is user configurable. This value is stored on the managed device."
+ ::= { lgpConditionControlEntry 4 }
+
+ lgpConditionControlEnableCapability OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ not-specified(0),
+ readonly(1),
+ readwrite(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Some devices do not allow write access to some entries in the
+ 'lgpConditionControlEnableStatus' column. This column indicates
+ whether the 'lgpConditionControlEnableStatus' entry for this row
+ can be written."
+ ::= { lgpConditionControlEntry 5 }
+
+lgpConditionDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The ASCII text description for the condition."
+ ::= { lgpConditions 5 }
+
+lgpNetworkName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (255))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The network name in a node.domain.com like format. This object is
+ intended to be used as a varbind object by other notifications that
+ have a context of a network address. As an example the
+ lgpAgentDnsLookupFailure trap which describes a network name that
+ is failing or has failed to be resolved from a Domain Name Service (DNS)
+ lookup.
+
+ Refer to RFC 952 for further information."
+ ::= { lgpConditions 6 }
+
+-- =============================================================================
+-- lgpConditions - Additional Liebert Conditions Registrations
+-- =============================================================================
+
+lgpFlexConditions OBJECT IDENTIFIER
+ -- STATUS current
+ -- DESCRIPTION
+ -- "Liebert well known Flexible conditions are defined by OIDs that reside
+ -- in this sub-tree. These OIDs can be found in the
+ -- LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB which is located in the file
+ -- LIEBERT_GP_FLEXIBLE_COND.MIB."
+ ::= { lgpConditions 7 }
+
+-- =============================================================================
+-- lgpConditionsWellKnown - Liebert "well-known" conditions
+-- =============================================================================
+
+lgpConditionHighTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold."
+ ::= { lgpConditionsWellKnown 1 }
+
+lgpConditionLowTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature is below the low temperature threshold."
+ ::= { lgpConditionsWellKnown 2 }
+
+lgpConditionHighHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidity has exceeded the high humidity threshold."
+ ::= { lgpConditionsWellKnown 3 }
+
+lgpConditionLowHumidity OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidity is below the low humidity threshold."
+ ::= { lgpConditionsWellKnown 4 }
+
+lgpConditionLossOfAirflow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of air flow."
+ ::= { lgpConditionsWellKnown 5 }
+
+ lgpConditionLossOfAirflow1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of air flow at sensor 1."
+ ::= { lgpConditionLossOfAirflow 1 }
+
+ lgpConditionLossOfAirflow2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of air flow at sensor 2."
+ ::= { lgpConditionLossOfAirflow 2 }
+
+ lgpConditionLossOfAirflowBlower1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of air flow from blower 1."
+ ::= { lgpConditionLossOfAirflow 3 }
+
+ lgpConditionLossOfAirflowAllBlowers OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "No air flow through the unit due to failure of all blowers."
+ ::= { lgpConditionLossOfAirflow 4 }
+
+lgpConditionChangeFilter OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a condition indicating the air filter
+ should be changed."
+ ::= { lgpConditionsWellKnown 6 }
+
+lgpConditionCompressorHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an excessive head pressure condition."
+ ::= { lgpConditionsWellKnown 7 }
+
+ lgpConditionCompressor1HighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected excessive head pressure in compressor 1."
+ ::= { lgpConditionCompressorHighHeadPressure 1 }
+
+ lgpConditionCompressor1AHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected excessive head pressure in compressor 1A."
+ ::= { lgpConditionCompressor1HighHeadPressure 1 }
+
+ lgpConditionCompressor1BHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected excessive head pressure in compressor 1B."
+ ::= { lgpConditionCompressor1HighHeadPressure 2 }
+
+ lgpConditionCompressor2HighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected excessive head pressure in compressor 2."
+ ::= { lgpConditionCompressorHighHeadPressure 2 }
+
+ lgpConditionCompressor2AHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected excessive head pressure in compressor 2A."
+ ::= { lgpConditionCompressor2HighHeadPressure 1 }
+
+ lgpConditionCompressor2BHighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected excessive head pressure in compressor 2B."
+ ::= { lgpConditionCompressor2HighHeadPressure 2 }
+
+ lgpConditionCompressor3HighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected excessive head pressure in compressor 3."
+ ::= { lgpConditionCompressorHighHeadPressure 3 }
+
+ lgpConditionCompressor4HighHeadPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected excessive head pressure in compressor 4."
+ ::= { lgpConditionCompressorHighHeadPressure 4 }
+
+lgpConditionCompressorOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a compressor overload condition."
+ ::= { lgpConditionsWellKnown 8 }
+
+ lgpConditionCompressor1Overload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an overload condition on compressor 1."
+ ::= { lgpConditionCompressorOverload 1 }
+
+ lgpConditionCompressor2Overload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an overload condition on compressor 2."
+ ::= { lgpConditionCompressorOverload 2 }
+
+ lgpConditionCompressor3Overload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an overload condition on compressor 3."
+ ::= { lgpConditionCompressorOverload 3 }
+
+ lgpConditionCompressor4Overload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an overload condition on compressor 4."
+ ::= { lgpConditionCompressorOverload 4 }
+
+lgpConditionCompressorShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A compressor has exceeded the maximum number of starts in a
+ minimum time period."
+ ::= { lgpConditionsWellKnown 9 }
+
+ lgpConditionCompressor1ShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycle event on compressor 1.
+ The compressor has exceeded the maximum number of starts for
+ specified amount of time."
+ ::= { lgpConditionCompressorShortCycle 1 }
+
+ lgpConditionCompressor1AShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycle event on compressor 1A.
+ The compressor has exceeded the maximum number of starts for
+ specified amount of time."
+ ::= { lgpConditionCompressor1ShortCycle 1 }
+
+ lgpConditionCompressor1BShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycle event on compressor 1B.
+ The compressor has exceeded the maximum number of starts for
+ specified amount of time."
+ ::= { lgpConditionCompressor1ShortCycle 2 }
+
+ lgpConditionCompressor2ShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycle event on compressor 2.
+ The compressor has exceeded the maximum number of starts for
+ specified amount of time."
+ ::= { lgpConditionCompressorShortCycle 2 }
+
+ lgpConditionCompressor2AShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycle event on compressor 2A.
+ The compressor has exceeded the maximum number of starts for
+ specified amount of time."
+ ::= { lgpConditionCompressor2ShortCycle 1 }
+
+ lgpConditionCompressor2BShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycle event on compressor 2B.
+ The compressor has exceeded the maximum number of starts for
+ specified amount of time."
+ ::= { lgpConditionCompressor2ShortCycle 2 }
+
+ lgpConditionCompressor3ShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycle event on compressor 3.
+ The compressor has exceeded the maximum number of starts for
+ specified amount of time."
+ ::= { lgpConditionCompressorShortCycle 3 }
+
+ lgpConditionCompressor4ShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycle event on compressor 4.
+ The compressor has exceeded the maximum number of starts for
+ specified amount of time."
+ ::= { lgpConditionCompressorShortCycle 4 }
+
+lgpConditionCompressorLowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The pressure at a compressor inlet has dropped below the
+ minimum setting."
+ ::= { lgpConditionsWellKnown 10 }
+
+ lgpConditionCompressor1LowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The pressure at compressor 1 inlet has dropped below the
+ minimum setting."
+ ::= { lgpConditionCompressorLowSuctionPressure 1 }
+
+ lgpConditionCompressor2LowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The pressure at compressor 2 inlet has dropped below the
+ minimum setting."
+ ::= { lgpConditionCompressorLowSuctionPressure 2 }
+
+ lgpConditionCompressor3LowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The pressure at compressor 3 inlet has dropped below the
+ minimum setting."
+ ::= { lgpConditionCompressorLowSuctionPressure 3 }
+
+ lgpConditionCompressor4LowSuctionPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The pressure at compressor 4 inlet has dropped below the
+ minimum setting."
+ ::= { lgpConditionCompressorLowSuctionPressure 4 }
+
+lgpConditionMainFanOverLoad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a main fan overload condition."
+ ::= { lgpConditionsWellKnown 11 }
+
+lgpConditionManualOverride OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a manual override condition."
+ ::= { lgpConditionsWellKnown 12 }
+
+lgpConditionStandbyGlycoolPumpOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The standby Glycol or Glycool pump is activated."
+ ::= { lgpConditionsWellKnown 13 }
+
+lgpConditionWaterUnderFloor OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Moisture has been detected under the floor."
+ ::= { lgpConditionsWellKnown 14 }
+
+lgpConditionHumidifierProblem OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a humidifier problem."
+ ::= { lgpConditionsWellKnown 15 }
+
+lgpConditionLowWaterInHumidifier OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low water condition in the humidifier
+ reservoir."
+ ::= { lgpConditionsWellKnown 16 }
+
+lgpConditionSmokeDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected smoke."
+ ::= { lgpConditionsWellKnown 17 }
+
+lgpConditionLowWaterFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low water flow rate condition."
+ ::= { lgpConditionsWellKnown 18 }
+
+lgpConditionLostPower OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has lost power before being switched off using the
+ controls. This condition is activated when power is restored."
+ ::= { lgpConditionsWellKnown 19 }
+
+lgpGeneralFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A fault condition has been detected that is not identified
+ in the well known list."
+ ::= { lgpConditionsWellKnown 20 }
+
+lgpConditionLocalAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a local, or customer, alarm condition."
+ ::= { lgpConditionsWellKnown 21 }
+
+ lgpConditionLocalAlarm1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that customer alarm condition 1 is active."
+ ::= { lgpConditionLocalAlarm 1 }
+
+ lgpConditionLocalAlarm2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that customer alarm condition 2 is active."
+ ::= { lgpConditionLocalAlarm 2 }
+
+ lgpConditionLocalAlarm3 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that customer alarm condition 3 is active."
+ ::= { lgpConditionLocalAlarm 3 }
+
+ lgpConditionLocalAlarm4 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that customer alarm condition 4 is active."
+ ::= { lgpConditionLocalAlarm 4 }
+
+ lgpConditionLocalAlarm5 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that customer alarm condition 5 is active."
+ ::= { lgpConditionLocalAlarm 5 }
+
+ lgpConditionLocalAlarm6 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that customer alarm condition 6 is active."
+ ::= { lgpConditionLocalAlarm 6 }
+
+ lgpConditionLocalAlarm7 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that customer alarm condition 7 is active."
+ ::= { lgpConditionLocalAlarm 7 }
+
+ lgpConditionLocalAlarm8 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that customer alarm condition 8 is active."
+ ::= { lgpConditionLocalAlarm 8 }
+
+lgpConditionStandbyUnitOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the standby unit is operating."
+ ::= { lgpConditionsWellKnown 22 }
+
+lgpConditionCompressorLowPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a low head compressor condition."
+ ::= { lgpConditionsWellKnown 23 }
+
+ lgpConditionCompressor1LowPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected low pressure in compressor 1."
+ ::= { lgpConditionCompressorLowPressure 1 }
+
+ lgpConditionTandemCompressorCircuit1LowPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected low pressure in tandem compressor circuit 1."
+ ::= { lgpConditionCompressor1LowPressure 1 }
+
+ lgpConditionCompressor2LowPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected low pressure in compressor 2."
+ ::= { lgpConditionCompressorLowPressure 2 }
+
+ lgpConditionTandemCompressorCircuit2LowPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected low pressure in tandem compressor circuit 2."
+ ::= { lgpConditionCompressor2LowPressure 1 }
+
+ lgpConditionCompressor3LowPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected low pressure in compressor 3."
+ ::= { lgpConditionCompressorLowPressure 3 }
+
+ lgpConditionCompressor4LowPressure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected low pressure in compressor 4."
+ ::= { lgpConditionCompressorLowPressure 4 }
+
+lgpConditionHighWaterInPan OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high water condition in the condenser pan."
+ ::= { lgpConditionsWellKnown 24 }
+
+lgpConditionFaultySensor OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a faulty temperature/humidity sensor."
+ ::= { lgpConditionsWellKnown 25 }
+
+lgpConditionServiceCooling OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Cooling system requires scheduled maintenance."
+ ::= { lgpConditionsWellKnown 26 }
+
+lgpConditionServiceHumidifier OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Humidifier requires scheduled maintenance."
+ ::= { lgpConditionsWellKnown 27 }
+
+lgpConditionSystemControlBatteryLow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Charge level of the system control's battery is below the
+ alarm set point."
