summaryrefslogtreecommitdiff
path: root/MIBS/jacarta/InterSeptor-MIB
diff options
context:
space:
mode:
authorDavid Leutgeb <david.leutgeb@mannundmouse.com>2023-12-05 12:25:34 +0100
committerDavid Leutgeb <david.leutgeb@mannundmouse.com>2023-12-05 12:25:34 +0100
commit98a672123c7872f6b9b75a9a2b6bb3aea504de6a (patch)
tree9b13bd7f563c3198047bd359195327cf28b3caf0 /MIBS/jacarta/InterSeptor-MIB
downloadmibs-98a672123c7872f6b9b75a9a2b6bb3aea504de6a.tar.gz
mibs-98a672123c7872f6b9b75a9a2b6bb3aea504de6a.zip
Initial commitHEADmain
Diffstat (limited to 'MIBS/jacarta/InterSeptor-MIB')
-rw-r--r--MIBS/jacarta/InterSeptor-MIB1580
1 files changed, 1580 insertions, 0 deletions
diff --git a/MIBS/jacarta/InterSeptor-MIB b/MIBS/jacarta/InterSeptor-MIB
new file mode 100644
index 0000000..fe255f4
--- /dev/null
+++ b/MIBS/jacarta/InterSeptor-MIB
@@ -0,0 +1,1580 @@
+-- Jacarta interSeptor MIB
+-- MIB for interSeptor Environmental Monitoring System
+--
+-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) jacarta(19011)
+-- product(1) webAppliance(3) inSept(1)
+-- ==============================================================================================
+---
+--- Revision History
+---
+--- V1.00 - Initial Release - July 03
+--- V1.01 - Minor SNMP bug fix - Aug 03
+--- v1.10 - Add temperature unit object - Oct, 15 2004
+--- Add date format object
+--- Add inSeptConfigAccessControlTable
+--- Add object
+--- v1.11 Change interSeptor-MIB to InterSeptor-MIB - Dec, 20 2004
+--- Updated InSeptsensorConfigSensorEntry and SensorMonitorSensorEntry
+--- V1.12 - Modified syntax error - May, 10 2005
+--- Fixed SYNTAX InSeptConfigTrapsReceiversEntry
+--- Changed SYNTAX inSeptConfigTrapsReceiversEntry to SYNTAX InSeptConfigTrapsReceiversEntry
+--- V1.13 - Modified syntax error - June, 27 2006
+--- Check error form http://wwwsnmp.cs.utwente.nl/ietf/mibs/validate/
+--- ===========================================================================================
+InterSeptor-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ enterprises
+ FROM RFC1155-SMI
+ OBJECT-TYPE
+ FROM RFC-1212
+ DisplayString
+ FROM RFC1213-MIB
+ TRAP-TYPE
+ FROM RFC-1215;
+
+jacarta OBJECT IDENTIFIER ::= { enterprises 19011 }
+product OBJECT IDENTIFIER ::= { jacarta 1 }
+webAppliance OBJECT IDENTIFIER ::= { product 3 }
+inSept OBJECT IDENTIFIER ::= { webAppliance 1}
+inSeptObjects OBJECT IDENTIFIER ::= { inSept 1 }
+inSeptTraps OBJECT IDENTIFIER ::= { inSept 2 }
+
+inSeptIdent OBJECT IDENTIFIER ::= { inSeptObjects 1 }
+inSeptConfig OBJECT IDENTIFIER ::= { inSeptObjects 2 }
+inSeptsensorMonitor OBJECT IDENTIFIER ::= { inSeptObjects 3 }
+inSeptsensorConfig OBJECT IDENTIFIER ::= { inSeptObjects 4 }
+
+-- ===========================================================================
+--
+-- inSeptIdentification
+--
+-- All objects in this group except for inSeptIdentName and
+-- inSeptIdentAttachedDevices are set at device initialization
+-- and remain static.
+--
+-- ===========================================================================
+
+inSeptIdentManufacturer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..31))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the interSeptor manufacturer."
+ ::= { inSeptIdent 1 }
+
+inSeptIdentModel OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..63))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The interSeptor Model designation."
+ ::= { inSeptIdent 2 }
+
+inSeptIdentAgentSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..31))
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The interSeptor software/firmware version."
+ ::= { inSeptIdent 3 }
+
+inSeptIdentName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "A string identifying the interSeptor. This object should be
+ set by the administrator."
+ ::= { inSeptIdent 4 }
+
+-- ===========================================================================
+--
+-- inSeptConfig
+--
+-- ===========================================================================
+
+inSeptConfigMibVersion OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The version of MIB spec."
