-rw-r--r--MIBS/huawei/HUAWEI-POWER-MIB3579
1 files changed, 3579 insertions, 0 deletions
diff --git a/MIBS/huawei/HUAWEI-POWER-MIB b/MIBS/huawei/HUAWEI-POWER-MIB
new file mode 100644
index 0000000..039aec4
--- /dev/null
+++ b/MIBS/huawei/HUAWEI-POWER-MIB
@@ -0,0 +1,3579 @@
+-- ============================================================================
+-- Copyright (C)2013 by HUAWEI TECHNOLOGIES. All rights reserved.
+-- Description: This MIB is used for defining Power Monitor management
+-- MIB objects.
+-- Reference:
+-- Version: V3.35
+-- ============================================================================
+ HUAWEI-POWER-MIB DEFINITIONS ::= BEGIN
+
+ IMPORTS
+ hwEnvEmuIndex,hwEnvEmuType,hwDigChannelIndex
+ FROM HUAWEI-ENVIRONMENT-MIB
+ huaweiUtility
+ FROM HUAWEI-MIB
+ Integer32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE
+ FROM SNMPv2-SMI
+ DisplayString, RowStatus, TruthValue, DateAndTime, TEXTUAL-CONVENTION
+ FROM SNMPv2-TC
+ hwFrameIndex
+ FROM HUAWEI-DEVICE-MIB;
+
+ hwPower MODULE-IDENTITY
+ LAST-UPDATED "201312280000Z"
+ ORGANIZATION "Huawei Technologies Co.,Ltd."
+ CONTACT-INFO
+ "Huawei Industrial Base
+ Bantian, Longgang
+ Shenzhen 518129
+ People's Republic of China
+ Website: http://www.huawei.com
+ Email: support@huawei.com
+ "
+ DESCRIPTION
+ "
+ This MIB is used for defining Power Monitor management MIB objects.
+ "
+
+ -- Revision history
+ REVISION "201312280000Z"
+ DESCRIPTION "V3.35, modify the leaf of hwRectifierOperState."
+
+ REVISION "201311160000Z"
+ DESCRIPTION "V3.34, modify the leaf of hwRectifierOperState."
+
+ REVISION "201212280000Z"
+ DESCRIPTION "V3.33, added enumerate etp48150(128) in hwPowerType leaf for smu EMU,
+ added enumerate h801pmu(127) in hwPowerType leaf for H801PMU."
+
+ REVISION "201212140000Z"
+ DESCRIPTION "V3.32, add the leaf of hwBatteryLogTestBatteryTemperature, hwBatteryLogTestBatteryCurrent
+ and hwBatteryGroupBomCode for battery smart manage.
+ add enumerate sleep(6) in hwChargeOperStatus leaf.
+ add enumerate supplyRecoverAutotestTerminated(7) in hwBatteryTestResult leaf."
+
+ REVISION "201207240000Z"
+ DESCRIPTION "V3.31, add the leaf of hwPowerModuleRestoreTrap and hwPowerModuleMismatchTrap for SMU digital alarm."
+
+ REVISION "201206250000Z"
+ DESCRIPTION "V3.30, add enumerate smu(124) in hwPowerType leaf for smu EMU,
+ modified the name of hwBatteryTestPrealarmThreshold to hwBatteryTestAlarmThreshold,
+ modified description of hwBatteryTestDuration,hwBatteryTestTerminateVoltage and hwBatteryTestAlarmThreshold,
+ delete enumerate smu(124),
+ add enumerate etp4830(125) and enumerate etp4890(126) in hwPowerType leaf for smu EMU"
+
+ REVISION "201201090000Z"
+ DESCRIPTION "V3.29, add the leafs of hwEmmBatt1TempFaultTrap, hwEmmBatt1TempRestoreTrap, hwEmmEnviHumFaultTrap,
+ hwEmmEnviHumRestoreTrap, hwEmmEnvi1TempFaultTrap, hwEmmEnvi1TempRestoreTrap, hwEmmBattTemFaultTrap,
+ hwEmmBattTemRecoverTrap and hwEmmPowerBatteryOffRecoverTrap"
+
+ REVISION "201112170000Z"
+ DESCRIPTION "V3.28, added hwBatteryLogTestEfficiency the objects of hwEmmPowerBattaryTestStopTrap.
+ add the leaf of hwEmmPowerBatteryUnDetectTrap and ch_hwEmmPowerBatteryDetectRecoverTrap for SMU digital alarm."
+
+ REVISION "201112080000Z"
+ DESCRIPTION "V3.27, added hwBatteryTestPrealarmThreshold leaf node for getting and setting battery test prealarm threshold.
+ added hwBatteryLogTestEfficiency leaf node for inquiry efficiency setting. "
+
+ REVISION "201108170000Z"
+ DESCRIPTION "V3.25, add the leaf of hwEmmPowerBatteryOffTrap for battary power-off."
+
+ REVISION "201103160000Z"
+ DESCRIPTION "V3.25, added enumerate discharge(5) in hwChargeOperStatus leaf for discharge.
+ add enumerate LiFeBattery(123) in hwPowerType leaf for LiFeBattery EMU"
+
+ REVISION "201012170000Z"
+ DESCRIPTION "V3.24, added Objects hwBatteryLogTestBatteryStatus of hwEmmPowerBattaryTestStopTrap node."