+ ::= { lgpConditionsWellKnown 28 }
+
+lgpConditionGroundSystemFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a ground system fault."
+ ::= { lgpConditionsWellKnown 29 }
+
+lgpConditionGroundFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a ground failure."
+ ::= { lgpConditionsWellKnown 30 }
+
+lgpConditionSecurityBreach OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a security breach."
+ ::= { lgpConditionsWellKnown 31 }
+
+lgpConditionEmergencyShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an emergency shutdown condition. The System
+ is shutting down as a result of this emergency."
+ ::= { lgpConditionsWellKnown 32 }
+
+lgpConditionOnBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected the load is being powered by a bypass
+ source."
+ ::= { lgpConditionsWellKnown 33 }
+
+ lgpConditionLoadOnBypass OBJECT-IDENTITY
+ STATUS obsolete
+ DESCRIPTION
+ "The load is being powered by a bypass source."
+ ::= { lgpConditionOnBypass 1 }
+
+ lgpConditionLoadOnMaintenceBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The load is being powered by a maintenance bypass source."
+ ::= { lgpConditionOnBypass 2 }
+
+ lgpConditionParallelSysLoadOnBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The parallel system has transferred to bypass."
+ ::= { lgpConditionOnBypass 3 }
+
+ lgpConditionLoadOnBypassByImpact OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a load impact and has transferred the
+ load to the bypass source."
+ ::= { lgpConditionOnBypass 4 }
+
+ lgpConditionLoadTransferedToBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has transferred to bypass. The load is being powered by
+ the bypass source."
+ ::= { lgpConditionOnBypass 5 }
+
+ lgpConditionEmergencyTransferToBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has performed an emergency transfer to bypass."
+ ::= { lgpConditionOnBypass 6 }
+
+lgpConditionOutputToLoadVoltTHD OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The total harmonic distortion (THD) of the output voltage has exceeded a
+ pre-determined threshold for a device, or system, defined amount of
+ time."
+ ::= { lgpConditionsWellKnown 34 }
+
+lgpConditionLogicFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a control logic failure."
+ ::= { lgpConditionsWellKnown 35 }
+
+lgpConditionPowerSupplyFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system had detected a power supply fault condition."
+ ::= { lgpConditionsWellKnown 36 }
+
+ lgpConditionPowerSupply1Fault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected power supply 1 is in a fault condition."
+ ::= { lgpConditionPowerSupplyFault 1 }
+
+ lgpConditionPowerSupply2Fault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected power supply 2 is in a fault condition."
+ ::= { lgpConditionPowerSupplyFault 2 }
+
+lgpConditionPowerSupplyFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a power supply failure condition."
+ ::= { lgpConditionsWellKnown 37 }
+
+ lgpConditionPowerSupply1Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected power supply 1 has failed."
+ ::= { lgpConditionPowerSupplyFailure 1 }
+
+ lgpConditionPowerSupply2Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected power supply 2 has failed."
+ ::= { lgpConditionPowerSupplyFailure 2 }
+
+ lgpConditionSource1PowerSupplyInputFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the source 1 Power supply input has failed."
+ ::= { lgpConditionPowerSupplyFailure 3 }
+
+ lgpConditionSource2PowerSupplyInputFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the source 2 Power supply input has failed."
+ ::= { lgpConditionPowerSupplyFailure 4 }
+
+ lgpConditionPowerSupplyLogicFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a power supply logic failure."
+ ::= { lgpConditionPowerSupplyFailure 5 }
+
+ lgpConditionCompressorPowerSupplyFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the power supply to the compressors
+ has failed."
+ ::= { lgpConditionPowerSupplyFailure 6 }
+
+lgpConditionOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an over voltage condition."
+ ::= { lgpConditionsWellKnown 38 }
+
+ lgpConditionSource1OverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over voltage condition on source 1.
+ The voltage measurement has risen above a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionOverVoltage 1 }
+
+ lgpConditionSource2OverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over voltage condition on source 2.
+ The voltage measurement has risen above a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionOverVoltage 2 }
+
+ lgpConditionOutputToLoadOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the output to load is in an over-voltage
+ condition. The voltage for the load has risen above a
+ pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOverVoltage 3 }
+
+ lgpConditionInputOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an input over voltage condition. The
+ voltage measurement has risen above a pre-determined threshold for
+ a specified amount of time."
+ ::= { lgpConditionOverVoltage 4 }
+
+ lgpConditionBypassOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over voltage condition on the bypass.
+ The voltage measurement has risen above a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionOverVoltage 5 }
+
+ lgpConditionBypassOverVoltageFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over voltage failure condition on the
+ bypass. The voltage measurement has risen above a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverVoltage 6 }
+
+ lgpConditionBatteryOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery over voltage condition."
+ ::= { lgpConditionOverVoltage 7 }
+
+ lgpConditionDcBusOverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a DC Bus over voltage condition."
+ ::= { lgpConditionOverVoltage 8 }
+
+ lgpConditionDcBus1OverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over voltage condition on DC Bus
+ 1."
+ ::= { lgpConditionDcBusOverVoltage 1 }
+
+ lgpConditionDcBus2OverVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over voltage condition on DC Bus
+ 2."
+ ::= { lgpConditionDcBusOverVoltage 2 }
+
+ lgpConditionDcBus1OverVoltageFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over voltage failure condition
+ on DC Bus 1."
+ ::= { lgpConditionDcBusOverVoltage 3 }
+
+ lgpConditionDcBus2OverVoltageFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over voltage failure condition
+ on DC Bus 2."
+ ::= { lgpConditionDcBusOverVoltage 4 }
+
+lgpConditionUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an under voltage condition."
+ ::= { lgpConditionsWellKnown 39 }
+
+ lgpConditionSource1UnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage condition on source 1.
+ The voltage measurement has fallen below a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionUnderVoltage 1 }
+
+ lgpConditionSource2UnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage condition on source 2.
+ The voltage measurement has fallen below a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionUnderVoltage 2 }
+
+ lgpConditionOutputToLoadUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the output to load is in an under-voltage
+ condition. The voltage for the load has fallen below a
+ pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionUnderVoltage 3 }
+
+ lgpConditionSource1UnderVoltageRMS OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage condition on source 1.
+ The voltage measurement has fallen below a pre-determined threshold
+ for a specified amount of time."
+ ::= { lgpConditionUnderVoltage 4 }
+
+ lgpConditionSource2UnderVoltageRMS OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage condition on source 2.
+ The voltage measurement has fallen below a pre-determined threshold
+ for a specified amount of time."
+ ::= { lgpConditionUnderVoltage 5 }
+
+ lgpConditionInputUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an input under voltage condition.
+ The voltage measurement has fallen below a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionUnderVoltage 6 }
+
+ lgpConditionBypassUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage condition on the bypass.
+ The voltage measurement has fallen below a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionUnderVoltage 7 }
+
+ lgpConditionBypassUnderVoltageFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage failure condition on the
+ bypass. The voltage measurement has fallen below a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionUnderVoltage 8 }
+
+ lgpConditionBatteryUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery under voltage condition."
+ ::= { lgpConditionUnderVoltage 9 }
+
+ lgpConditionDcBusUnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a DC bus under voltage condition"
+ ::= { lgpConditionUnderVoltage 10 }
+
+ lgpConditionDcBus1UnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage condition on DC Bus
+ 1."
+ ::= { lgpConditionDcBusUnderVoltage 1 }
+
+ lgpConditionDcBus2UnderVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage condition on DC Bus
+ 2."
+ ::= { lgpConditionDcBusUnderVoltage 2 }
+
+ lgpConditionDcBus1UnderVoltageFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage failure condition
+ on DC Bus 1."
+ ::= { lgpConditionDcBusUnderVoltage 3 }
+
+ lgpConditionDcBus2UnderVoltageFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an under voltage failure condition
+ on DC Bus 2."
+ ::= { lgpConditionDcBusUnderVoltage 4 }
+
+lgpConditionOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an overload condition."
+ ::= { lgpConditionsWellKnown 40 }
+
+ lgpConditionSource1Overload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an overload condition on source 1. The
+ power requirement for this source has risen above a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverload 1 }
+
+ lgpConditionSystemOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an overload condition."
+ ::= { lgpConditionOverload 2 }
+
+ lgpConditionSource1PeakCurrentOverLoad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected source 1 in is experiencing a peak over load
+ condition. The current has risen above a pre-determined threshold for
+ a specified amount of time."
+ ::= { lgpConditionOverload 3 }
+
+ lgpConditionSource2PeakCurrentOverLoad OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected source 2 in is experiencing a peak over load
+ condition. The current has risen above a pre-determined threshold for
+ a specified amount of time."
+ ::= { lgpConditionOverload 4 }
+
+ lgpConditionOutputToLoadOverLimit OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system had detected that the output to the load has exceeded the
+ lgpPwrOutputToLoadUserOverloadLimit."
+ ::= { lgpConditionOverload 5 }
+
+ lgpConditionOutputToLoadOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an output overload condition."
+ ::= { lgpConditionOverload 6 }
+
+ lgpConditionParallelSysOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The parallel system has detected an overload condition."
+ ::= { lgpConditionOverload 7 }
+
+ lgpConditionBypassCurrentOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "With the load on bypass static switch, the measured output
+ RMS current has exceeded a specified percentage of the nominal
+ RMS current."
+ ::= { lgpConditionOverload 8 }
+
+ lgpConditionBypassCurrentOverloadPhsA OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "With the load on bypass static switch, the measured phase A output
+ RMS current has exceeded a specified percentage of the nominal
+ per-phase RMS current."
+ ::= { lgpConditionBypassCurrentOverload 1 }
+
+ lgpConditionBypassCurrentOverloadPhsB OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "With the load on bypass static switch, the measured phase B output
+ RMS current has exceeded a specified percentage of the nominal
+ per-phase RMS current."
+ ::= { lgpConditionBypassCurrentOverload 2 }
+
+ lgpConditionBypassCurrentOverloadPhsC OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "With the load on bypass static switch, the measured phase C output
+ RMS current has exceeded a specified percentage of the nominal
+ per-phase RMS current."
+ ::= { lgpConditionBypassCurrentOverload 3 }
+
+lgpConditionScrShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a Silicon Controlled Rectifier (SCR)
+ short condition."
+ ::= { lgpConditionsWellKnown 41 }
+
+ lgpConditionSource1ScrShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 1 Silicon Controlled Rectifier
+ (SCR) short condition."
+ ::= { lgpConditionScrShort 1 }
+
+ lgpConditionSource2ScrShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 2 Silicon Controlled Rectifier
+ (SCR) short condition."
+ ::= { lgpConditionScrShort 2 }
+
+ lgpConditionBypassScrShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a Silicon Controlled Rectifier (SCR) short
+ condition on the bypass."
+ ::= { lgpConditionScrShort 3 }
+
+ lgpConditionInvStaticSwScrShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short across one or more inverter static
+ switch Silicon Controlled Rectifiers (SCRs)."
+ ::= { lgpConditionScrShort 4 }
+
+ lgpConditionSource1NeutralScrShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 1 Silicon Controlled Rectifier
+ (SCR) short condition on the neutral line."
+ ::= { lgpConditionScrShort 5 }
+
+ lgpConditionSource2NeutralScrShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 2 Silicon Controlled Rectifier
+ (SCR) short condition on the neutral line."
+ ::= { lgpConditionScrShort 6 }
+
+lgpConditionScrOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a Silicon Controlled Rectifier (SCR)
+ open condition."
+ ::= { lgpConditionsWellKnown 42 }
+
+ lgpConditionSource1ScrOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 1 Silicon Controlled Rectifier
+ (SCR) open condition."
+ ::= { lgpConditionScrOpen 1 }
+
+ lgpConditionSource2ScrOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 2 Silicon Controlled Rectifier
+ (SCR) open condition."
+ ::= { lgpConditionScrOpen 2 }
+
+ lgpConditionBypassScrOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a Silicon Controlled Rectifier (SCR) open
+ condition on the bypass."
+ ::= { lgpConditionScrOpen 3 }
+
+ lgpConditionSource1NeutralScrOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 1 Silicon Controlled Rectifier
+ (SCR) open condition on the neutral line."
+ ::= { lgpConditionScrOpen 4 }
+
+ lgpConditionSource2NeutralScrOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 2 Silicon Controlled Rectifier
+ (SCR) open condition on the neutral line."