+ ::= { inSeptConfig 1}
+
+inSeptConfigNetwork OBJECT IDENTIFIER ::= { inSeptConfig 2 }
+
+inSeptConfigIpAddress OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The ip address that NMS can identify the managed
+ device"
+ ::= { inSeptConfigNetwork 1 }
+
+inSeptConfigGateway OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The default gateway that allows the device to be managed
+ through routers "
+ ::= { inSeptConfigNetwork 2 }
+
+inSeptConfigSubnetMask OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " Internet address subnet mask"
+ ::= { inSeptConfigNetwork 3 }
+
+inSeptConfigDateTime OBJECT IDENTIFIER ::= { inSeptConfig 3 }
+
+inSeptConfigDate OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (10..10))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The date in inSept, format is (dd/mm/yyyy)"
+ ::= { inSeptConfigDateTime 1}
+
+inSeptConfigTime OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (8..8))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time in interSeptor, format is (hh:mm:ss)"
+ ::= { inSeptConfigDateTime 2}
+
+inSeptConfigTimeFromNtp OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable update date/time from NTP server."
+ ::= { inSeptConfigDateTime 3}
+
+inSeptConfigNtpIpAddress OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "NTP IP address."
+ ::= { inSeptConfigDateTime 4}
+
+inSeptConfigNtpTimeZone OBJECT-TYPE
+ SYNTAX INTEGER {
+ gMT-1200(1),
+ gMT-1100(2),
+ gMT-1000(3),
+ gMT-0900(4),
+ gMT-0800(5),
+ gMT-0700(6),
+ gMT-0600(7),
+ gMT-0500(8),
+ gMT-0400(9),
+ gMT-0330(10),
+ gMT-0300(11),
+ gMT-0200(12),
+ gMT-0100(13),
+ gMT-0000(14),
+ gMT0100(15),
+ gMT0200(16),
+ gMT0300(17),
+ gMT0330(18),
+ gMT0400(19),
+ gMT0500(20),
+ gMT0530(21),
+ gMT0600(22),
+ gMT0700(23),
+ gMT0800(24),
+ gMT0900(25),
+ gMT1000(26),
+ gMT1100(27),
+ gMT1200(28)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable update date/time from NTP server."
+ ::= { inSeptConfigDateTime 5}
+
+inSeptConfigDayLightSaving OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable daylight saving for NTP time, if enabled, the time get from NTP will be set
+ set one hour in advance to reflect daylight saving status."
+ ::= { inSeptConfigDateTime 6}
+
+inSeptConfigLog OBJECT IDENTIFIER ::= { inSeptConfig 4 }
+
+inSeptConfigHistoryLogFrequency OBJECT-TYPE
+ SYNTAX INTEGER (5..3600) -- in seconds
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency of the update of the history log. The value
+ is in seconds"
+ ::= { inSeptConfigLog 1}
+
+inSeptConfigExtHistoryLogFrequency OBJECT-TYPE
+ SYNTAX INTEGER (1..1440) -- in minutes
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The frequency of the update of the extended history log.
+ The value is in seconds"
+ ::= { inSeptConfigLog 2}
+
+inSeptConfigConfigurationLog OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " Enable/disable inSept to log parameter change."
+ ::= { inSeptConfigLog 3}
+
+inSeptConfigDhcpStatue OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable DHCP/BootP capability"
+ ::= { inSeptConfig 5}
+
+inSeptConfigPingStatue OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable Ping Echo capability"
+ ::= { inSeptConfig 6}
+
+inSeptConfigTftpStatue OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable TFTP network upgrade capability"
+ ::= { inSeptConfig 7}
+
+inSeptConfigTelnet OBJECT IDENTIFIER ::= { inSeptConfig 8 }
+
+inSeptConfigTelnetStatue OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable telnet access"
+ ::= { inSeptConfigTelnet 1}
+
+inSeptConfigTelnetPortNumber OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting the server port of telnet."
+ ::= { inSeptConfigTelnet 2}
+
+inSeptConfigHttp OBJECT IDENTIFIER ::= { inSeptConfig 9 }
+
+inSeptConfigHttpStatue OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable HTTP access"
+ ::= { inSeptConfigHttp 1}
+
+inSeptConfigHttpPortNumber OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting the server port of HTTP."
+ ::= { inSeptConfigHttp 2}
+
+inSeptConfigHttpSecurity OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable HTTP access for read-only users"
+ ::= { inSeptConfigHttp 3}
+
+
+inSeptConfigSnmp OBJECT IDENTIFIER ::= { inSeptConfig 10 }
+inSeptConfigSnmpStatue OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable or disable SNMP access"
+ ::= { inSeptConfigSnmp 1}
+
+inSeptConfigSnmpPortNumber OBJECT-TYPE
+ SYNTAX INTEGER (1..65535)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setting the server port of SNMP."