+
+ REVISION "201011100000Z"
+ DESCRIPTION "V3.23, added enumerate power3000(122) in hwPowerType leaf for Power3000 EMU.
+ Modified the objects of hwEmmPowerBattloopFaultTrap and hwEmmPowerBattloopRecoverTrap.
+ Added hwEmmDigMainsupplyFaultTrap and hwEmmDigMainsupplyRecoverTrap."
+
+ REVISION "201007180900Z"
+ DESCRIPTION "V3.22, added enumerate power3000(122) in hwPowerType leaf for Power3000 EMU.
+ Modified the objects of hwEmmPowerBattloopFaultTrap and hwEmmPowerBattloopRecoverTrap.
+ Added hwEmmDigMainsupplyFaultTrap and hwEmmDigMainsupplyRecoverTrap."
+
+ REVISION "201006120900Z"
+ DESCRIPTION "V3.21, modified description of hwBatteryGroupOperStatus node."
+
+ REVISION "201004210900Z"
+ DESCRIPTION "V3.20, modified node name to avoid conflict."
+
+ REVISION "201004080900Z"
+ DESCRIPTION "V3.19, modified this MIB for clearing simple tester errors and warnings."
+
+ REVISION "201003090900Z"
+ DESCRIPTION "V3.18, added hwBatteryInstallTime leaf node for getting the battery installation time"
+
+ REVISION "201002060900Z"
+ DESCRIPTION "V3.17,Modified the description."
+
+ REVISION "201001290900Z"
+ DESCRIPTION "V3.16,Deleted simple tester MIB compile errors and warnings."
+
+ REVISION "200611100900Z"
+ DESCRIPTION "V3.09,Added hwBatteryHardwareState."
+
+ REVISION "200610250900Z"
+ DESCRIPTION "V3.08,Added hwBatteryVoltageState."
+
+ ::= { huaweiUtility 2 }
+
+
+ MeasuresRange ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "Basic unit of measure:
+ 1.pressure:indicated by mV, 1V = 1000 mV
+ 2.current:indicated by mA, 1A = 1000 mA
+ 3.temperature: indicated by 1% degree centigrade
+ "
+ SYNTAX Integer32
+
+
+
+ hwPowerMonObjects OBJECT IDENTIFIER ::= { hwPower 1 }
+ hwPowerSysInfoTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwPowerSysInfoEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Power basic information table. The indexes of this table are hwEnvEmuIndex
+ and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
+ the index of the monitoring unit. hwPowerIndex is the index of the power
+ supply monitored by the monitoring unit.
+ "
+ ::= { hwPowerMonObjects 1 }
+
+ hwPowerSysInfoEntry OBJECT-TYPE
+ SYNTAX HwPowerSysInfoEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Power basic information table. The indexes of this entry are hwEnvEmuIndex
+ and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
+ the index of the monitoring unit. hwPowerIndex is the index of the power
+ supply monitored by the monitoring unit.
+ "
+ INDEX { hwEnvEmuIndex, hwPowerIndex }
+ ::= { hwPowerSysInfoTable 1 }
+
+ HwPowerSysInfoEntry ::=
+ SEQUENCE {
+ hwPowerIndex
+ Integer32,
+ hwPowerType
+ INTEGER,
+ hwPowerName
+ DisplayString,
+ hwPowerState
+ INTEGER,
+ hwPowerRowStatus
+ RowStatus,
+ hwPowerControlMode
+ INTEGER,
+ hwPowerRemoteFrameID
+ Integer32,
+ hwPowerProtect
+ INTEGER,
+ hwPowerVersion
+ DisplayString,
+ hwPowerSupplyState
+ INTEGER
+ }
+
+ hwPowerIndex OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Index of the power supply monitored by the monitoring unit"
+ ::= { hwPowerSysInfoEntry 1 }
+
+ hwPowerType OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ power4875(1),
+ power4810(2),
+ power48100(3),
+ power4850(4),
+ power48240(5),
+ power48120(6),
+ power48300(7),
+ power48240SinglePhase(8),
+ universalPower(9),
+ power4845(10),
+ rpower(11),
+ power4805(15),
+ power4820(16),
+ onps(17),
+ power4875l(18),
+ psma(100),
+ perm-al175nt(101),
+ mcs1800(102),
+ mcs1800A(103),
+ mcs3000(104),
+ sm40sm60(105),
+ scu(106),
+ eltek(107),
+ dk04(108),
+ dk04C(109),
+ dpc(110),
+ power4830(120),
+ h831pmua(121),
+ power3000(122),
+ liFeBattery(123),
+ etp4830(125),
+ etp4890(126),
+ h801pmu(127),
+ etp48150(128),
+ other(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Type of the Power emu device.