+ ::= { lgpConditionScrOpen 5 }
+
+lgpConditionFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a fan failure condition."
+ ::= { lgpConditionsWellKnown 43 }
+
+ lgpConditionFan1Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a fan 1 failure condition."
+ ::= { lgpConditionFanFailure 1 }
+
+ lgpConditionRedundantFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A failure has occurred in a fan that cools the system's internal
+ components and has resulted in a loss of fan redundancy."
+ ::= { lgpConditionFanFailure 2 }
+
+ lgpConditionMultipleFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Multiple fans have failed resulting in a decreased ability to cool
+ the system's internal components."
+ ::= { lgpConditionFanFailure 3 }
+
+ lgpConditionBlowerFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a problem with one or more of the blower
+ fans. These are not the system internal cooling fans."
+ ::= { lgpConditionFanFailure 4 }
+
+ lgpConditionBottomBlowerFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The bottom environmental unit blower fan is not operating
+ within its normal parameters."
+ ::= { lgpConditionBlowerFanFailure 1 }
+
+ lgpConditionTopBlowerFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The top environmental unit blower fan is not operating
+ within its normal parameters."
+ ::= { lgpConditionBlowerFanFailure 2 }
+
+ lgpConditionCondenserFanVFDFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a problem with the Variable Frequency
+ Drive system for the condenser fan."
+ ::= { lgpConditionFanFailure 5 }
+
+ lgpConditionFanPowerFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a power failure on one or more fans."
+ ::= { lgpConditionFanFailure 6 }
+
+lgpConditionTransferInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is preventing a transfer of the load to the alternate
+ source."
+ ::= { lgpConditionsWellKnown 44 }
+
+lgpConditionAutoReTransferPrimed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is capable to retransfer to the preferred source."
+ ::= { lgpConditionsWellKnown 45 }
+
+lgpConditionSourcesOutOfSync OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that the input sources are not within the
+ specified phase difference (synchronization window)."
+ ::= { lgpConditionsWellKnown 46 }
+
+lgpConditionSourceFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an input source failure condition."
+ ::= { lgpConditionsWellKnown 47 }
+
+ lgpConditionSource1Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected source 1 has failed."
+ ::= { lgpConditionSourceFailure 1 }
+
+ lgpConditionSource2Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected source 2 has failed."
+ ::= { lgpConditionSourceFailure 2 }
+
+lgpConditionAutoReTransferInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is preventing a retransfer of the load back to the
+ preferred source."
+ ::= { lgpConditionsWellKnown 48 }
+
+lgpConditionAutoReTransferFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is failing to automatically retransfer the load back to the
+ preferred source."
+ ::= { lgpConditionsWellKnown 49 }
+
+lgpConditionFuseOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an open fuse condition."
+ ::= { lgpConditionsWellKnown 50 }
+
+ lgpConditionControlFuse1Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a control power fuse 1 open condition."
+ ::= { lgpConditionFuseOpen 1 }
+
+ lgpConditionControlFuse2Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a control power fuse 2 open condition."
+ ::= { lgpConditionFuseOpen 2 }
+
+ lgpConditionRectifierFuseOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a rectifier fuse open condition."
+ ::= { lgpConditionFuseOpen 3 }
+
+ lgpConditionInverterFuseOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter fuse open condition."
+ ::= { lgpConditionFuseOpen 4 }
+
+ lgpConditionOutputToLoadFuseOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an output to load fuse open condition."
+ ::= { lgpConditionFuseOpen 5 }
+
+ lgpConditionDcCapacitorFuseOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a DC capacitor fuse open condition."
+ ::= { lgpConditionFuseOpen 6 }
+
+lgpConditionDisconnect OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a disconnect condition."
+ ::= { lgpConditionsWellKnown 51 }
+
+ lgpConditionSource1DisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the source 1 disconnect is open.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 1 }
+
+ lgpConditionSource2DisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the source 2 disconnect is open.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 2 }
+
+ lgpConditionSource1PduDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the source 1 PDU (Power Distribution Unit)
+ disconnect is open.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 3 }
+
+ lgpConditionSource2PduDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the source 2 PDU (Power Distribution Unit)
+ disconnect is open.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 4 }
+
+ lgpConditionOutputToLoadDisconnect1Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected Output to load disconnect 1 is open.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 5 }
+
+ lgpConditionOutputToLoadDisconnect2Open OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected Output to load disconnect 2 is open.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 6 }
+
+ lgpConditionSource1BypassDisconnectClosed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the source 1 bypass disconnect is closed.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 7 }
+
+ lgpConditionSource2BypassDisconnectClosed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the source 2 bypass disconnect is closed.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 8 }
+
+ lgpConditionOutputToLoadNeutralDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the output to load neutral disconnect is
+ open. A disconnect is a device which disconnects a conductor of a
+ circuit from its supply (ex. circuit breaker, contactor, isolating
+ switch, disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 9 }
+
+ lgpConditionBatteryDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the battery disconnect is open.
+ A disconnect is a device which disconnects a conductor of a
+ circuit from its supply (ex. circuit breaker, contactor, isolating
+ switch, disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 10 }
+
+ lgpConditionBatteryDiscOpenCab01 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the cabinet 1 battery disconnect is
+ open."
+ ::= { lgpConditionBatteryDisconnectOpen 1 }
+
+ lgpConditionBatteryDiscOpenCab02 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the cabinet 2 battery disconnect is
+ open."
+ ::= { lgpConditionBatteryDisconnectOpen 2 }
+
+ lgpConditionBatteryDiscOpenCab03 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the cabinet 3 battery disconnect is
+ open."
+ ::= { lgpConditionBatteryDisconnectOpen 3 }
+
+ lgpConditionBatteryDiscOpenCab04 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the cabinet 4 battery disconnect is
+ open."
+ ::= { lgpConditionBatteryDisconnectOpen 4 }
+
+ lgpConditionBatteryDiscOpenCab05 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the cabinet 5 battery disconnect is
+ open."
+ ::= { lgpConditionBatteryDisconnectOpen 5 }
+
+ lgpConditionBatteryDiscOpenCab06 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the cabinet 6 battery disconnect is
+ open."
+ ::= { lgpConditionBatteryDisconnectOpen 6 }
+
+ lgpConditionBatteryDiscOpenCab07 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the cabinet 7 battery disconnect is
+ open."
+ ::= { lgpConditionBatteryDisconnectOpen 7 }
+
+ lgpConditionBatteryDiscOpenCab08 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the cabinet 8 battery disconnect is
+ open."
+ ::= { lgpConditionBatteryDisconnectOpen 8 }
+
+ lgpConditionInputDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the input disconnect is open.
+ A disconnect is a device which disconnects a conductor of a
+ circuit from its supply (ex. circuit breaker, contactor, isolating
+ switch, disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 11 }
+
+ lgpConditionOutputToLoadDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the Output to load disconnect is open.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 12 }
+
+ lgpConditionBypassDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the bypass disconnect is open. A
+ disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 13 }
+
+ lgpConditionStaticSwitchDisconnectOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the static switch disconnect is open.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnect 14 }
+
+ lgpConditionBreakerOpenFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A breaker in the system has failed to respond to an Open signal."
+ ::= { lgpConditionDisconnect 15 }
+
+ lgpConditionBreakerCloseFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A breaker in the system has failed to respond to a Close signal."
+ ::= { lgpConditionDisconnect 16 }
+
+lgpConditionFrequencyDeviation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a frequency deviation condition.
+ The frequency of a source is outside of the pre-determined thresholds
+ for a specified amount of time."
+ ::= { lgpConditionsWellKnown 52 }
+
+ lgpConditionSource1FrequencyDeviation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The frequency for source 1 has been outside of the pre-determined
+ thresholds for a specified period of time."
+ ::= { lgpConditionFrequencyDeviation 1 }
+
+ lgpConditionSource2FrequencyDeviation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The frequency for source 2 has been outside of the pre-determined
+ thresholds for a specified period of time."
+ ::= { lgpConditionFrequencyDeviation 2 }
+
+ lgpConditionInputFrequencyDeviation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The frequency for the input has been outside of the pre-determined
+ thresholds for a specified period of time."
+ ::= { lgpConditionFrequencyDeviation 3 }
+
+ lgpConditionOutputToLoadFrequencyDeviation
+ OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The frequency for the output has been outside of the pre-determined
+ thresholds for a specified period of time."
+ ::= { lgpConditionFrequencyDeviation 4 }
+
+ lgpConditionBypassFrequencyDeviation OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The frequency for the bypass input has been outside of the
+ pre-determined thresholds for a specified period of time."
+ ::= { lgpConditionFrequencyDeviation 5 }
+
+lgpConditionOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an over-current condition. The current of a
+ source has risen above a pre-determined threshold for a device,
+ or system, defined amount of time."
+ ::= { lgpConditionsWellKnown 53 }
+
+ lgpConditionSource1OverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over current condition on source 1.
+ The current of a source has risen above a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverCurrent 1 }
+
+ lgpConditionSource2OverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over current condition on source 2.
+ The current of a source has risen above a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverCurrent 2 }
+
+ lgpConditionOutputToLoadOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the output to load is in an over-current
+ condition. The current for the load has risen above a
+ pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOverCurrent 3 }
+
+ lgpConditionOutputToLoadOverCurrentPhsA OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the output to load on phase A is in an
+ over-current condition. The current on this phase has risen above
+ a pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOutputToLoadOverCurrent 1 }
+
+ lgpConditionOutputToLoadOverCurrentPhsB OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the output to load on phase B is in an
+ over-current condition. The current on this phase has risen above
+ a pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOutputToLoadOverCurrent 2 }
+
+ lgpConditionOutputToLoadOverCurrentPhsC OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the output to load on phase C is in an
+ over-current condition. The current on this phase has risen above
+ a pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOutputToLoadOverCurrent 3 }
+
+ lgpConditionGroundOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A ground source is experiencing an over-current condition. The
+ current for the ground line has risen above a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverCurrent 4 }
+
+ lgpConditionRectifierOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a rectifier over current condition.
+ The current for the rectifier has risen above a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverCurrent 5 }
+
+ lgpConditionInverterOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter over current condition.
+ The current for the inverter has risen above a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverCurrent 6 }
+
+ lgpConditionInverterOverCurrentPhsA OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter over current condition on
+ phase A. The current for the this phase in the inverter has risen
+ above a pre-determined threshold for a device, or system, defined
+ amount of time."
+ ::= { lgpConditionInverterOverCurrent 1 }
+
+ lgpConditionInverterOverCurrentPhsB OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter over current condition on
+ phase B. The current for the this phase in the inverter has risen
+ above a pre-determined threshold for a device, or system, defined
+ amount of time."
+ ::= { lgpConditionInverterOverCurrent 2 }
+
+ lgpConditionInverterOverCurrentPhsC OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter over current condition on
+ phase C. The current for the this phase in the inverter has risen
+ above a pre-determined threshold for a device, or system, defined
+ amount of time."
+ ::= { lgpConditionInverterOverCurrent 3 }
+
+ lgpConditionBatteryConverterOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over current condition on the battery
+ converter. The current of the converter has risen above a
+ pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOverCurrent 7 }
+
+ lgpConditionBatteryBalancerOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery balancer over current condition.
+ The current at this point has risen above a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverCurrent 8 }
+
+ lgpConditionHumidifierOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over current condition on the
+ humidifier. The current of the humidifier has risen above
+ a pre-determined threshold for a defined amount of time."
+ ::= { lgpConditionOverCurrent 9 }
+
+ lgpConditionInputOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "There is an over current condition on the system input power.
+ The input current has risen above a pre-determined threshold for
+ a pre-defined amount of time."
+ ::= { lgpConditionOverCurrent 10 }
+
+ lgpConditionSource1NeutralOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over current condition on the neutral
+ line of source 1. The neutral current at source 1 has risen above
+ a pre-determined threshold for a pre-defined amount of time."
+ ::= { lgpConditionOverCurrent 11 }
+
+ lgpConditionSource2NeutralOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over current condition on the neutral
+ line of source 2. The neutral current at source 2 has risen above
+ a pre-determined threshold for a pre-defined amount of time."
+ ::= { lgpConditionOverCurrent 12 }
+
+lgpConditionSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a sensor failure condition."
+ ::= { lgpConditionsWellKnown 54 }
+
+ lgpConditionOutputToLoadVoltageSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system had detected an output to load voltage sensor failure."