+ ::= { inSeptConfigSnmp 2}
+
+inSeptConfigControl OBJECT IDENTIFIER ::= { inSeptConfig 11 }
+inSeptConfigResetToDefault OBJECT-TYPE
+ SYNTAX INTEGER {
+ reset(1),
+ nothing(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Reset all parameters of interSeptor to default value"
+ ::= { inSeptConfigControl 1}
+
+inSeptConfigRestart OBJECT-TYPE
+ SYNTAX INTEGER {
+ restart(1),
+ nothing(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Restart interSeptor"
+ ::= { inSeptConfigControl 2}
+
+inSeptConfigTrap OBJECT IDENTIFIER ::= { inSeptConfig 12 }
+inSeptConfigTrapRetryCount OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The count of repeat traps to send to NMS before trap
+ acknowledgement is received."
+ ::= { inSeptConfigTrap 1}
+
+inSeptConfigTrapRetryTime OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The time between retrying to send traps to NMS."
+ ::= { inSeptConfigTrap 2}
+
+inSeptConfigTrapAckSignature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The signature of trap acknowledgement."
+ ::= { inSeptConfigTrap 3}
+
+
+inSeptConfigPollRate OBJECT-TYPE
+ SYNTAX INTEGER (3..60)
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ " The frequency that interSeptor updates readings from sensors
+ (unit : second)."
+ ::= { inSeptConfig 13}
+
+inSeptConfigTrapsReceiversTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF InSeptConfigTrapsReceiversEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of managers to send traps to. The number of
+ entries is given by the value of inSeptConfigNumTrapReceivers"
+ ::= { inSeptConfig 14}
+
+inSeptConfigTrapsReceiversEntry OBJECT-TYPE
+ SYNTAX InSeptConfigTrapsReceiversEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The managers to send traps to."
+ INDEX { inSepttrapsIndex}
+ ::= { inSeptConfigTrapsReceiversTable 1 }
+
+InSeptConfigTrapsReceiversEntry ::=
+ SEQUENCE {
+ inSepttrapsIndex
+ INTEGER,
+ inSepttrapsReceiverAddr
+ IpAddress,
+ inSeptreceiverCommunityString
+ DisplayString,
+ inSeptreceiverSeverityLevel
+ INTEGER,
+ inSeptreceiverDescription
+ DisplayString
+ }
+
+inSepttrapsIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to a trap receiver entry."
+ ::= { inSeptConfigTrapsReceiversEntry 1 }
+
+inSepttrapsReceiverAddr OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The IP address of the manager to send a trap to."
+ ::= { inSeptConfigTrapsReceiversEntry 2 }
+
+inSeptreceiverCommunityString OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..19))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The community name to use in the trap when
+ sent to the manager."
+ ::= { inSeptConfigTrapsReceiversEntry 3 }
+
+inSeptreceiverSeverityLevel OBJECT-TYPE
+ SYNTAX INTEGER {
+ informational(1),
+ warning(2),
+ severe(3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The severity level of traps to be received by this manager."
+ ::= { inSeptConfigTrapsReceiversEntry 4 }
+
+inSeptreceiverDescription OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..31))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Description of trap receivers"
+ ::= { inSeptConfigTrapsReceiversEntry 5 }
+
+inSeptConfigAccessControlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF InSeptConfigAccessControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of managers which can access interSeptor with private
+ community string."
+ ::= { inSeptConfig 15}
+
+inSeptConfigAccessControlEntry OBJECT-TYPE
+ SYNTAX InSeptConfigAccessControlEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The managers."
+ INDEX { accessIndex}
+ ::= { inSeptConfigAccessControlTable 1 }
+
+InSeptConfigAccessControlEntry ::=
+ SEQUENCE {
+ accessIndex
+ INTEGER,
+ accessControlAddr
+ IpAddress,
+ accessCommunityString
+ DisplayString,
+ accessControlMode
+ INTEGER
+ }
+
+accessIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to a access control entry."