+ Options:
+ 1.power4875(1) - Type of the Power emu device is power4875
+ 2.power4810(2) - Type of the Power emu device is power4810
+ 3.power48100(3) - Type of the Power emu device is power48100
+ 4.power4850(4) - Type of the Power emu device is power4850
+ 5.power48240(5) - Type of the Power emu device is power48240
+ 6.power48120(6) - Type of the Power emu device is power48120
+ 7.power48300(7) - Type of the Power emu device is power48300
+ 8.power48240SinglePhase(8) - Type of the Power emu device is power48240SinglePhase
+ 9.universalPower(9) - Type of the Power emu device is universalPower
+ 10.power4845(10) - Type of the Power emu device is power4845
+ 11.rpower(11) - Type of the Power emu device is rpower
+ 12.power4805(15) - Type of the Power emu device is power4805
+ 13.power4820(16) - Type of the Power emu device is power4820
+ 14.onps(17) - Type of the Power emu device is onps
+ 15.power4875l(18) - Type of the Power emu device is power4875l
+ 16.psma(100) - Type of the Power emu device is psma
+ 17.perm-al175nt(101) - Type of the Power emu device is perm-al175nt
+ 18.mcs1800(102) - Type of the Power emu device is mcs1800
+ 19.mcs1800A(103) - Type of the Power emu device is mcs1800A
+ 20.mcs3000(104) - Type of the Power emu device is mcs3000
+ 21.sm40sm60(105) - Type of the Power emu device is sm40sm60
+ 22.scu(106) - Type of the Power emu device is scu
+ 23.eltek(107) - Type of the Power emu device is eltek
+ 24.dk04(108) - Type of the Power emu device is dk04
+ 25.dk04C(109) - Type of the Power emu device is dk04C
+ 26.dpc(110) - Type of the Power emu device is dpc
+ 27.power4830(120) - Type of the Power emu device is power4830
+ 28.h831pmua(121) - Type of the Power emu device is h831pmua
+ 29.power3000(122) - Type of the Power emu device is power3000
+ 30.liFeBattery(123) - Type of the Power emu device is LiFeBattery
+ 31.etp4830(125), - Type of SMU Power emu device is etp4830
+ 32.etp4890(126), - Type of SMU Power emu device is etp4890
+ 33.h801pmu(127), - Type of the Power emu device is h801pmua
+ 34.etp48150(128), - Type of SMU Power emu device is etp48150
+ 35.other(255) - other Power Type
+ "
+ ::= { hwPowerSysInfoEntry 2 }
+
+ hwPowerName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "
+ Power name.
+ "
+ ::= { hwPowerSysInfoEntry 3 }
+
+ hwPowerState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ fault(2),
+ protecting(3),
+ switched(4),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Power board status:
+ Refers to the status of communication between the internal monitor board
+ of the power device and the external upper board.
+ Options:
+ 1.normal(1) - indicates the normal state
+ 2.fault(2) - indicates the faulty state
+ 3.protecting(3)- indicates that the backup power supply works in the protection state
+ 4.switched(4) - indicates that the main power supply is faulty, and is protected by backup power supply
+ 5.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwPowerSysInfoEntry 4 }
+
+ hwPowerRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "RowStatus standard operation. The values 1 and 2 are supported currently.
+ 1 indicates the activation status, and 2 indicates the non-activation status."
+ ::= { hwPowerSysInfoEntry 5 }
+
+ hwPowerControlMode OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ manualControl(1),
+ autoControl(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Control mode of the power monitor module.
+ Options:
+ 1.manualControl(1) - control by manual, the remote mode
+ 2.autoControl(2) - auto control mode, the default is auto control mode
+ 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ DEFVAL { 1 }
+ ::= { hwPowerSysInfoEntry 6 }
+
+ hwPowerRemoteFrameID OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Apply for remote power system.
+ It is the frame ID that the remote unit exists in"
+ ::= { hwPowerSysInfoEntry 7 }
+
+ hwPowerProtect OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ protect(1),
+ undoProtect(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Apply for remote power system.
+ It is used to enable or disable N+1 protection function.
+ Options:
+ 1.protect(1) - enables the N+1 protection function
+ 2.undoProtect(2) - disables the N+1 protection function"
+ ::= { hwPowerSysInfoEntry 8 }
+
+ hwPowerVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Version of power"
+ ::= { hwPowerSysInfoEntry 9 }
+
+ hwPowerSupplyState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ ac(1),
+ battery(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ Power supply modes.
+ Options:
+ 1.ac(1) - indicates the AC power supply
+ 2.battery(2) - indicates power supply by the batteries
+ "
+ ::= { hwPowerSysInfoEntry 10 }
+
+ hwACInputTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwACInputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "AC input table. Through this table,
+ AC input monitoring parameters of 4875 power supply, 4845 power supply,
+ 4810 power supply, 48100 power supply, and 48240 power supply can
+ be set and queried.
+ The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex.
+ hwEnvEmuIndex is the index of the monitoring unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
+ "
+ ::= { hwPowerMonObjects 2 }
+
+ hwACInputEntry OBJECT-TYPE
+ SYNTAX HwACInputEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "AC input table. Through this table,
+ AC input monitoring parameters of 4875 power supply, 4845 power supply,
+ 4810 power supply, 48100 power supply, and 48240 power supply can
+ be set and queried.
+ The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex.
+ hwEnvEmuIndex is the index of the monitoring unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit."