+ ::= { lgpConditionSensorFailure 1 }
+
+ lgpConditionSource1VoltageSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system had detected a source 1 voltage sensor failure."
+ ::= { lgpConditionSensorFailure 2 }
+
+ lgpConditionSource2VoltageSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system had detected a source 2 voltage sensor failure."
+ ::= { lgpConditionSensorFailure 3 }
+
+ lgpConditionSource1ScrSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system had detected a source 1 SCR (Silicon Controlled
+ Rectifier) sensor failure."
+ ::= { lgpConditionSensorFailure 4 }
+
+ lgpConditionSource2ScrSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system had detected a source 2 SCR (Silicon Controlled
+ Rectifier) sensor failure."
+ ::= { lgpConditionSensorFailure 5 }
+
+ lgpConditionSource1CurrentSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 1 current sensor failure."
+ ::= { lgpConditionSensorFailure 6 }
+
+ lgpConditionSource2CurrentSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 2 current sensor failure."
+ ::= { lgpConditionSensorFailure 7 }
+
+ lgpConditionRoomTempHumiditySensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a device temperature and humidity sensor
+ failure."
+ ::= { lgpConditionSensorFailure 8 }
+
+ lgpConditionGlycolTempSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a glycol temperature sensor failure."
+ ::= { lgpConditionSensorFailure 9 }
+
+ lgpConditionLocal1SensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a local 1 sensor failure."
+ ::= { lgpConditionSensorFailure 10 }
+
+ lgpConditionCompressor1SensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a compressor 1 digital scroll sensor
+ failure condition."
+ ::= { lgpConditionSensorFailure 11 }
+
+ lgpConditionCompressor2SensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a compressor 2 digital scroll sensor
+ failure condition."
+ ::= { lgpConditionSensorFailure 12 }
+
+ lgpConditionSupplySensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a supply sensor failure."
+ ::= { lgpConditionSensorFailure 13 }
+
+ lgpConditionCabinetTemperatureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a cabinet temperature sensor failure."
+ ::= { lgpConditionSensorFailure 14 }
+
+ lgpConditionCabinetHumiditySensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a cabinet humidity sensor failure."
+ ::= { lgpConditionSensorFailure 15 }
+
+ lgpConditionRoomTempSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a room temperature sensor failure."
+ ::= { lgpConditionSensorFailure 16 }
+
+ lgpConditionBatteryTempSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery temperature sensor failure."
+ ::= { lgpConditionSensorFailure 17 }
+
+ lgpConditionAirSensorAFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a failure with air sensor A. The sensor
+ may have been disconnected or the signal is out of range."
+ ::= { lgpConditionSensorFailure 18 }
+
+ lgpConditionAirSensorBFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a failure with air sensor B. The sensor
+ may have been disconnected or the signal is out of range."
+ ::= { lgpConditionSensorFailure 19 }
+
+ lgpConditionChilledWaterSupplySensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a failure with the chilled water supply
+ sensor. The sensor may have been disconnected or the signal is out
+ of range."
+ ::= { lgpConditionSensorFailure 20 }
+
+ lgpConditionRefrigerantSupplySensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a failure with the refrigerant supply
+ sensor. The sensor may have been disconnected or the signal is out
+ of range."
+ ::= { lgpConditionSensorFailure 21 }
+
+ lgpConditionFluidSupplySensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a failure with the fluid supply
+ sensor. The sensor may have been disconnected or the signal is out
+ of range."
+ ::= { lgpConditionSensorFailure 22 }
+
+ lgpConditionCompressorLowPressureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that a compressor low pressure
+ transducer is disconnected or the signal is out of range."
+ ::= { lgpConditionSensorFailure 23 }
+
+ lgpConditionCompressor1LowPressureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that compressor 1 low pressure
+ transducer is disconnected or the signal is out of range."
+ ::= { lgpConditionCompressorLowPressureSensorFailure 1 }
+
+ lgpConditionRemoteSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that a remote sensor is disconnected
+ or the signal is out of range."
+ ::= { lgpConditionSensorFailure 24 }
+
+ lgpConditionAirSupplyTempSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that the supply air temperature sensor is
+ disconnected or the signal is out of range."
+ ::= { lgpConditionSensorFailure 25 }
+
+ lgpConditionAirReturnTempSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that the return air temperature sensor is
+ disconnected or the signal is out of range."
+ ::= { lgpConditionSensorFailure 26 }
+
+ lgpConditionCompressorHighPressureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that a compressor high pressure
+ transducer is disconnected or the signal is out of range."
+ ::= { lgpConditionSensorFailure 27 }
+
+ lgpConditionCompressor2HighPressureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that compressor 2 high pressure
+ transducer is disconnected or the signal is out of range."
+ ::= { lgpConditionCompressorHighPressureSensorFailure 2 }
+
+ lgpConditionCompressor3HighPressureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that compressor 3 high pressure
+ transducer is disconnected or the signal is out of range."
+ ::= { lgpConditionCompressorHighPressureSensorFailure 3 }
+
+ lgpConditionCompressor4HighPressureSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that compressor 4 high pressure
+ transducer is disconnected or the signal is out of range."
+ ::= { lgpConditionCompressorHighPressureSensorFailure 4 }
+
+
+lgpConditionInternalCommunicationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an internal communication failure condition."
+ ::= { lgpConditionsWellKnown 55 }
+
+lgpConditionExternalCommunicationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an external communication failure condition."
+ ::= { lgpConditionsWellKnown 56 }
+
+lgpConditionSourceGateDriveFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a source gate drive failure condition."
+ ::= { lgpConditionsWellKnown 57 }
+
+ lgpConditionSource1GateDriveFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 1 gate drive failure."
+ ::= { lgpConditionSourceGateDriveFailure 1 }
+
+ lgpConditionSource2GateDriveFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a source 2 gate drive failure."
+ ::= { lgpConditionSourceGateDriveFailure 2 }
+
+lgpConditionDisconnectFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a disconnect failure condition.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionsWellKnown 58 }
+
+ lgpConditionOutputToLoadNeutralDisconnectFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the output to load neutral disconnect has
+ failed.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnectFailure 1 }
+
+ lgpConditionSource1DisconnectShuntTripFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a shunt trip failure of a disconnecting device
+ on source 1.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnectFailure 2 }
+
+ lgpConditionSource2DisconnectShuntTripFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a shunt trip failure of a disconnecting device
+ on source 2.
+ A disconnect is a device which disconnects a conductor of a circuit
+ from its supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnectFailure 3 }
+
+ lgpConditionInverterDisconnectFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter disconnect failure. A disconnect
+ is a device which disconnects a conductor of a circuit from its
+ supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnectFailure 4 }
+
+ lgpConditionBatteryDisconnectFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery disconnect failure. A disconnect
+ is a device which disconnects a conductor of a circuit from its
+ supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnectFailure 5 }
+
+ lgpConditionRectifierDisconnectFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a rectifier disconnect failure. A disconnect
+ is a device which disconnects a conductor of a circuit from its
+ supply (ex. circuit breaker, contactor, isolating switch,
+ disconnecting switch, etc.)."
+ ::= { lgpConditionDisconnectFailure 6 }
+
+lgpConditionOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an over temperature condition."
+ ::= { lgpConditionsWellKnown 59 }
+
+ lgpConditionHeatSink1OverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a heat sink 1 over temperature condition."
+ ::= { lgpConditionOverTemperature 1 }
+
+ lgpConditionAmbient1OverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an ambient over temperature condition at
+ location 1."
+ ::= { lgpConditionOverTemperature 2 }
+
+ lgpConditionSystemOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system or a component of the system has detected an over
+ temperature condition. The temperature measurement has risen
+ above a pre-determined threshold for a device, or system, defined
+ amount of time."
+ ::= { lgpConditionOverTemperature 3 }
+
+ lgpConditionTransformerOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The transformer is experiencing an over temperature condition.
+ The transformer's temperature has exceeded a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverTemperature 4 }
+
+ lgpConditionBatteryOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery is experiencing an over temperature condition.
+ The battery's temperature has exceeded a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionOverTemperature 5 }
+
+ lgpConditionRectifierOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a rectifier over temperature condition.
+ The rectifier's temperature has exceeded a pre-determined threshold
+ for a device, or system, defined amount of time."
+ ::= { lgpConditionOverTemperature 6 }
+
+ lgpConditionInverterOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter over temperature condition.
+ The inverter's temperature has exceeded a pre-determined
+ threshold for a device, or system, defined amount of time."
+ ::= { lgpConditionOverTemperature 7 }
+
+ lgpConditionRectifierInductorOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a rectifier inductor over temperature
+ condition. The rectifier's inductor temperature has exceeded a
+ pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOverTemperature 8 }
+
+ lgpConditionInverterInductorOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter inductor over temperature
+ condition. The inverter's inductor temperature has exceeded a
+ pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOverTemperature 9 }
+
+ lgpConditionBatteryConverterOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery converter over temperature
+ condition. The battery converter's temperature has exceeded a
+ pre-determined threshold for a device, or system, defined amount
+ of time."
+ ::= { lgpConditionOverTemperature 10 }
+
+ lgpConditionBatteryBalancerInductorOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery balancer Inductor over
+ temperature condition. The battery balancer Inductor's temperature
+ has exceeded a pre-determined threshold for a specified amount of
+ time."
+ ::= { lgpConditionOverTemperature 11 }
+
+ lgpConditionChilledWaterOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a chilled water over temperature
+ condition."
+ ::= { lgpConditionOverTemperature 12 }
+
+ lgpConditionElectricHeatersOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an electric heater over temperature
+ condition."
+ ::= { lgpConditionOverTemperature 13 }
+
+ lgpConditionInletAirOverTemperature OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inlet air over temperature condition."
+ ::= { lgpConditionOverTemperature 14 }
+
+ lgpConditionSystemOverTempWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system or a component of the system has detected an over
+ temperature condition. The temperature measurement has risen
+ above a normal operating range for a device, or system, defined
+ amount of time. The system is still operational but a threshold has
+ been exceeded."
+ ::= { lgpConditionOverTemperature 15 }
+
+ lgpConditionHighTemperatureBattString OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high temperature on a battery string.
+ The temperature has exceeded a specified temperature threshold."
+ ::= { lgpConditionOverTemperature 16 }
+
+lgpConditionLoadOnAlternateSource OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that the load is being supplied by the
+ alternate source."
+ ::= { lgpConditionsWellKnown 60 }
+
+lgpConditionPhaseRotationError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a phase rotation error condition."
+ ::= { lgpConditionsWellKnown 61 }
+
+ lgpConditionSource1PhaseRotationError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a phase rotation error on source 1."
+ ::= { lgpConditionPhaseRotationError 1 }
+
+ lgpConditionSource2PhaseRotationError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a phase rotation error on source 2."
+ ::= { lgpConditionPhaseRotationError 2 }
+
+ lgpConditionBypassPhaseRotationError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a phase rotation error on the bypass."
+ ::= { lgpConditionPhaseRotationError 3 }
+
+ lgpConditionInputPhaseRotationError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a phase rotation error on the input."
+ ::= { lgpConditionPhaseRotationError 4 }
+
+lgpConditionControlModuleFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a control module failure condition."
+ ::= { lgpConditionsWellKnown 62 }
+
+ lgpConditionControlModule1Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a control module 1 failure."
+ ::= { lgpConditionControlModuleFailure 1 }
+
+lgpConditionHistoryLogFull OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the history log is full."
+ ::= { lgpConditionsWellKnown 63 }
+
+lgpConditionConfigurationModified OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the configuration has been modified."
+ ::= { lgpConditionsWellKnown 64 }
+
+lgpConditionPasswordModified OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the password has been modified."
+ ::= { lgpConditionsWellKnown 65 }
+
+lgpConditionTimeModified OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the time has been modified."
+ ::= { lgpConditionsWellKnown 66 }
+
+lgpConditionDateModified OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the date has been modified."
+ ::= { lgpConditionsWellKnown 67 }
+
+lgpConditionEventLogCleared OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the event log has been cleared."
+ ::= { lgpConditionsWellKnown 68 }
+
+lgpConditionHistoryLogCleared OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the history log has been cleared."
+ ::= { lgpConditionsWellKnown 69 }
+
+lgpConditionUtilityFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a utility failure."