+ ::= { inSeptConfigAccessControlEntry 1 }
+
+accessControlAddr OBJECT-TYPE
+ SYNTAX IpAddress
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The IP address of the manager to access interSeptor"
+ ::= { inSeptConfigAccessControlEntry 2 }
+
+accessCommunityString OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..19))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The community name to use in the manager when
+ access interSeptor"
+ ::= { inSeptConfigAccessControlEntry 3 }
+
+accessControlMode OBJECT-TYPE
+ SYNTAX INTEGER {
+ readOnly (1),
+ read-write (2),
+ notAccess (3)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Access type, only read/Write access type can change parameter
+ of interSeptor"
+ ::= { inSeptConfigAccessControlEntry 4 }
+
+
+inSeptConfigTemperatureUnit OBJECT-TYPE
+ SYNTAX INTEGER {
+ celsius(1),
+ fahrenheit(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature unit of the system, can be Celsius or Farenheit"
+ ::= { inSeptConfig 16}
+
+inSeptConfigDateFormat OBJECT-TYPE
+ SYNTAX INTEGER {
+ dd-mm-yyyy(1),
+ mm-dd-yyyy(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy"
+ ::= { inSeptConfig 17}
+
+
+-- Sensor Monitoring
+
+inSeptsensorMonitorSensorNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of sensors that can be monitored."
+ ::= { inSeptsensorMonitor 1}
+
+inSeptsensorMonitorSensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SensorMonitorSensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of sensor devices to be monitored."
+ ::= { inSeptsensorMonitor 2}
+
+inSeptsensorMonitorSensorEntry OBJECT-TYPE
+ SYNTAX SensorMonitorSensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor device."
+ INDEX { inSeptsensorMonitorDeviceIndex}
+ ::= { inSeptsensorMonitorSensorTable 1 }
+
+SensorMonitorSensorEntry ::=
+ SEQUENCE {
+ inSeptsensorMonitorDeviceIndex
+ INTEGER,
+ inSeptsensorMonitorDeviceStatus
+ INTEGER,
+ inSeptsensorMonitorDeviceTemperature
+ INTEGER,
+ inSeptsensorMonitorDeviceTemperatureAlarm
+ INTEGER,
+ inSeptsensorMonitorDeviceHumidity
+ INTEGER,
+ inSeptsensorMonitorDeviceHumidityAlarm
+ INTEGER,
+ inSeptsensorMonitorAlarm1
+ INTEGER,
+ inSeptsensorMonitorAlarm2
+ INTEGER
+ }
+
+inSeptsensorMonitorDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to a sensor device entry."
+ ::= { inSeptsensorMonitorSensorEntry 1 }
+
+inSeptsensorMonitorDeviceStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ disabled(2),
+ eMD-HT(3),
+ eMD-T(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The device type connected to interSeptor."
+ ::= { inSeptsensorMonitorSensorEntry 2 }
+
+inSeptsensorMonitorDeviceTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature of sensor on device interSeptor, the unit is 0.1 degree."
+ ::= { inSeptsensorMonitorSensorEntry 3 }
+
+inSeptsensorMonitorDeviceTemperatureAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ disabled(2),
+ normal(3),
+ lowWarning(4),
+ lowCritical(5),
+ highWarning(6),
+ highCritical(7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm type of sensor on device interSeptor."
+ ::= { inSeptsensorMonitorSensorEntry 4 }
+
+inSeptsensorMonitorDeviceHumidity OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity of sensor on device interSeptor, the unit is 0.1%."
+ ::= { inSeptsensorMonitorSensorEntry 5 }
+
+inSeptsensorMonitorDeviceHumidityAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ disabled(2),
+ normal(3),
+ lowWarning(4),
+ lowCritical(5),
+ highWarning(6),
+ highCritical(7)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The alarm type of sensor on device interSeptor."
+ ::= { inSeptsensorMonitorSensorEntry 6 }
+
+inSeptsensorMonitorAlarm1 OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ disabled(2),
+ active(3),
+ inactive(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The device status of sensor 1 connected to interSeptor."
+ ::= { inSeptsensorMonitorSensorEntry 7 }
+
+inSeptsensorMonitorAlarm2 OBJECT-TYPE
+ SYNTAX INTEGER {
+ unknown(1),
+ disabled(2),
+ active(3),
+ inactive(4)
+ }
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The device status of sensor 2 connected to interSeptor."
+ ::= { inSeptsensorMonitorSensorEntry 8 }
+
+-- Sensor Configuration
+
+inSeptsensorConfigSensorNumber OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The number of sensors that are connected to interSeptor."
+ ::= { inSeptsensorConfig 1 }
+
+inSeptsensorConfigSensorTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF InSeptsensorConfigSensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "A list of sensor devices to be configured."
+ ::= { inSeptsensorConfig 2 }
+
+inSeptsensorConfigSensorEntry OBJECT-TYPE
+ SYNTAX InSeptsensorConfigSensorEntry
+ ACCESS not-accessible
+ STATUS mandatory
+ DESCRIPTION
+ "The sensor device."