+ INDEX { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ ::= { hwACInputTable 1 }
+
+ HwACInputEntry ::=
+ SEQUENCE {
+ hwACLoopIndex
+ Integer32,
+ hwACPowerState
+ INTEGER,
+ hwACVoltA
+ MeasuresRange,
+ hwACCurrentA
+ MeasuresRange,
+ hwACVoltB
+ MeasuresRange,
+ hwACCurrentB
+ MeasuresRange,
+ hwACVoltC
+ MeasuresRange,
+ hwACCurrentC
+ MeasuresRange,
+ hwACVoltageHigh
+ MeasuresRange,
+ hwACVoltageLow
+ MeasuresRange,
+ hwACRowStatus
+ RowStatus,
+ hwACVoltageAState
+ INTEGER,
+ hwACVoltageBState
+ INTEGER,
+ hwACVoltageCState
+ INTEGER
+ }
+
+ hwACLoopIndex OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Input loop index. There are two channels of AC current input,
+ which are the backup for each other."
+ ::= { hwACInputEntry 1 }
+
+ hwACPowerState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ offline(2),
+ exceedVoltage(3),
+ belowVoltage(4),
+ backup(5),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Status of power supply.
+ Options:
+ 1.normal(1) - indicates that the power supply is normal
+ 2.offline(2) - indicates that the power supply is offline
+ 3.exceedVoltage(3) - indicates that the power supply is overvoltage
+ 4.belowVoltage(4) - indicates that the power supply is undervoltage
+ 5.backup(5) - indicates that the power supply is not supported currently
+ 6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwACInputEntry 2 }
+
+ hwACVoltA OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "AC Inuput voltage A.
+ Unit: mV"
+ ::= { hwACInputEntry 3 }
+
+ hwACCurrentA OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "AC input Current A.
+ Unit: mA"
+ ::= { hwACInputEntry 4 }
+
+ hwACVoltB OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "AC input voltage B.
+ Unit: mv"
+ ::= { hwACInputEntry 5 }
+
+ hwACCurrentB OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "AC input current B.
+ Unit: mA"
+ ::= { hwACInputEntry 6 }
+
+ hwACVoltC OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "AC input voltage C.
+ Unit: mV"
+ ::= { hwACInputEntry 7 }
+
+ hwACCurrentC OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "AC input current C.
+ Unit: mA"
+ ::= { hwACInputEntry 8 }
+
+ hwACVoltageHigh OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "AC input over-voltage alarm threshold.
+ Unit: mV"
+ DEFVAL { 280000 }
+ ::= { hwACInputEntry 9 }
+
+ hwACVoltageLow OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "AC input under-voltage alarm threshold.
+ Unit: mV"
+ DEFVAL { 180000 }
+ ::= { hwACInputEntry 10 }
+
+ hwACRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Only the add operation, delete operation, and status query operation are supported."
+ ::= { hwACInputEntry 11 }
+
+ hwACVoltageAState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(0),
+ belowVoltage(1) ,
+ exceedVoltage(2),
+ missing-phase(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Phase AB/A of AC input state.
+ Options:
+ 1. normal(0) - indicates that the Phase AB/A of AC input state is normal
+ 2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage
+ 3. exceedVoltage(2) - indicates that the Phase AB/A of AC input state is exceedVoltage
+ 4. missing-phase(3) - indicates that the Phase AB/A of AC input state is missing-phase
+ "
+ ::= { hwACInputEntry 12 }
+
+ hwACVoltageBState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(0),
+ belowVoltage(1) ,
+ exceedVoltage(2),
+ missing-phase(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Phase BC/B of AC input state.
+ Options:
+ 1. normal(0) - indicates that the Phase BC/B of AC input state is normal
+ 2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage
+ 3. exceedVoltage(2) - indicates that the Phase BC/B of AC input state is exceedVoltage
+ 4. missing-phase(3) - indicates that the Phase BC/B of AC input state is missing-phase
+ "
+ ::= { hwACInputEntry 13 }
+
+ hwACVoltageCState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(0),
+ belowVoltage(1) ,
+ exceedVoltage(2),
+ missing-phase(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Phase CA/C of AC input state.
+ Options:
+ 1. normal(0) - indicates that the Phase CA/C of AC input state is normal
+ 2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage
+ 3. exceedVoltage(2) - indicates that the Phase CA/C of AC input state is exceedVoltage
+ 4. missing-phase(3) - indicates that the Phase CA/C of AC input state is missing-phase
+ "
+ ::= { hwACInputEntry 14 }
+
+ hwDCOutTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwDCOutEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "DC output table. Through this table,
+ DC output monitoring parameters of 4875 power supply, 4845 power supply,
+ 4810 power supply, 482400 power supply, and 48100 power supply can
+ be set and queried.
+ The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
+ is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ ::= { hwPowerMonObjects 3 }
+
+ hwDCOutEntry OBJECT-TYPE
+ SYNTAX HwDCOutEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "DC output table. Through this table,
+ DC output monitoring parameters of 4875 power supply, 4845 power supply,
+ 4810 power supply, 482400 power supply, and 48100 power supply can
+ be set and queried.