+ ::= { lgpConditionsWellKnown 70 }
+
+lgpConditionBatteryTestInProgress OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is performing a battery test at this time."
+ ::= { lgpConditionsWellKnown 71 }
+
+lgpConditionLoadOnBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system load is being supported by the battery."
+ ::= { lgpConditionsWellKnown 72 }
+
+lgpConditionReplaceBattery OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the batteries are due to be replaced."
+ ::= { lgpConditionsWellKnown 74 }
+
+lgpConditionUpsShutdownPending OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is in a shutdown pending condition."
+ ::= { lgpConditionsWellKnown 75 }
+
+lgpConditionBatteryChargerFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the battery charger has failed."
+ ::= { lgpConditionsWellKnown 76 }
+
+lgpConditionBypassVoltageUnqualified OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the bypass voltage is unqualified.
+ The voltage measurement is outside a pre-determined threshold range for
+ a specified amount of time."
+ ::= { lgpConditionsWellKnown 77 }
+
+lgpConditionCheckAirFilter OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected it is time to check the air filter."
+ ::= { lgpConditionsWellKnown 78 }
+
+lgpConditionBrownOut OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a brown out condition."
+ ::= { lgpConditionsWellKnown 79 }
+
+lgpConditionMultipleTransferLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has locked out transfers to bypass. Too many transfers
+ have occurred over a specified amount of time."
+ ::= { lgpConditionsWellKnown 80 }
+
+lgpConditionBypassPhaseLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected one or more bypass phases are missing."
+ ::= { lgpConditionsWellKnown 81 }
+
+lgpConditionMaintenceBypassInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is preventing a transfer of the load to maintenance bypass."
+ ::= { lgpConditionsWellKnown 82 }
+
+lgpConditionLoadLockedOnBypass OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An error has been detected requiring the system to be put into a
+ 'locked on bypass' state."
+ ::= { lgpConditionsWellKnown 83 }
+
+lgpConditionOutputToLoadShort OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an output to load short circuit condition."
+ ::= { lgpConditionsWellKnown 84 }
+
+lgpConditionEmergencyTransferToInverter OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an emergency transfer of the load to
+ inverter."
+ ::= { lgpConditionsWellKnown 85 }
+
+lgpConditonEmergencyPowerOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an Emergency Power Off (EPO) condition.
+ An external EPO switch has cut off the power source to the system."
+ ::= { lgpConditionsWellKnown 86 }
+
+lgpConditionInverterBackFeed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter back-feed condition. The inverter
+ is feeding power through the bypass back to the input."
+ ::= { lgpConditionsWellKnown 87 }
+
+lgpConditionDcGroundFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a DC ground fault."
+ ::= { lgpConditionsWellKnown 88 }
+
+ lgpConditionDcGroundFaultPos OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ground fault current has been detected in the positive DC link to
+ ground."
+ ::= { lgpConditionDcGroundFault 1 }
+
+ lgpConditionDcGroundFaultNeg OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ground fault current has been detected in the negative DC link to
+ ground."
+ ::= { lgpConditionDcGroundFault 2 }
+
+lgpConditionStaticTransferSwitchInhibited
+ OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is preventing the use of the static transfer switch."
+ ::= { lgpConditionsWellKnown 89 }
+
+lgpConditionBatteryLogFullWarning
+ OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the battery log is approaching the maximum
+ record limit."
+ ::= { lgpConditionsWellKnown 90 }
+
+lgpConditionInputCurrentUnbalanced
+ OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an unbalanced input current condition.
+ The currents of input phases are out of tolerance."
+ ::= { lgpConditionsWellKnown 91 }
+
+lgpConditionSelfTestFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a self-test failure."
+ ::= { lgpConditionsWellKnown 92 }
+
+lgpConditionInverterOutOfSynchronization
+ OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an Inverter out of sync condition."
+ ::= { lgpConditionsWellKnown 93 }
+
+lgpConditionModuleAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected an alarm within the multi-module system."
+ ::= { lgpConditionsWellKnown 94 }
+
+ lgpConditioniModuleUnit1Alarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system has detected an alarm condition on
+ unit 1."
+ ::= { lgpConditionModuleAlarm 1 }
+
+ lgpConditioniModuleUnit2Alarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system has detected an alarm condition on
+ unit 2."
+ ::= { lgpConditionModuleAlarm 2 }
+
+ lgpConditioniModuleUnit3Alarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system has detected an alarm condition on
+ unit 3."
+ ::= { lgpConditionModuleAlarm 3 }
+
+ lgpConditioniModuleUnit4Alarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system has detected an alarm condition on
+ unit 4."
+ ::= { lgpConditionModuleAlarm 4 }
+
+ lgpConditioniModuleUnit5Alarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system has detected an alarm condition on
+ unit 5."
+ ::= { lgpConditionModuleAlarm 5 }
+
+ lgpConditioniModuleUnit6Alarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system has detected an alarm condition on
+ unit 6."
+ ::= { lgpConditionModuleAlarm 6 }
+
+ lgpConditioniModuleUnit7Alarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system has detected an alarm condition on
+ unit 7."
+ ::= { lgpConditionModuleAlarm 7 }
+
+ lgpConditioniModuleUnit8Alarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The multi-module system has detected an alarm condition on
+ unit 8."
+ ::= { lgpConditionModuleAlarm 8 }
+
+lgpConditionActiveModuleAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an active alarm in one, or more, of the
+ sub-modules of the multi-module system."
+ ::= { lgpConditionsWellKnown 95 }
+
+lgpConditionControlFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a control failure condition."
+ ::= { lgpConditionsWellKnown 96 }
+
+ lgpConditionMainControlFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a main control failure condition."
+ ::= { lgpConditionControlFailure 1 }
+
+ lgpConditionRedundantControlFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a redundant control failure condition."
+ ::= { lgpConditionControlFailure 2 }
+
+ lgpConditionParallelSysControlFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The parallel system has detected a control failure condition with
+ one of the controls."
+ ::= { lgpConditionControlFailure 3 }
+
+ lgpConditionMainControlCommFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "One or more communications failures have occurred in the main
+ control."
+ ::= { lgpConditionControlFailure 4 }
+
+ lgpConditionControlBoardFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a control board failure."
+ ::= { lgpConditionControlFailure 5 }
+
+ lgpConditionHumidifierControlBdFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Humidifier control board is required to be connected,
+ but no signal is detected."
+ ::= { lgpConditionControlBoardFailure 1 }
+
+lgpConditionControlWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This system has detected a control warning conditions."
+ ::= { lgpConditionsWellKnown 97 }
+
+ lgpConditionMainControlWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a main control warning condition."
+ ::= { lgpConditionControlWarning 1 }
+
+ lgpConditionRedundantControlWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a redundant control warning condition."
+ ::= { lgpConditionControlWarning 2 }
+
+lgpConditionUserInterfaceFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a user interface control failure condition."
+ ::= { lgpConditionsWellKnown 98 }
+
+lgpConditionLostPowerRedundancy OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the number of redundant power modules has
+ fallen below the minimum redundant power module setting."
+ ::= { lgpConditionsWellKnown 99 }
+
+lgpConditionPowerModuleFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a power module failure condition in the
+ system."
+ ::= { lgpConditionsWellKnown 100 }
+
+lgpConditionBatteryModuleFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery module failure condition in the
+ system."
+ ::= { lgpConditionsWellKnown 101 }
+
+lgpConditionOutputToLoadOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that there is no power being supplied to the
+ load."
+ ::= { lgpConditionsWellKnown 102 }
+
+lgpConditionSystemOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is off."
+ ::= { lgpConditionsWellKnown 103 }
+
+lgpConditionRectifierStartupFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a rectifier under voltage start-up failure
+ condition."
+ ::= { lgpConditionsWellKnown 104 }
+
+lgpConditionRectifierFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a rectifier fault condition."
+ ::= { lgpConditionsWellKnown 105 }
+
+lgpConditionInverterShutdownLowDc OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has shutdown the inverter due to a DC bus under voltage."
+ ::= { lgpConditionsWellKnown 106 }
+
+lgpConditionInverterFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an inverter fault condition."
+ ::= { lgpConditionsWellKnown 107 }
+
+lgpConditionInverterDcOffsetOverrun OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an over run of the inverter DC offset
+ voltage."
+ ::= { lgpConditionsWellKnown 108 }
+
+lgpConditionParallelSysLowBatteryWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The parallel system has detected a low battery warning condition."
+ ::= { lgpConditionsWellKnown 109 }
+
+lgpConditionParallelSysLoadShareFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The parallel system has detected a load share fault condition."
+ ::= { lgpConditionsWellKnown 110 }
+
+lgpConditionBatteryFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery fault condition. The battery
+ conductors are either reversed or disconnected."
+ ::= { lgpConditionsWellKnown 111 }
+
+lgpConditionBatteryConverterFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery converter failure condition."
+ ::= { lgpConditionsWellKnown 112 }
+
+lgpConditionBatteryBalancerFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery balancer fault condition."
+ ::= { lgpConditionsWellKnown 113 }
+
+lgpConditionpsUpsOperationFault OBJECT-IDENTITY
+ STATUS deprecated
+ DESCRIPTION
+ "The system has detected an operation fault. The UPS attempted to
+ transfer to maintenance bypass without following the proper sequence."
+ ::= { lgpConditionsWellKnown 114 }
+
+lgpConditionOutputToLoadOnJointMode OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system load is being supported by both the battery and rectifier."
+ ::= { lgpConditionsWellKnown 115 }
+
+lgpConditionInputNeutralLost OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system had detected the main input neutral is disconnected."
+ ::= { lgpConditionsWellKnown 116 }
+
+lgpConditionLowBatteryWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery's remaining charge is less than or equal to the
+ configured low threshold."
+ ::= { lgpConditionsWellKnown 117 }
+
+lgpConditionInternalFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an internal fault."
+ ::= { lgpConditionsWellKnown 118 }
+
+lgpConditionBatteryTestFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a battery self-test failure."
+ ::= { lgpConditionsWellKnown 119 }
+
+lgpConditionPowerModuleWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an alarm condition on one, or more,
+ power modules."
+ ::= { lgpConditionsWellKnown 120 }
+
+lgpConditionBatteryModuleWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an alarm condition on one, or more,
+ battery modules."
+ ::= { lgpConditionsWellKnown 121 }
+
+lgpConditionControlModuleWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a control module warning."
+ ::= { lgpConditionsWellKnown 122 }
+
+lgpConditionUpsOperationFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an operation fault. The UPS attempted to
+ transfer to maintenance bypass without following the proper sequence."
+ ::= { lgpConditionsWellKnown 123 }
+
+lgpConditionActiveAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an alarm condition."
+ ::= { lgpConditionsWellKnown 124 }
+
+lgpConditionRectifierCommunicationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an internal communication failure
+ condition with the rectifier."
+ ::= { lgpConditionsWellKnown 125 }
+
+lgpConditionInverterCommunicationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an internal communication failure
+ condition with the inverter."
+ ::= { lgpConditionsWellKnown 126 }
+
+lgpConditionParallelSysConnectionFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The parallel system has detected a connection fault.
+ One or more of the devices are not properly connected."
+ ::= { lgpConditionsWellKnown 127 }
+
+lgpConditionParallelSysCommunicationFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The parallel system has detected a communication failure."
+ ::= { lgpConditionsWellKnown 128 }
+
+lgpConditionLostBatteryRedundancy OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the number of redundant battery modules has
+ fallen below the configured redundant battery module threshold."
+ ::= { lgpConditionsWellKnown 129 }
+
+lgpConditionCompPumpDownFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that a compressor has failed to pump down."
+ ::= { lgpConditionsWellKnown 130 }
+
+ lgpConditionComp1PumpDownFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that compressor 1 has failed to pump
+ down."
+ ::= { lgpConditionCompPumpDownFailure 1 }
+
+ lgpConditionComp2PumpDownFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that compressor 2 has failed to pump
+ down."
+ ::= { lgpConditionCompPumpDownFailure 2 }
+
+ lgpConditionComp3PumpDownFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that compressor 3 has failed to pump
+ down."
+ ::= { lgpConditionCompPumpDownFailure 3 }
+
+ lgpConditionComp4PumpDownFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that compressor 4 has failed to pump
+ down."
+ ::= { lgpConditionCompPumpDownFailure 4 }
+
+lgpConditionChilledWaterLowWaterFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a chilled water low water flow condition."