+ INDEX { inSeptsensorConfigDeviceIndex }
+ ::= { inSeptsensorConfigSensorTable 1 }
+
+InSeptsensorConfigSensorEntry ::=
+ SEQUENCE {
+ inSeptsensorConfigDeviceIndex
+ INTEGER,
+ inSeptsensorConfigDeviceName
+ DisplayString,
+ inSeptsensorConfigDeviceState
+ INTEGER
+ }
+
+inSeptsensorConfigDeviceIndex OBJECT-TYPE
+ SYNTAX INTEGER (1..2147483647)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION
+ "The index to a sensor device entry."
+ ::= { inSeptsensorConfigSensorEntry 1 }
+
+inSeptsensorConfigDeviceName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of the sensor device for identification."
+ ::= { inSeptsensorConfigSensorEntry 2 }
+
+inSeptsensorConfigDeviceState OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ auto(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The setup of sensor device type."
+ ::= { inSeptsensorConfigSensorEntry 3 }
+
+inSeptsensorConfigSensor1 OBJECT IDENTIFIER ::= { inSeptsensorConfig 3 }
+
+inSeptsensorConfigSensor1DeviceName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of sensor device."
+ ::= { inSeptsensorConfigSensor1 1}
+
+inSeptsensorConfigSensor1DeviceState OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ auto(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The setup of sensor device type."
+ ::= { inSeptsensorConfigSensor1 2 }
+
+inSeptsensorConfigSensor1Temperature OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 3 }
+
+inSeptsensorConfigSensor1TemperatureName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature sensor name."
+ ::= { inSeptsensorConfigSensor1Temperature 1 }
+
+inSeptsensorConfigSensor1TemperatureLowWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set point to trigger low warning alarm."
+ ::= { inSeptsensorConfigSensor1Temperature 2 }
+
+
+inSeptsensorConfigSensor1TemperatureLowCritical OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger low critical alarm."
+ ::= { inSeptsensorConfigSensor1Temperature 3 }
+
+inSeptsensorConfigSensor1TemperatureHighWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger high warning alarm."
+ ::= { inSeptsensorConfigSensor1Temperature 4 }
+
+inSeptsensorConfigSensor1TemperatureHighCritical OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger high critical alarm."
+ ::= { inSeptsensorConfigSensor1Temperature 5 }
+
+inSeptsensorConfigSensor1TemperatureHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to prevent too many alarms when temperature is hovering around the
+ set threshold."
+ ::= { inSeptsensorConfigSensor1Temperature 6 }
+
+inSeptsensorConfigSensor1TemperatureCalibration OBJECT-TYPE
+ SYNTAX INTEGER {
+ temperatureIncrease0Point0(1),
+ temperatureIncrease0Point5(2),
+ temperatureIncrease1Point0(3),
+ temperatureIncrease1Point5(4),
+ temperatureIncrease2Point0(5),
+ temperatureIncrease2Point5(6),
+ temperatureIncrease3Point0(7),
+ temperatureMinus0Point5(8),
+ temperatureMinus1Point0(9),
+ temperatureMinus1Point5(10),
+ temperatureMinus2Point0(11),
+ temperatureMinus2Point5(12),
+ temperatureMinusPoint0(13)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to get the correct temperature according to your reference temperature."
+ ::= { inSeptsensorConfigSensor1Temperature 7 }
+
+inSeptsensorConfigSensor1TemperatureLowWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger low warning alarm."
+ ::= { inSeptsensorConfigSensor1Temperature 8 }
+
+inSeptsensorConfigSensor1TemperatureLowCriticalStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger low critical alarm."
+ ::= { inSeptsensorConfigSensor1Temperature 9 }
+
+inSeptsensorConfigSensor1TemperatureHighWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger high warning alarm."
+ ::= { inSeptsensorConfigSensor1Temperature 10 }
+
+inSeptsensorConfigSensor1TemperatureHighCriticalStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger high critical alarm."
+ ::= { inSeptsensorConfigSensor1Temperature 11 }
+
+inSeptsensorConfigSensor1Humidity OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 4 }
+
+inSeptsensorConfigSensor1HumdityName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity sensor name."
+ ::= { inSeptsensorConfigSensor1Humidity 1 }
+
+inSeptsensorConfigSensor1HumidityLowWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set point to trigger low warning alarm."
+ ::= { inSeptsensorConfigSensor1Humidity 2 }
+
+
+inSeptsensorConfigSensor1HumidityLowCritical OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshole to trigger low critical alarm."