+ The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
+ is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ INDEX { hwEnvEmuIndex, hwPowerIndex }
+ ::= { hwDCOutTable 1 }
+
+ HwDCOutEntry ::=
+ SEQUENCE {
+ hwDCVoltageOut
+ MeasuresRange,
+ hwDCCurrentOut
+ MeasuresRange,
+ hwDCVoltageOutHigh
+ MeasuresRange,
+ hwDCVoltageOutLow
+ MeasuresRange,
+ hwDCVoltageOutState
+ INTEGER,
+ hwDCCurrentOutHigh
+ MeasuresRange,
+ hwDCCurrentOutLow
+ MeasuresRange,
+ hwDCCurrentOutState
+ INTEGER,
+ hwDCOutRowStatus
+ RowStatus,
+ hwDCOutLoadCurrent
+ MeasuresRange,
+ hwDCOutLoadTmpHigh
+ MeasuresRange,
+ hwDCOutRunState
+ BITS ,
+ hwDCCommunicationState
+ INTEGER
+ }
+
+ hwDCVoltageOut OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "DC voltage output.
+ Unit: mV"
+ ::= { hwDCOutEntry 1 }
+
+ hwDCCurrentOut OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "DC current output.
+ Unit: mA"
+ ::= { hwDCOutEntry 2 }
+
+ hwDCVoltageOutHigh OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Output DC exceed-voltage alarm point.
+ Default: 58000
+ Unit: mV"
+ DEFVAL { 58000 }
+ ::= { hwDCOutEntry 3 }
+
+ hwDCVoltageOutLow OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Output DC below-voltage alarm point . Default value is 45V.
+ Unit: mV"
+ DEFVAL { 45000 }
+ ::= { hwDCOutEntry 4 }
+
+ hwDCVoltageOutState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ exceedVoltage(2),
+ belowVoltage(3),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "DC output voltage status.
+ Options:
+ 1. normal(1) - indicates that the DC output voltage state is normal
+ 2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage
+ 3. belowVoltage(3) - indicates that the DC output voltage state is belowVoltage
+ 4.invalid(-1) - indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwDCOutEntry 5 }
+
+ hwDCCurrentOutHigh OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Output DC exceed-current alarm point .
+ Unit: mA"
+ ::= { hwDCOutEntry 6 }
+
+ hwDCCurrentOutLow OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Output below-current alarm point .
+ Unit: mA"
+ ::= { hwDCOutEntry 7 }
+
+ hwDCCurrentOutState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ exceedVoltage(2),
+ belowVoltage(3),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS deprecated
+ DESCRIPTION
+ "DC output current status.
+ Options:
+ 1.normal(1) - indicates that the DC output current state is normal
+ 2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage
+ 3.belowVoltage(3) - indicates that the DC output current state is belowVoltage
+ 4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwDCOutEntry 8 }
+
+ hwDCOutRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "RowStatus standard operation"
+ ::= { hwDCOutEntry 9 }
+
+ hwDCOutLoadCurrent OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total load current of DC output .
+ Unit: mA"
+ ::= { hwDCOutEntry 10 }
+
+ hwDCOutLoadTmpHigh OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "0.01 degree"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The off protection point under the load temperature, by default,
+ it is 65 degrees centigrade.
+ Unit: 0.01 degree"
+ DEFVAL { 6500 }
+ ::= { hwDCOutEntry 11 }
+
+ hwDCOutRunState OBJECT-TYPE
+ SYNTAX BITS
+ {
+ battery1ChargeCurOver(0),
+ battery2ChargeCurOver(1),
+ batteryVoltageOver(2),
+ batteryVoltageLack(3),
+ loadOff(4),
+ batteryOff(5),
+ communicationFailure(6),
+ dcOutManual(7)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "DC output running status.
+ Options:
+ 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
+ 2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
+ 3.batteryVoltageOver(2) - indicates output over-voltage
+ 4.batteryVoltageLack(3) - indicates battery lack-voltage
+ 5.loadOff(4) - indicates load off twice
+ 6.batteryOff(5) - indictes battery protection (off once)
+ 7.communicationFailure(6) - indicates that the communication fails
+ 8.dcOutManual(7) - indicates DC by manual"
+ ::= { hwDCOutEntry 12 }
+
+ hwDCCommunicationState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(0),
+ fault(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "DC communication status.
+ Options:
+ 1.normal(0) - indicates that the DC communication state is normal
+ 2.fault(1) - indicates that the DC communication state is fault
+ "
+ ::= { hwDCOutEntry 13 }
+
+ hwLoadinfoTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwLoadinfoEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Load information table. Through this table, the load parameter can be set and queried.
+ The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
+ hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwLoadIndex is the index of the monitored load.
+ "
+ ::= { hwPowerMonObjects 4 }
+
+ hwLoadinfoEntry OBJECT-TYPE
+ SYNTAX HwLoadinfoEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Load information table. Through this table, the load parameter can be set and queried.
+ The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
+ hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwLoadIndex is the index of the monitored load.
+ "
+ INDEX { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ ::= { hwLoadinfoTable 1 }
+
+ HwLoadinfoEntry ::=
+ SEQUENCE {
+ hwLoadIndex
+ Integer32,
+ hwLoadInfoAdminState
+ INTEGER,
+ hwLoadInfoOperStatus
+ INTEGER,
+ hwLoadCurrent
+ MeasuresRange,
+ hwLoadVoltage
+ MeasuresRange,
+ hwLoadVoltageHigh
+ MeasuresRange,
+ hwLoadLoadName
+ DisplayString,
+ hwLoadInfoRowStatus
+ RowStatus,
+ hwLoadFuseState
+ INTEGER,
+ hwLoadHoreIndex
+ Integer32
+ }
+
+ hwLoadIndex OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Loop index: usually each DC output loop corresponds to a load."