+ ::= { lgpConditionsWellKnown 131 }
+
+ lgpConditionChilledWaterLowWaterFlowCircuit2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a chilled water low water flow condition for circuit 2."
+ ::= { lgpConditionChilledWaterLowWaterFlow 2 }
+
+lgpConditionAirFilterClogged OBJECT-IDENTITY
+ STATUS deprecated
+ DESCRIPTION
+ "The system has detected a air filter clogged condition."
+ ::= { lgpConditionsWellKnown 132 }
+
+lgpConditionHumidifierFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a humidifier failure condition."
+ ::= { lgpConditionsWellKnown 133 }
+
+lgpConditionRunHoursExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a pre-determined run hours threshold has been
+ exceeded."
+ ::= { lgpConditionsWellKnown 134 }
+
+ lgpConditionUnitRunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the system run hours has exceeded the
+ pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 1 }
+
+ lgpConditionComp1RunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the compressor 1 run hours has exceeded
+ the pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 2 }
+
+ lgpConditionComp2RunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the compressor 2 run hours has exceeded
+ the pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 3 }
+
+ lgpConditionFreeCoolRunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the free cooling run hours has exceeded
+ the pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 4 }
+
+ lgpConditionElectricalHeater1RunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the electrical heater's run hours have
+ exceeded the pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 5 }
+
+ lgpConditionElectricalHeater2RunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the electrical heater's run hours have
+ exceeded the pre-determined limit."
+ ::= { lgpConditionRunHoursExceeded 6 }
+
+ lgpConditionElectricalHeater3RunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the electrical heater's run hours have
+ exceeded the pre-determined limit."
+ ::= { lgpConditionRunHoursExceeded 7 }
+
+ lgpConditionHotWaterRunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the hot water run hours have exceeded
+ the pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 8 }
+
+ lgpConditionHotGasRunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the hot gas run hours have exceeded the
+ pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 9 }
+
+ lgpConditionHumidifierRunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the humidifier run hours have exceeded
+ the pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 10 }
+
+ lgpConditionDehumidiferRunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the dehumidifier run hours have exceeded
+ the pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 11 }
+
+ lgpConditionFanRunHrsExceeded OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the unit blower fan run hours have
+ exceeded the pre-determined threshold."
+ ::= { lgpConditionRunHoursExceeded 12 }
+
+lgpConditionCommWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with another
+ module."
+ ::= { lgpConditionsWellKnown 135 }
+
+ lgpConditionCommWarningUnit1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 1."
+ ::= { lgpConditionCommWarning 1 }
+
+ lgpConditionCommWarningUnit2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 2."
+ ::= { lgpConditionCommWarning 2 }
+
+ lgpConditionCommWarningUnit3 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 3."
+ ::= { lgpConditionCommWarning 3 }
+
+ lgpConditionCommWarningUnit4 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 4."
+ ::= { lgpConditionCommWarning 4 }
+
+ lgpConditionCommWarningUnit5 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 5."
+ ::= { lgpConditionCommWarning 5 }
+
+ lgpConditionCommWarningUnit6 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 6."
+ ::= { lgpConditionCommWarning 6 }
+
+ lgpConditionCommWarningUnit7 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 7."
+ ::= { lgpConditionCommWarning 7 }
+
+ lgpConditionCommWarningUnit8 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 8."
+ ::= { lgpConditionCommWarning 8 }
+
+ lgpConditionCommWarningUnit9 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 9."
+ ::= { lgpConditionCommWarning 9 }
+
+ lgpConditionCommWarningUnit10 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 10."
+ ::= { lgpConditionCommWarning 10 }
+
+ lgpConditionCommWarningUnit11 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 11."
+ ::= { lgpConditionCommWarning 11 }
+
+ lgpConditionCommWarningUnit12 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 12."
+ ::= { lgpConditionCommWarning 12 }
+
+ lgpConditionCommWarningUnit13 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 13."
+ ::= { lgpConditionCommWarning 13 }
+
+ lgpConditionCommWarningUnit14 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 14."
+ ::= { lgpConditionCommWarning 14 }
+
+ lgpConditionCommWarningUnit15 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 15."
+ ::= { lgpConditionCommWarning 15 }
+
+ lgpConditionCommWarningUnit16 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of communications with unit 16."
+ ::= { lgpConditionCommWarning 16 }
+
+lgpConditionUnitOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The unit is on."
+ ::= { lgpConditionsWellKnown 136 }
+
+lgpConditionUnitOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The unit is off."
+ ::= { lgpConditionsWellKnown 137 }
+
+lgpConditionSleepModeOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system sleep mode operation has been turned off."
+ ::= { lgpConditionsWellKnown 138 }
+
+lgpConditionPowerOn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system power is on."
+ ::= { lgpConditionsWellKnown 139 }
+
+lgpConditionSystemOnStanby OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is on standby."
+ ::= { lgpConditionsWellKnown 140 }
+
+lgpConditionPowerOff OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system power is off."
+ ::= { lgpConditionsWellKnown 141 }
+
+lgpConditionHighTemperatureGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high temperature condition. This group
+ contains various high temperature conditions."
+ ::= { lgpConditionsWellKnown 142 }
+
+ lgpConditionHighTemperatureSensor1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold
+ for sensor 1."
+ ::= { lgpConditionHighTemperatureGroup 1 }
+
+ lgpConditionHighTemperatureDigitalScroll1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high temperature event on Digital
+ Scroll Compressor 1. The temperature has exceeded a specified
+ temperature threshold."
+ ::= { lgpConditionHighTemperatureGroup 2 }
+
+ lgpConditionHighTemperatureDigitalScroll2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high temperature event on Digital
+ Scroll Compressor 2. The temperature has exceeded a specified
+ temperature threshold."
+ ::= { lgpConditionHighTemperatureGroup 3 }
+
+ lgpConditionHighTemperatureUser1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold
+ for user configured temperature sensor 1."
+ ::= { lgpConditionHighTemperatureGroup 4 }
+
+ lgpConditionHighTemperatureInternal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high internal temperature condition.
+ The temperature has exceeded a specified temperature threshold."
+ ::= { lgpConditionHighTemperatureGroup 5 }
+
+ lgpConditionHighTemperatureExternalAirSensorA OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold
+ for external air sensor A."
+ ::= { lgpConditionHighTemperatureGroup 6 }
+
+ lgpConditionHighTemperatureExternalAirSensorB OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold
+ for external air sensor B."
+ ::= { lgpConditionHighTemperatureGroup 7 }
+
+ lgpConditionHighTemperatureRefrigerantSupply OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold
+ for the refrigerant supply."
+ ::= { lgpConditionHighTemperatureGroup 8 }
+
+ lgpConditionHighTemperatureFluidSupply OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold
+ for the fluid supply."
+ ::= { lgpConditionHighTemperatureGroup 9 }
+
+ lgpConditionHighTemperatureSupplyAir OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold
+ for the supply air."
+ ::= { lgpConditionHighTemperatureGroup 10 }
+
+ lgpConditionHighTemperatureReturnAir OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature has exceeded the high temperature threshold
+ for the return air."
+ ::= { lgpConditionHighTemperatureGroup 11 }
+
+lgpConditionLowTemperatureGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low temperature condition. This group
+ contains various low temperature conditions."
+ ::= { lgpConditionsWellKnown 143 }
+
+ lgpConditionLowTemperatureSensor1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature is below the low temperature threshold for
+ sensor 1."
+ ::= { lgpConditionLowTemperatureGroup 1 }
+
+ lgpConditionLowTemperatureInternal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low internal temperature condition.
+ The temperature is below a specified temperature threshold."
+ ::= { lgpConditionLowTemperatureGroup 2 }
+
+ lgpConditionLowTemperatureExternalAirSensorA OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature is below the low temperature threshold for
+ external air sensor A."
+ ::= { lgpConditionLowTemperatureGroup 3 }
+
+ lgpConditionLowTemperatureExternalAirSensorB OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature is below the low temperature threshold for
+ external air sensor B."
+ ::= { lgpConditionLowTemperatureGroup 4 }
+
+ lgpConditionLowTemperatureRefrigerantSupply OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature is below the low temperature threshold for
+ the refrigerant supply."
+ ::= { lgpConditionLowTemperatureGroup 5 }
+
+ lgpConditionLowTemperatureFluidSupply OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature is below the low temperature threshold for
+ the fluid supply."
+ ::= { lgpConditionLowTemperatureGroup 6 }
+
+ lgpConditionLowTemperatureSupplyAir OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature is below the low temperature threshold for
+ the supply air."
+ ::= { lgpConditionLowTemperatureGroup 7 }
+
+lgpConditionHighHumidityGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high humidity condition. This group
+ contains various high humidity conditions."
+ ::= { lgpConditionsWellKnown 144 }
+
+ lgpConditionHighHumiditySensor1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidity has exceeded the high humidity threshold for
+ sensor 1."
+ ::= { lgpConditionHighHumidityGroup 1 }
+
+ lgpConditionHighHumidityReturnAir OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidity has exceeded the high humidity threshold for
+ the return air."
+ ::= { lgpConditionHighHumidityGroup 2 }
+
+lgpConditionLowHumidityGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low humidity condition. This group
+ contains various high humidity conditions."
+ ::= { lgpConditionsWellKnown 145 }
+
+ lgpConditionLowHumiditySensor1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidity is below the low humidity threshold for sensor 1."
+ ::= { lgpConditionLowHumidityGroup 1 }
+
+ lgpConditionLowHumidityReturnAir OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidity is below the low humidity threshold for the return
+ air."
+ ::= { lgpConditionLowHumidityGroup 2 }
+
+lgpConditionPeerNetworkNoMaster OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is unable to communicate with the master on the peer to
+ peer network."
+ ::= { lgpConditionsWellKnown 146 }
+
+lgpConditionNoOnOffPermissions OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system lacks the permissions to execute the on/off operation."
+ ::= { lgpConditionsWellKnown 147 }
+
+lgpConditionPeerNetworkFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a communication failure on the peer to
+ peer network."
+ ::= { lgpConditionsWellKnown 148 }
+
+lgpConditionUnitDisabled OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The unit is disabled."
+ ::= { lgpConditionsWellKnown 149 }
+
+lgpConditionUnitShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has shutdown."
+ ::= { lgpConditionsWellKnown 150 }
+
+lgpConditionPeerNetworkDiscovered OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has established communications on the peer to peer
+ network."
+ ::= { lgpConditionsWellKnown 151 }
+
+lgpConditionLossOfWaterFlow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of water flow condition."
+ ::= { lgpConditionsWellKnown 152 }
+
+lgpConditionCondensatePumpHighWater OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected high water in the condensate pump."
+ ::= { lgpConditionsWellKnown 153 }
+
+lgpConditionGeneralAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a general alarm condition."
+ ::= { lgpConditionsWellKnown 154 }
+
+lgpConditionProductSpecific OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a product specific condition. This condition
+ is not currently available via the agent card."
+ ::= { lgpConditionsWellKnown 155 }
+
+lgpConditionReheatLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has locked out the electrical reheat operation for a
+ specified amount of time."
+ ::= { lgpConditionsWellKnown 156 }
+
+lgpConditionHumidifierLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has locked out the humidifier operation for a
+ specified amount of time."
+ ::= { lgpConditionsWellKnown 157 }
+
+lgpConditionCompressorsLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has locked out compressor operation for a specified amount
+ of time."
+ ::= { lgpConditionsWellKnown 158 }
+
+lgpConditionCallService OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a condition that requires a service
+ representative be contacted."
+ ::= { lgpConditionsWellKnown 159 }
+
+lgpConditionLowMemoryGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains various low memory conditions."
+ ::= { lgpConditionsWellKnown 160 }
+
+ lgpConditionLowMemory1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low memory condition. The control
+ board is low in memory resources."
+ ::= { lgpConditionLowMemoryGroup 1 }
+
+lgpConditionMemoryFailureGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains various memory device failure conditions."
+ ::= { lgpConditionsWellKnown 161 }
+
+ lgpConditionMemory1Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a memory 1 module failure."
+ ::= { lgpConditionMemoryFailureGroup 1 }
+
+ lgpConditionMemory2Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a memory 2 module failure."
+ ::= { lgpConditionMemoryFailureGroup 2 }
+
+lgpConditionUnitCodeErrorGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains various memory device failure conditions."
+ ::= { lgpConditionsWellKnown 162 }
+
+ lgpConditionUnitCodeNotConfigured OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the unit code is not configured. The unit
+ code must be configured before system start-up."