+ ::= { inSeptsensorConfigSensor1Humidity 3 }
+
+inSeptsensorConfigSensor1HumidityHighWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger high warning alarm."
+ ::= { inSeptsensorConfigSensor1Humidity 4 }
+
+inSeptsensorConfigSensor1HumidityHighCritical OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger high critical alarm."
+ ::= { inSeptsensorConfigSensor1Humidity 5 }
+
+inSeptsensorConfigSensor1HumidityHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to prevent too many alarms when Humidity is hovering around the
+ set threshold."
+ ::= { inSeptsensorConfigSensor1Humidity 6 }
+
+inSeptsensorConfigSensor1HumidityCalibration OBJECT-TYPE
+ SYNTAX INTEGER {
+ humidityIncrease0Point0(1),
+ humidityIncrease1Point0(2),
+ humidityIncrease2Point0(3),
+ humidityIncrease3Point0(4),
+ humidityIncrease4Point0(5),
+ humidityIncrease5Point0(6),
+ humidityIncrease6Point0(7),
+ humidityMinus1Point0(8),
+ humidityMinus2Point0(9),
+ humidityMinus3Point0(10),
+ humidityMinus4Point0(11),
+ humidityMinus5Point0(12),
+ humidityMinus6Point0(13)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to get the correct temperature according to your reference temperature."
+ ::= { inSeptsensorConfigSensor1Humidity 7 }
+
+inSeptsensorConfigSensor1HumidityLowWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger low warning alarm."
+ ::= { inSeptsensorConfigSensor1Humidity 8 }
+
+inSeptsensorConfigSensor1HumidityLowCriticalStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger low critical alarm."
+ ::= { inSeptsensorConfigSensor1Humidity 9 }
+
+inSeptsensorConfigSensor1HumidityHighWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger high warning alarm."
+ ::= { inSeptsensorConfigSensor1Humidity 10 }
+
+inSeptsensorConfigSensor1HumidityHighCriticalStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger high critical alarm."
+ ::= { inSeptsensorConfigSensor1Humidity 11 }
+
+inSeptsensorConfigSensor1Alarm1 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 5 }
+
+inSeptsensorConfigSensor1Alarm1Name OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of alarm-1."
+ ::= { inSeptsensorConfigSensor1Alarm1 1 }
+
+inSeptsensorConfigSensor1Alarm1State OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ normalOpen(2),
+ normalClose(3),
+ highActive(4),
+ lowActive(5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup the signal type to trigger alarm."
+ ::= { inSeptsensorConfigSensor1Alarm1 2 }
+
+inSeptsensorConfigSensor1Alarm1Hysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to delay the alarm triggered when event occurs."
+ ::= { inSeptsensorConfigSensor1Alarm1 3 }
+
+inSeptsensorConfigSensor1Alarm2 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 6 }
+
+inSeptsensorConfigSensor1Alarm2Name OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of alarm-1."
+ ::= { inSeptsensorConfigSensor1Alarm2 1 }
+
+inSeptsensorConfigSensor1Alarm2State OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ normalOpen(2),
+ normalClose(3),
+ highActive(4),
+ lowActive(5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup the signal type to trigger alarm."
+ ::= { inSeptsensorConfigSensor1Alarm2 2 }
+
+inSeptsensorConfigSensor1Alarm2Hysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to delay the alarm triggered when event occurs."
+ ::= { inSeptsensorConfigSensor1Alarm2 3 }
+
+inSeptsensorConfigSensor2 OBJECT IDENTIFIER ::= { inSeptsensorConfig 4 }
+
+inSeptsensorConfigSensor2DeviceName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of sensor device."
+ ::= { inSeptsensorConfigSensor2 1}
+
+inSeptsensorConfigSensor2DeviceState OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ auto(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The setup of sensor device type."
+ ::= { inSeptsensorConfigSensor2 2 }
+
+inSeptsensorConfigSensor2Temperature OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 3 }
+
+inSeptsensorConfigSensor2TemperatureName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The temperature sensor name."
+ ::= { inSeptsensorConfigSensor2Temperature 1 }
+
+inSeptsensorConfigSensor2TemperatureLowWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set point to trigger low warning alarm."
+ ::= { inSeptsensorConfigSensor2Temperature 2 }
+
+
+inSeptsensorConfigSensor2TemperatureLowCritical OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger low critical alarm."
+ ::= { inSeptsensorConfigSensor2Temperature 3 }
+
+inSeptsensorConfigSensor2TemperatureHighWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger high warning alarm."
+ ::= { inSeptsensorConfigSensor2Temperature 4 }
+
+inSeptsensorConfigSensor2TemperatureHighCritical OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger high critical alarm."