+ ::= { hwLoadinfoEntry 1 }
+
+ hwLoadInfoAdminState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Load operation.
+ Options:
+ 1. on(1) - indicates that the Load is enabled
+ 2. off(2) - indicates that the Load is disabled
+ 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ DEFVAL { 1 }
+ ::= { hwLoadinfoEntry 2 }
+
+ hwLoadInfoOperStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ abnormal(2),
+ stop(3),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Status of power supply.
+ Options:
+ 1. normal(1) - indicates that the state of power supply is normal
+ 2. abnormal(2) - indicates that the state of power supply is abnormal
+ 3. stop(3) - indicates that the state of power supply is stopping power supply
+ 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwLoadinfoEntry 3 }
+
+ hwLoadCurrent OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Present current .
+ Unit: mA"
+ ::= { hwLoadinfoEntry 4 }
+
+ hwLoadVoltage OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Present voltage .
+ Unit: mV"
+ ::= { hwLoadinfoEntry 5 }
+
+ hwLoadVoltageHigh OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Off voltage (Stop external voltage), in unit of mV,
+ When DC output voltage exceeds the value, the load will be automatically cut off.
+ Default: 43500
+ Unit: mV
+ "
+ DEFVAL { 43500 }
+ ::= { hwLoadinfoEntry 6 }
+
+ hwLoadLoadName OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Load name: usually each DC output loop corresponds to a load."
+ ::= { hwLoadinfoEntry 7 }
+
+ hwLoadInfoRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "RowStatus standard operation"
+ ::= { hwLoadinfoEntry 8 }
+
+ hwLoadFuseState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Load fuse state, including the auxiliary load fuse.
+ Options:
+ 1. on(1) - indicates that the fuse is connected
+ 2. off(2) - indicates that the fuse is disconnected
+ 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwLoadinfoEntry 9 }
+
+ hwLoadHoreIndex OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "
+ load hore index
+ "
+ ::= { hwLoadinfoEntry 10 }
+
+
+ hwRectifierTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwRectifierEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Rectifier module table.
+ Through this table, the status information of the rectifier module
+ can be set and queried.
+ The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
+ hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
+ is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwRectifierIndex is the index of the monitored rectifier module under the power supply.
+ "
+ ::= { hwPowerMonObjects 5 }
+
+ hwRectifierEntry OBJECT-TYPE
+ SYNTAX HwRectifierEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Rectifier module table.
+ Through this table, the status information of the rectifier module
+ can be set and queried.
+ The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
+ hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
+ is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwRectifierIndex is the index of the monitored rectifier module under the power supply.
+ "
+ INDEX { hwEnvEmuIndex, hwPowerIndex, hwRectifierIndex }
+ ::= { hwRectifierTable 1 }
+
+ HwRectifierEntry ::=
+ SEQUENCE {
+ hwRectifierIndex
+ Integer32,
+ hwRectifierAdminState
+ INTEGER,
+ hwRectifierOperState
+ INTEGER,
+ hwRectifierVoltage
+ MeasuresRange,
+ hwRectifierCurrent
+ MeasuresRange,
+ hwRectifierRowStatus
+ RowStatus,
+ hwRectifierCurrentLimit
+ TruthValue,
+ hwRectifierRunState
+ BITS,
+ hwRectifierChargeState
+ INTEGER
+ }
+
+ hwRectifierIndex OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Rectifier Module index. There are multiple rectifier
+ modules to a power source.
+ "
+ ::= { hwRectifierEntry 1 }
+
+ hwRectifierAdminState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Switch operation of rectifier module.
+ Options:
+ 1.on(1) - indicates that the Rectifier module is enabled
+ 2.off(2) - indicates that the Rectifier module is disabled
+ 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ DEFVAL { 1 }
+ ::= { hwRectifierEntry 2 }
+
+ hwRectifierOperState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ fault(2),
+ protect(3),
+ communicationFailure(4),
+ on(5),
+ noConfig(6),
+ offline(7),
+ close(8),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device.
+ Options:
+ 1. normal(1) - indicates that the Rectifier operation state is normal
+ 2. fault(2) - indicates that the Rectifier operation state is fault
+ 3. protect(3) - indicates that the Rectifier operation state is protect
+ 4. communicationFailure(4) - indicates that the Rectifier operation state is communicationFailure
+ 5. on(5) - indicates that the Rectifier operation state is on
+ 6. noConfig(6) - indicates that the Rectifier operation state is not Configured
+ 7. offline(7) - indicates that the Rectifier operation state is offline
+ 8. close(8) - indicates that the Rectifier operation state is closed
+ 9. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwRectifierEntry 3 }
+
+ hwRectifierVoltage OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Output voltage .
+ Unit: mV"
+ ::= { hwRectifierEntry 4 }
+
+ hwRectifierCurrent OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Output current .