+ ::= { lgpConditionUnitCodeErrorGroup 1 }
+
+ lgpConditionUnitCode01OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 2 }
+
+ lgpConditionUnitCode02OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 3 }
+
+ lgpConditionUnitCode03OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 4 }
+
+ lgpConditionUnitCode04OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 5 }
+
+ lgpConditionUnitCode05OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 6 }
+
+ lgpConditionUnitCode06OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 7 }
+
+ lgpConditionUnitCode07OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 8 }
+
+ lgpConditionUnitCode08OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 9 }
+
+ lgpConditionUnitCode09OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 10 }
+
+ lgpConditionUnitCode10OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 11 }
+
+ lgpConditionUnitCode11OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 12 }
+
+ lgpConditionUnitCode12OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 13 }
+
+ lgpConditionUnitCode13OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 14 }
+
+ lgpConditionUnitCode14OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 15 }
+
+ lgpConditionUnitCode15OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 16 }
+
+ lgpConditionUnitCode16OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 17 }
+
+ lgpConditionUnitCode17OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 18 }
+
+ lgpConditionUnitCode18OutOfRange OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a unit code error. This digit of the unit
+ code value is out of range."
+ ::= { lgpConditionUnitCodeErrorGroup 19 }
+
+lgpConditionHighExternalDewPoint OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a high external dew point condition.
+ The room dew point has exceeded the specified threshold."
+ ::= { lgpConditionsWellKnown 163 }
+
+lgpConditionHcbDisconnected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the humidifier control board is disconnected
+ or not installed."
+ ::= { lgpConditionsWellKnown 164 }
+
+lgpConditionBmsResetTimerExpired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The BMS fan speed control reset counter has timed out."
+ ::= { lgpConditionsWellKnown 165 }
+
+lgpConditionAgentFirmwareCorrupt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The firmware update to the agent card has failed and the firmware is now
+ corrupt."
+ ::= { lgpConditionsWellKnown 166 }
+
+lgpConditionSystemAccessGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains various system access conditions. An examples is
+ an open access panel."
+ ::= { lgpConditionsWellKnown 175 }
+
+ lgpConditionFrontAccessOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the front access panel/door is open."
+ ::= { lgpConditionSystemAccessGroup 1 }
+
+ lgpConditionRearAccessOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the rear access panel/door is open."
+ ::= { lgpConditionSystemAccessGroup 2 }
+
+lgpConditionsDamperFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains various damper failure conditions."
+ ::= { lgpConditionsWellKnown 176 }
+
+ lgpConditionEmergencyDamperFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an emergency damper failure. The damper is
+ in the wrong position."
+ ::= { lgpConditionsDamperFailure 1 }
+
+lgpConditionRemoteShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A remote shutdown occurred."
+ ::= { lgpConditionsWellKnown 177 }
+
+lgpConditionFireAlarm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fire Alarm."
+ ::= { lgpConditionsWellKnown 178 }
+
+lgpConditionHeatersOverheated OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Heaters Overheated."
+ ::= { lgpConditionsWellKnown 179 }
+
+lgpConditionCondenserFailureGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains condenser failure conditions."
+ ::= { lgpConditionsWellKnown 180 }
+
+ lgpConditionCondenser1Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser 1 Failure."
+ ::= { lgpConditionCondenserFailureGroup 1 }
+
+ lgpConditionCondenser2Failure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser 2 Failure."
+ ::= { lgpConditionCondenserFailureGroup 2 }
+
+ lgpConditionCondenserTVSSFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The condenser Transient Voltage Surge Suppressor or Surge
+ Protection Device has failed."
+ ::= { lgpConditionCondenserFailureGroup 3 }
+
+lgpConditionHumidifierCyclinderWorn OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected the humidifier cylinder is worn."
+ ::= { lgpConditionsWellKnown 181 }
+
+lgpConditionUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low current condition. The current of
+ one or more sources in the system has fallen below a threshold for
+ a specified amount of time. The threshold and time that triggered
+ this condition is system dependent."
+ ::= { lgpConditionsWellKnown 182 }
+
+ lgpConditionHumidifierUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a low current condition on the
+ humidifier. The current of the humidifier has fallen below
+ a pre-determined threshold for a defined amount of time."
+ ::= { lgpConditionUnderCurrent 1 }
+
+ lgpConditionInputUnderCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "There is a low current condition on the input power source. The
+ current of the input power source has fallen below a
+ pre-determined threshold for a defined amount of time."
+ ::= { lgpConditionUnderCurrent 2 }
+
+lgpConditionHeatRejectorGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains failure conditions for the heat rejection unit."
+ ::= { lgpConditionsWellKnown 183 }
+
+ lgpConditionHeatRejectorFanFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The heat rejecter fan has failed."
+ ::= { lgpConditionHeatRejectorGroup 1 }
+
+ lgpConditionHeatRejectorVoltageSuppressionFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The heat rejecter voltage suppression has failed and is no longer
+ able to protect the unit from power fluctuations."
+ ::= { lgpConditionHeatRejectorGroup 2 }
+
+lgpConditionFreeCoolLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The free cooling capability has been disabled."
+ ::= { lgpConditionsWellKnown 184 }
+
+lgpConditionWaterLeakSensorFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The sensor used to detect water leaks is not connected or has failed."
+ ::= { lgpConditionsWellKnown 185 }
+
+lgpConditionNoLoadDetectedWarning OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "There is no load detected on the output. This can be an indication
+ that the output is being powered by an external bypass source and has
+ inadvertently been left on external bypass. This warning is triggered
+ after a delay. The delay is specified by the object
+ 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output
+ current falls below a certain threshold specified by the object
+ 'lgpPwrNoLoadWarningLimit'"
+ ::= { lgpConditionsWellKnown 186 }
+
+lgpConditionFirmwareGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Grouping level for firmware related conditions."
+ ::= { lgpConditionsWellKnown 187 }
+
+ lgpConditionFirmwareUpdateRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The firmware on the system or one or more components of the
+ system must be updated. This typically indicates that one or more
+ components of the system contain corrupted firmware or the
+ firmware on one or more components are incompatible with one
+ another. When this condition is active the system may not be able
+ to function to its full capacity or may not be able to function at
+ all."
+ ::= { lgpConditionFirmwareGroup 3 }
+
+lgpConditionTestGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Objects in this group of conditions are related to testing or test
+ events. This object is never active."
+ ::= { lgpConditionsWellKnown 188 }
+
+ lgpConditionTest01 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This is a 'test' condition. It is a generic test event that can
+ be utilized to evaluate system handling of events. Some products
+ will support the activation of this event upon user request so that
+ user management stations can execute end-to-end event handling
+ tests."
+ ::= { lgpConditionTestGroup 5 }
+
+lgpConditionReceptacleBranchGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Grouping level for receptacle branch conditions."
+ ::= { lgpConditionsWellKnown 190 }
+
+ lgpConditionRcpBranchFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The receptacle branch module or control system has failed.
+ Service is required."
+ ::= { lgpConditionReceptacleBranchGroup 5 }
+
+ lgpConditionRcpBranchBreakerOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The receptacle branch breaker is open."
+ ::= { lgpConditionReceptacleBranchGroup 10 }
+
+lgpConditionInputUnqualified OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The input is not qualified to provide power to the system. This may
+ be due to system input over-voltage, system input under-voltage,
+ system input frequency out of range, or other similar issues."
+ ::= { lgpConditionsWellKnown 192 }
+
+lgpConditionBypassUnavailable OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This summary event is asserted when the bypass is not available.
+ Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass
+ Overvoltage, Bypass Undervoltage, Bypass Phase Rotation Error, or
+ other similar causes."
+ ::= { lgpConditionsWellKnown 193 }
+
+lgpConditionAutoTransferFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is failing to automatically transfer the load to the
+ alternate source."
+ ::= { lgpConditionsWellKnown 194 }
+
+lgpConditionSBSUnavailable OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A Static Bypass Switch (SBS) Failure has been detected. Possible
+ causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier)
+ Shorted, SBS Overload Exceeded, Bypass Power Supply
+ Fail, Static Bypass Switch Fuse Failure, or other similar causes."
+ ::= { lgpConditionsWellKnown 195 }
+
+lgpConditionSBSOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "On at least one phase of the static bypass switch (SBS), the power
+ dissipation limit has been exceeded."
+ ::= { lgpConditionsWellKnown 196 }
+
+lgpConditionExcessPulseParallel OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has performed too many pulse parallel operations within
+ the specified time interval. A pulse parallel operation is a
+ momentary operation of the static bypass switch (SBS) in parallel with
+ the inverter."
+ ::= { lgpConditionsWellKnown 197 }
+
+lgpConditionRemoteBypassSwitchOffExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The static bypass switch is off due to the state of an external
+ signal."
+ ::= { lgpConditionsWellKnown 198 }
+
+lgpConditionManTransferInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Manual transfer from inverter to bypass is inhibited. Bypass is not
+ qualified."
+ ::= { lgpConditionsWellKnown 199 }
+
+lgpConditionManReTransferInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Manual retransfer from bypass to inverter is inhibited."
+ ::= { lgpConditionsWellKnown 200 }
+
+lgpConditionBatteryChargeError OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery is not charging properly. Some reasons for this condition
+ include, but are not limited to: battery charger failure,
+ battery failure, etc."
+ ::= { lgpConditionsWellKnown 201 }
+
+lgpConditionBatteryAutoTestInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Automatic (scheduled) battery tests are inhibited."
+ ::= { lgpConditionsWellKnown 202 }
+
+lgpConditionBatteryChargeReducedExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A reduced battery charging algorithm is being used due to an external
+ signal."
+ ::= { lgpConditionsWellKnown 203 }
+
+lgpConditionBatteryCapacityLow OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The battery capacity is low. Some reasons for this condition include,
+ but are not limited to: a battery is offline, the battery age has
+ reduced its capabilities, etc."
+ ::= { lgpConditionsWellKnown 204 }
+
+lgpConditionBatteryTempImbalance OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The temperature difference between two batteries in the system
+ exceeds the predefined threshold."
+ ::= { lgpConditionsWellKnown 205 }
+
+lgpConditionBatteryEqualize OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The rectifier output voltage has been increased to equalize the battery
+ voltage level."
+ ::= { lgpConditionsWellKnown 206 }
+
+lgpConditionBatteryChargeInhibitedExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery charging is inhibited due to an external inhibit signal."
+ ::= { lgpConditionsWellKnown 207 }
+
+lgpConditionServiceExtBatteryMonitorGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains battery monitor service conditions."
+ ::= { lgpConditionsWellKnown 208 }
+
+ lgpConditionServiceExtBatteryMonitor1 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "External battery monitor 1 indicates battery maintenance is
+ required."
+ ::= { lgpConditionServiceExtBatteryMonitorGroup 1 }
+
+ lgpConditionServiceExtBatteryMonitor2 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "External battery monitor 2 indicates battery maintenance is
+ required."
+ ::= { lgpConditionServiceExtBatteryMonitorGroup 2 }
+
+lgpConditionBatteryGroundFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Battery system ground fault amperage exceeds the threshold."
+ ::= { lgpConditionsWellKnown 209 }
+
+lgpConditionBatteryLowShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "With the battery breaker closed, the battery voltage has dropped
+ below the calculated End-Of-Discharge (EOD) limit."
+ ::= { lgpConditionsWellKnown 210 }
+
+lgpConditionEmergencyPowerOffLocal OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an Emergency Power Off (EPO) condition.
+ The local EPO switch has cut off the power source to the system."
+ ::= { lgpConditionsWellKnown 211 }
+
+lgpConditionOutputLowPFLagging OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a lagging output power factor below the
+ threshold, resulting in reduced load capacity."
+ ::= { lgpConditionsWellKnown 212 }
+
+lgpConditionOutputLowPFLeading OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a leading output power factor below the
+ threshold, resulting in reduced load capacity."
+ ::= { lgpConditionsWellKnown 213 }
+
+lgpConditionOutputToLoadFault OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an output to load fault. This could be
+ caused by over or under voltage, or by over or under frequency."
+ ::= { lgpConditionsWellKnown 214 }
+
+lgpConditionInvRestartInhibitedExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Restart of the inverter is inhibited by an external signal."
+ ::= { lgpConditionsWellKnown 215 }
+
+lgpConditionInverterShutdownOverload OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has shutdown the inverter due to a sustained overload.