+ ::= { inSeptsensorConfigSensor2Temperature 5 }
+
+inSeptsensorConfigSensor2TemperatureHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to prevent too many alarms when temperature is hovering around the
+ set threshold."
+ ::= { inSeptsensorConfigSensor2Temperature 6 }
+
+inSeptsensorConfigSensor2TemperatureCalibration OBJECT-TYPE
+ SYNTAX INTEGER {
+ temperatureIncrease0Point0(1),
+ temperatureIncrease0Point5(2),
+ temperatureIncrease1Point0(3),
+ temperatureIncrease1Point5(4),
+ temperatureIncrease2Point0(5),
+ temperatureIncrease2Point5(6),
+ temperatureIncrease3Point0(7),
+ temperatureMinus0Point5(8),
+ temperatureMinus1Point0(9),
+ temperatureMinus1Point5(10),
+ temperatureMinus2Point0(11),
+ temperatureMinus2Point5(12),
+ temperatureMinusPoint0(13)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to get the correct temperature according to your reference temperature."
+ ::= { inSeptsensorConfigSensor2Temperature 7 }
+
+inSeptsensorConfigSensor2TemperatureLowWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger low warning alarm."
+ ::= { inSeptsensorConfigSensor2Temperature 8 }
+
+inSeptsensorConfigSensor2TemperatureLowCriticalStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger low critical alarm."
+ ::= { inSeptsensorConfigSensor2Temperature 9 }
+
+inSeptsensorConfigSensor2TemperatureHighWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger high warning alarm."
+ ::= { inSeptsensorConfigSensor2Temperature 10 }
+
+inSeptsensorConfigSensor2TemperatureHighCriticalStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger high critical alarm."
+ ::= { inSeptsensorConfigSensor2Temperature 11 }
+
+inSeptsensorConfigSensor2Humidity OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 4 }
+
+inSeptsensorConfigSensor2HumdityName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The humidity sensor name."
+ ::= { inSeptsensorConfigSensor2Humidity 1 }
+
+inSeptsensorConfigSensor2HumidityLowWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set point to trigger low warning alarm."
+ ::= { inSeptsensorConfigSensor2Humidity 2 }
+
+
+inSeptsensorConfigSensor2HumidityLowCritical OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger low critical alarm."
+ ::= { inSeptsensorConfigSensor2Humidity 3 }
+
+inSeptsensorConfigSensor2HumidityHighWarning OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger high warning alarm."
+ ::= { inSeptsensorConfigSensor2Humidity 4 }
+
+inSeptsensorConfigSensor2HumidityHighCritical OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The threshold to trigger high critical alarm."
+ ::= { inSeptsensorConfigSensor2Humidity 5 }
+
+inSeptsensorConfigSensor2HumidityHysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to prevent too many alarms when Humidity is hovering around the
+ set threshold."
+ ::= { inSeptsensorConfigSensor2Humidity 6 }
+
+inSeptsensorConfigSensor2HumidityCalibration OBJECT-TYPE
+ SYNTAX INTEGER {
+ humidityIncrease0Point0(1),
+ humidityIncrease1Point0(2),
+ humidityIncrease2Point0(3),
+ humidityIncrease3Point0(4),
+ humidityIncrease4Point0(5),
+ humidityIncrease5Point0(6),
+ humidityIncrease6Point0(7),
+ humidityMinus1Point0(8),
+ humidityMinus2Point0(9),
+ humidityMinus3Point0(10),
+ humidityMinus4Point0(11),
+ humidityMinus5Point0(12),
+ humidityMinus6Point0(13)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to get the correct temperature according to your reference temperature."
+ ::= { inSeptsensorConfigSensor2Humidity 7 }
+
+inSeptsensorConfigSensor2HumidityLowWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger low warning alarm."
+ ::= { inSeptsensorConfigSensor2Humidity 8 }
+
+inSeptsensorConfigSensor2HumidityLowCriticalStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger low critical alarm."
+ ::= { inSeptsensorConfigSensor2Humidity 9 }
+
+inSeptsensorConfigSensor2HumidityHighWarningStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger high warning alarm."
+ ::= { inSeptsensorConfigSensor2Humidity 10 }
+
+inSeptsensorConfigSensor2HumidityHighCriticalStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ enabled(1),
+ disabled(2)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Enable/disable the set point to trigger high critical alarm."
+ ::= { inSeptsensorConfigSensor2Humidity 11 }
+
+inSeptsensorConfigSensor2Alarm1 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 5 }
+
+inSeptsensorConfigSensor2Alarm1Name OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of alarm-1."