+ Unit: mA"
+ ::= { hwRectifierEntry 5 }
+
+ hwRectifierRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "RowStatus standard operation"
+ ::= { hwRectifierEntry 6 }
+
+ hwRectifierCurrentLimit OBJECT-TYPE
+ SYNTAX TruthValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "current limit switch"
+ DEFVAL { 1 }
+ ::= { hwRectifierEntry 7 }
+
+ hwRectifierRunState OBJECT-TYPE
+ SYNTAX BITS
+ {
+ rectifierOn(0),
+ averageCharge(1),
+ output(2),
+ isLimit(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Running state of rectifier module.
+ Options:
+ 1.rectifierOn(0) - indicates that the module is on
+ 2.averageCharge(1) - indicates that the module is being averagely charged.
+ 3.output(2) - indicates that the module has output
+ 4. isLimit(3) - indicates the current limit switch
+ "
+ ::= { hwRectifierEntry 8 }
+
+ hwRectifierChargeState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ float(0),
+ average(1),
+ test(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Charging state of rectifier.
+ Options:
+ 1. float(0) - indicates that the Charge state of Rectifier is float
+ 2. average(1) - indicates that the Charge state of Rectifier is average
+ 3. test(2) - indicates that the Charge state of Rectifier is test
+ "
+ ::= { hwRectifierEntry 9 }
+
+ hwBatteryGroup OBJECT IDENTIFIER ::= { hwPowerMonObjects 6 }
+ hwBatteryGroupTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwBatteryGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Basic information table of battery group.
+ The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex is the index of the monitored unit,
+ and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ ::= { hwBatteryGroup 1 }
+
+ hwBatteryGroupEntry OBJECT-TYPE
+ SYNTAX HwBatteryGroupEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Basic information table of battery group.
+ The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex is the index of the monitored unit,
+ and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ INDEX { hwEnvEmuIndex, hwPowerIndex }
+ ::= { hwBatteryGroupTable 1 }
+
+ HwBatteryGroupEntry ::=
+ SEQUENCE {
+ hwBatteryGroupCapacity
+ Integer32,
+ hwBatteryGroupCapcaityRemain
+ Integer32,
+ hwBatteryGroups
+ Integer32,
+ hwBatteryGroupVoltageLow
+ MeasuresRange,
+ hwBatteryGroupChargeLimit
+ MeasuresRange,
+ hwBatteryGroupRowStatus
+ RowStatus,
+ hwBatteryGroupOperStatus
+ INTEGER,
+ hwBatteryGroupVoltageHigh
+ MeasuresRange,
+ hwBatteryGroupTwiceOffVoltage
+ MeasuresRange,
+ hwBatteryGroupProtectVoltage
+ MeasuresRange,
+ hwBatteryGroupTmpOffHigh
+ MeasuresRange,
+ hwBatteryInstallTime
+ DisplayString,
+ hwBatteryGroupBomCode
+ DisplayString
+ }
+
+ hwBatteryGroupCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total capacity of the present battery group.
+ Unit: Ah"
+ ::= { hwBatteryGroupEntry 1 }
+
+ hwBatteryGroupCapcaityRemain OBJECT-TYPE
+ SYNTAX Integer32 (-1..100)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Total remain capacity of the present battery group .
+ invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
+ Unit: Ah"
+ ::= { hwBatteryGroupEntry 2 }
+
+ hwBatteryGroups OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Number of battery group"
+ DEFVAL { 2 }
+ ::= { hwBatteryGroupEntry 3 }
+
+ hwBatteryGroupVoltageLow OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "When the voltage of the battery group is lower than the value set,
+ the battery group will no longer supply power. Its unit is mV.
+ Default: 43000
+ Unit: mV
+ "
+ DEFVAL { 43000 }
+ ::= { hwBatteryGroupEntry 4 }
+
+ hwBatteryGroupChargeLimit OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "percent"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Charge limit point quotient, the product of which and the max capacity
+ of the battery group is the max charge current allowed.
+ Default: 15
+ Unit: percent
+ "
+ DEFVAL { 15 }
+ ::= { hwBatteryGroupEntry 5 }
+
+ hwBatteryGroupRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "RowStatus standard operation"
+ ::= { hwBatteryGroupEntry 6 }
+
+ hwBatteryGroupOperStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The State of the battery supply which was connected with Power EMU.
+ To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal.
+ When the mains supply is abnormal, the battery group usually supplies power in an emergency.
+ Options:
+ 1.on(1) - indicates that the state of the battery power supply is on
+ 2.off(2) - indicates that the state of the battery power supply is off
+ 3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormal"
+ ::= { hwBatteryGroupEntry 7 }
+
+ hwBatteryGroupVoltageHigh OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "When the voltage of the battery group is higher than the value set, the battery group
+ will no longer supply power. Its unit is mV.
+ Default: 43000
+ Unit: mV
+ "
+ DEFVAL { 43000 }
+ ::= { hwBatteryGroupEntry 8 }
+
+ hwBatteryGroupTwiceOffVoltage OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The twice off protection voltage of the battery group. Its unit is mV.
+ Default: 44000
+ Unit: mV
+ "
+ DEFVAL { 44000 }
+ ::= { hwBatteryGroupEntry 9 }
+
+ hwBatteryGroupProtectVoltage OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The first off protection voltage of the battery,
+ whose default is 43V.