+ This event does not indicate if the load has been dropped or
+ transferred to bypass. At least one phase of the inverter power
+ dissipation limit has been exceeded."
+ ::= { lgpConditionsWellKnown 216 }
+
+lgpConditionInverterOffExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The inverter is off due to the state of an external signal."
+ ::= { lgpConditionsWellKnown 217 }
+
+lgpConditionInputContactGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an active input contact."
+ ::= { lgpConditionsWellKnown 218 }
+
+ lgpConditionInputContact01 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 1 is active."
+ ::= { lgpConditionInputContactGroup 1 }
+
+ lgpConditionInputContact02 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 2 is active."
+ ::= { lgpConditionInputContactGroup 2 }
+
+ lgpConditionInputContact03 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 3 is active."
+ ::= { lgpConditionInputContactGroup 3 }
+
+ lgpConditionInputContact04 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 4 is active."
+ ::= { lgpConditionInputContactGroup 4 }
+
+ lgpConditionInputContact05 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 5 is active."
+ ::= { lgpConditionInputContactGroup 5 }
+
+ lgpConditionInputContact06 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 6 is active."
+ ::= { lgpConditionInputContactGroup 6 }
+
+ lgpConditionInputContact07 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 7 is active."
+ ::= { lgpConditionInputContactGroup 7 }
+
+ lgpConditionInputContact08 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 8 is active."
+ ::= { lgpConditionInputContactGroup 8 }
+
+ lgpConditionInputContact09 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 9 is active."
+ ::= { lgpConditionInputContactGroup 9 }
+
+ lgpConditionInputContact10 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 10 is active."
+ ::= { lgpConditionInputContactGroup 10 }
+
+ lgpConditionInputContact11 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 11 is active."
+ ::= { lgpConditionInputContactGroup 11 }
+
+ lgpConditionInputContact12 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 12 is active."
+ ::= { lgpConditionInputContactGroup 12 }
+
+ lgpConditionInputContact13 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 13 is active."
+ ::= { lgpConditionInputContactGroup 13 }
+
+ lgpConditionInputContact14 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 14 is active."
+ ::= { lgpConditionInputContactGroup 14 }
+
+ lgpConditionInputContact15 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 15 is active."
+ ::= { lgpConditionInputContactGroup 15 }
+
+ lgpConditionInputContact16 OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that input contact 16 is active."
+ ::= { lgpConditionInputContactGroup 16 }
+
+lgpConditionRectifierOperInhibited
+ OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The operation of the rectifier is inhibited by an external signal."
+ ::= { lgpConditionsWellKnown 219 }
+
+lgpConditionBypassBackFeedBrkrOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The bypass backfeed breaker is in the open position."
+ ::= { lgpConditionsWellKnown 220 }
+
+lgpConditionAutoRestartInProgress OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Auto restart is in progress. Becomes inactive when auto restart
+ completes or fails."
+ ::= { lgpConditionsWellKnown 221 }
+
+lgpConditionAutoRestartInhibitedExt OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Auto restart is inhibited due to an external signal."
+ ::= { lgpConditionsWellKnown 222 }
+
+lgpConditionAutoRestartFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Auto restart has failed."
+ ::= { lgpConditionsWellKnown 223 }
+
+lgpConditionInputOnGenerator OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A generator is supplying the power to the system."
+ ::= { lgpConditionsWellKnown 224 }
+
+lgpConditionInputFilterCycleLock OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The input filter disconnect has opened too many times within a given
+ period of time."
+ ::= { lgpConditionsWellKnown 225 }
+
+lgpConditionServiceCodeActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system is in an operational mode intended for testing. In normal
+ operating conditions, the system should not be in this state."
+ ::= { lgpConditionsWellKnown 226 }
+
+lgpConditionLoadBusSyncActive OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Load Bus Sync Operation is active. This synchronizes the UPS output
+ with the output of another UPS."
+ ::= { lgpConditionsWellKnown 227 }
+
+lgpConditionLoadBusSyncInhibited OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected that conditions to perform Load Bus Sync
+ Operation are not satisfied."
+ ::= { lgpConditionsWellKnown 228 }
+
+lgpConditionControlsResetRequired OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A controls reset is required because one or more critical settings
+ have changed."
+ ::= { lgpConditionsWellKnown 229 }
+
+lgpConditionEquipTempSensorFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A temperature sensor is reporting a value outside the bounds of a
+ properly operating sensor."
+ ::= { lgpConditionsWellKnown 230 }
+
+lgpConditionInputCurrentImbalance OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The current on one input phase is much greater or lower than the
+ average current of all the phases. This may indicate improper operation
+ of the rectifier or input filter."
+ ::= { lgpConditionsWellKnown 231 }
+
+lgpConditionPumpGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an alarm with one of the pumps."
+ ::= { lgpConditionsWellKnown 232 }
+
+ lgpConditionPumpFlowLoss OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of flow with one or more pumps."
+ ::= { lgpConditionPumpGroup 1 }
+
+ lgpConditionPump1FlowLoss OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of flow with pump 1."
+ ::= { lgpConditionPumpFlowLoss 1 }
+
+ lgpConditionPump2FlowLoss OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a loss of flow with pump 2."
+ ::= { lgpConditionPumpFlowLoss 2 }
+
+ lgpConditionPumpShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycling of the pumps. One or more
+ of the pumps has been turned on and off a number of times within a
+ specified time period."
+ ::= { lgpConditionPumpGroup 2 }
+
+ lgpConditionPumpInverterShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycling of one or more pump
+ inverters and has temporarily locked out further pump operation
+ to protect from thermal overload. A short cycle is defined as
+ powering on and off a number of times over a set time period."
+ ::= { lgpConditionPumpGroup 3 }
+
+ lgpConditionPump1InverterShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycling of the inverter for
+ pump 1 and has temporarily locked out further pump operation
+ to protect from thermal overload. A short cycle is defined as
+ powering on and off a number of times over a set time period."
+ ::= { lgpConditionPumpInverterShortCycle 1 }
+
+ lgpConditionPump2InverterShortCycle OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a short cycling of the inverter for
+ pump 2 and has temporarily locked out further pump operation
+ to protect from thermal overload. A short cycle is defined as
+ powering on and off a number of times over a set time period."
+ ::= { lgpConditionPumpInverterShortCycle 2 }
+
+lgpConditionValveGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected an alarm with one of the valves."
+ ::= { lgpConditionsWellKnown 233 }
+
+ lgpConditionChilledWaterValvePosition OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a problem with the chilled water valve
+ position. The position of the chilled water control valve does not
+ match an expected value."
+ ::= { lgpConditionValveGroup 1 }
+
+lgpConditionCondensationDetected OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected condensation."
+ ::= { lgpConditionsWellKnown 234 }
+
+lgpConditionMaintenanceGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a maintenance condition. This group
+ contains various maintenance conditions."
+ ::= { lgpConditionsWellKnown 235 }
+
+ lgpConditionMaintenanceDue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "System is due for maintenance."
+ ::= { lgpConditionMaintenanceGroup 1 }
+
+ lgpConditionMaintenanceComplete OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system maintenance has been completed."
+ ::= { lgpConditionMaintenanceGroup 2 }
+
+lgpConditionExternalEventSignalGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains various conditions signalled by external inputs.
+ Each event is deactivated when the signal is inactive."
+ ::= { lgpConditionsWellKnown 236 }
+
+ lgpConditionExternalFireDetect OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Fire detected, as indicated by an external input signal."
+ ::= { lgpConditionExternalEventSignalGroup 1 }
+
+ lgpConditionExternalFlowLoss OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Loss of flow is detected, as indicated by an external input signal."
+ ::= { lgpConditionExternalEventSignalGroup 2 }
+
+ lgpConditionExternalReheatLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The reheater is shut down and disabled by an external input signal."
+ ::= { lgpConditionExternalEventSignalGroup 3 }
+
+ lgpConditionExternalOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A temperature has exceeded its threshold, as indicated by an
+ external input signal."
+ ::= { lgpConditionExternalEventSignalGroup 4 }
+
+ lgpConditionExternalCompLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The compressor is shut down and disabled by an external input signal."
+ ::= { lgpConditionExternalEventSignalGroup 5 }
+
+ lgpConditionExternalHumidifierLockout OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The humidifier is shut down and disabled by an external input signal."
+ ::= { lgpConditionExternalEventSignalGroup 6 }
+
+lgpConditionComponentShutdownGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains conditions signaling shutdown of various system
+ components."
+ ::= { lgpConditionsWellKnown 237 }
+
+ lgpConditionComponentShutdownPartial OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An event has occurred requiring some system components to be
+ shutdown and disabled."
+ ::= { lgpConditionComponentShutdownGroup 1 }
+
+ lgpConditionComponentShutdownHighPower OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Supply to high power components has been shutdown."
+ ::= { lgpConditionComponentShutdownGroup 2 }
+
+lgpConditionCondenserProblemGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains condenser conditions."
+ ::= { lgpConditionsWellKnown 238 }
+
+ lgpConditionCondenser1Problem OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Condenser 1 is not operating within its normal parameters."
+ ::= { lgpConditionCondenserProblemGroup 1 }
+
+lgpConditionHumidityOutOfPropBand OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The system has detected a humidity reading that remained outside of
+ the proportional control band for an extended period of time."
+ ::= { lgpConditionsWellKnown 239 }
+
+lgpConditionEnvRemoteSensorGroup OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "This group contains remote sensors."
+ ::= { lgpConditionsWellKnown 240 }
+
+ lgpConditionEnvRemoteSensor1Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 1 }
+
+ lgpConditionEnvRemoteSensor2Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 2 }
+
+ lgpConditionEnvRemoteSensor3Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 3 }
+
+ lgpConditionEnvRemoteSensor4Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 4 }
+
+ lgpConditionEnvRemoteSensor5Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 5 }
+
+ lgpConditionEnvRemoteSensor6Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 6 }
+
+ lgpConditionEnvRemoteSensor7Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 7 }
+
+ lgpConditionEnvRemoteSensor8Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 8 }
+
+ lgpConditionEnvRemoteSensor9Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 9 }
+
+ lgpConditionEnvRemoteSensor10Issue OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Remote sensor is disconnected or the signal is out of range. The
+ event is deactivated when sensor signal is re-established."
+ ::= { lgpConditionEnvRemoteSensorGroup 10 }
+
+lgpConditionNeutralSnubberBoardCommFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The Neutral Snubber board has stopped communicating."
+ ::= { lgpConditionsWellKnown 241 }
+
+lgpConditionRedundantChargerFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The redundant charger has failed."
+ ::= { lgpConditionsWellKnown 242 }
+
+lgpConditionBoardInputContactorPowerFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Board input contactor power failure."
+ ::= { lgpConditionsWellKnown 243 }
+
+ lgpConditionBoard1InputContactorPowerFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Board1 input contactor power failure."
+ ::= { lgpConditionBoardInputContactorPowerFailure 1 }
+
+ lgpConditionBoard2InputContactorPowerFailure OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Board2 input contactor power failure."
+ ::= { lgpConditionBoardInputContactorPowerFailure 2 }
+
+lgpConditionTooManySensors OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The number of sensors installed on the device has exceeded the
+ pre-determined limit."
+ ::= { lgpConditionsWellKnown 5423 }
+
+lgpConditionDoorSwitchOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An open door has been detected."
+ ::= { lgpConditionsWellKnown 5471 }
+
+lgpConditionContactClosureOpen OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "An open circuit has been detected."
+ ::= { lgpConditionsWellKnown 5479 }
+
+lgpConditionContactClosureClosed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "A closed circuit has been detected."
+ ::= { lgpConditionsWellKnown 5480 }
+
+lgpConditionSensorsNotDisplayed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "The number of sensors that can be displayed (monitored) on the
+ device has exceeded the pre-determined limit. Note this condition
+ differs from the lgpConditionTooManySensors in that the system may
+ currently have less than the maximum of installed sensors present but
+ one or more of those sensors can not be displayed because the display
+ order table (lgpPduAuxMeasOrderTable) contains entries for sensors
+ that are not currently installed. This condition effectively
+ prevents one or more installed sensors from being presented in the
+ lgpPduAuxMeasTable. It is possible for both this condition and the
+ lgpConditionTooManySensors condition to be active at the same time."
+ ::= { lgpConditionsWellKnown 6119 }
+