+ ::= { inSeptsensorConfigSensor2Alarm1 1 }
+
+inSeptsensorConfigSensor2Alarm1State OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ normalOpen(2),
+ normalClose(3),
+ highActive(4),
+ lowActive(5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup the signal type to trigger alarm."
+ ::= { inSeptsensorConfigSensor2Alarm1 2 }
+
+inSeptsensorConfigSensor2Alarm1Hysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to delay the alarm triggered when event occurs."
+ ::= { inSeptsensorConfigSensor2Alarm1 3 }
+
+inSeptsensorConfigSensor2Alarm2 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 6 }
+
+inSeptsensorConfigSensor2Alarm2Name OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The name of alarm-1."
+ ::= { inSeptsensorConfigSensor2Alarm2 1 }
+
+inSeptsensorConfigSensor2Alarm2State OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(1),
+ normalOpen(2),
+ normalClose(3),
+ highActive(4),
+ lowActive(5)
+ }
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "Setup the signal type to trigger alarm."
+ ::= { inSeptsensorConfigSensor2Alarm2 2 }
+
+inSeptsensorConfigSensor2Alarm2Hysteresis OBJECT-TYPE
+ SYNTAX INTEGER
+ ACCESS read-write
+ STATUS mandatory
+ DESCRIPTION
+ "The set value to delay the alarm triggered when event occurs."
+ ::= { inSeptsensorConfigSensor2Alarm2 3 }
+
+
+-- ===========================================================================
+-- inSeptTraps
+--
+-- Traps group
+-- ===========================================================================
+-- This section defines the well-known notifications sent by
+-- inSept agents.
+-- Care must be taken to ensure that no particular notification
+-- is sent to a single receiving entity more often than once
+-- every five seconds.
+
+inSeptCommunicationRestored TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: Communication between interSeptor and sensor has been
+ established."
+ ::= 1
+
+inSeptCommunicationLost TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "WARNING: Communication between interSeptor and sensor has been
+ lost."
+ ::= 2
+
+inSeptAlarm1Inactive TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: Alarm1 of sensor has returned from active state."
+ ::= 3
+
+inSeptAlarm1Active TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "WARNING: Alarm1 has become active."
+ ::= 4
+
+inSeptAlarm2Inactive TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: Alarm2 of sensor has returned from active state."
+ ::= 5
+
+inSeptAlarm2Active TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "WARNING: Alarm2 has become active."
+ ::= 6
+
+inSeptTemperatureNotHighWarning TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: The temperature of sensor has returned from High warning to normal."
+ ::= 7
+
+inSeptTemperatureHighWarning TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "WARNING: The temperature of sensor is higher than High warning set point."
+ ::= 8
+
+inSeptTemperatureNotLowWarning TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: The temperature of sensor has returned from low warning to normal."
+ ::= 9
+
+inSeptTemperatureLowWarning TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "WARNING: The temperature of sensor is lower than low warning set point."
+ ::= 10
+
+inSeptTemperatureNotHighCritical TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: The temperature of sensor is lower than high critical set point."
+ ::= 11
+
+inSeptTemperatureHighCritical TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "CRITICAL: The temperature of sensor is higher than high critical set point."
+ ::= 12
+
+inSeptTemperatureNotLowCritical TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: The temperature of sensor is higher than low critical set point."
+ ::= 13
+
+inSeptTemperatureLowCritical TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "CRITICAL: The temperature of sensor is lower than low critical set point."
+ ::= 14
+
+inSeptHumidityNotHighWarning TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: The humidity of sensor has returned from High warning to normal."
+ ::= 15
+
+inSeptHumidityHighWarning TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "WARNING: The humidity of sensor is higher than High warning set point."
+ ::= 16
+
+inSeptHumidityNotLowWarning TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: The humidity of sensor has returned from low warning to normal."
+ ::= 17
+
+inSeptHumidityLowWarning TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "WARNING: The humidity of sensor is lower than low warning set point."
+ ::= 18
+
+inSeptHumidityNotHighCritical TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: The humidity of sensor is lower than high critical set point."
+ ::= 19
+
+inSeptHumidityHighCritical TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "CRITICAL: The humidity of sensor is higher than high critical set point."
+ ::= 20
+
+inSeptHumidityNotLowCritical TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "INFORMATION: The humidity of sensor is higher than low critical set point."
+ ::= 21
+
+inSeptHumidityLowCritical TRAP-TYPE
+ ENTERPRISE inSeptTraps
+ DESCRIPTION
+ "CRITICAL: The humidity of sensor is lower than low critical set point."
+ ::= 22
+
+END
+