+ Default: 43000
+ Unit: mV
+ "
+ DEFVAL { 43000 }
+ ::= { hwBatteryGroupEntry 10 }
+
+ hwBatteryGroupTmpOffHigh OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "0.01 degree"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The high temperature off protection point of the battery group,
+ whose default is 50 degrees centigrade.
+ Unit: 0.01 degree
+ "
+ DEFVAL { 5000 }
+ ::= { hwBatteryGroupEntry 11 }
+
+ hwBatteryInstallTime OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ The installing date of battery group.
+ "
+ ::= { hwBatteryGroupEntry 12 }
+
+ hwBatteryGroupBomCode OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..32))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "
+ The BOM code of battery.
+ "
+ ::= { hwBatteryGroupEntry 13 }
+
+ hwChargeTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwChargeEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Charge management table.
+ Through this table, the charging parameter of the battery can be set and queried.
+ The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex is the index of the monitored unit,
+ and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ ::= { hwBatteryGroup 2 }
+
+ hwChargeEntry OBJECT-TYPE
+ SYNTAX HwChargeEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Charge management table.
+ Through this table, the charging parameter of the battery can be set and queried.
+ The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex is the index of the monitored unit,
+ and hwPowerIndex is the index of the power supply monitored by the monitoring unit."
+ INDEX { hwEnvEmuIndex, hwPowerIndex }
+ ::= { hwChargeTable 1 }
+
+ HwChargeEntry ::=
+ SEQUENCE {
+ hwChargeAdminStatus
+ INTEGER,
+ hwChargeOperStatus
+ INTEGER,
+ hwAverageChargeVoltage
+ MeasuresRange,
+ hwFloatChargeVoltage
+ MeasuresRange,
+ hwChargeControlRowStatus
+ RowStatus,
+ hwAverageChargeTime
+ Integer32,
+ hwBatteryTmpRedeemingQuotiety
+ Integer32
+ }
+
+ hwChargeAdminStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ average(1),
+ float(2),
+ auto(3),
+ invalid(-1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Charge management mode.
+ Options:
+ 1. average(1) - indicates that the charge management mode is average charge
+ 2. float(2) - indicates that the charge management mode is float charge
+ 3. auto(3) - indicates that the charge management mode is auto-control charge
+ 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ DEFVAL { 2 }
+ ::= { hwChargeEntry 1 }
+
+ hwChargeOperStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ average(1),
+ float(2),
+ full(3),
+ noCharge(4),
+ discharge(5),
+ sleep(6),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Charge operation status.
+ Options:
+ 1. average(1) - indicates that the charge operation state is average charge
+ 2. float(2) - indicates that the charge operation state is float charge
+ 3. full(3) - indicates that the charge operation state is full
+ 4. noCharge(4) - indicates that there is no charge in operation
+ 5. discharge(5) - indicates that there is discharge in operation
+ 6. sleep(6) - indicates that the charge operation state is sleep
+ 7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwChargeEntry 2 }
+
+ hwAverageChargeVoltage OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Voltage value of average charge, in unit of mV.
+ Default: 56500
+ Unit: mV
+ "
+ DEFVAL { 56500 }
+ ::= { hwChargeEntry 3 }
+
+ hwFloatChargeVoltage OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Voltage value of float charge .
+ Default: 53500
+ Unit: mV
+ "
+ DEFVAL { 53500 }
+ ::= { hwChargeEntry 4 }
+
+ hwChargeControlRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "RowStatus standard operation"
+ ::= { hwChargeEntry 5 }
+
+ hwAverageChargeTime OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "day"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Timing average charge time interval, effective range is 190 days.
+ Default :value is 60 days
+ Unit: day"
+ DEFVAL { 60 }
+ ::= { hwChargeEntry 6 }
+
+ hwBatteryTmpRedeemingQuotiety OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Temperature redeeming quotient, used to set the co-relation
+ between the float charge voltage and the battery temperature.
+ It means How much will the float charge voltage decrease
+ with the increasing of every degree centigrade of the battery
+ temperature. The unit is mV.
+ Specific value is determined by the redeem feature curve of
+ floating charge for the battery group used.
+ Default value is 100mV
+ "
+ DEFVAL { 100 }
+ ::= { hwChargeEntry 7 }
+
+ hwBatteryTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwBatteryEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Battery group state table.
+ Through this table, the status parameter of a battery group can be set and queried.
+ The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
+ hwEnvEmuIndex is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwBatteryIndex is the index of the monitored battery group.
+ "
+ ::= { hwBatteryGroup 3 }
+
+ hwBatteryEntry OBJECT-TYPE
+ SYNTAX HwBatteryEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Battery group state table.
+ Through this table, the status parameter of a battery group can be set and queried.
+ The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
+ hwEnvEmuIndex is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwBatteryIndex is the index of the monitored battery group.
+ "
+ INDEX { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
+ ::= { hwBatteryTable 1 }
+
+ HwBatteryEntry ::=
+ SEQUENCE {
+ hwBatteryIndex
+ Integer32,
+ hwBatteryCapacity
+ Integer32,
+ hwBatteryLoopState
+ INTEGER,
+ hwBatteryVoltage
+ MeasuresRange,
+ hwBatteryState
+ INTEGER,
+ hwBatteryCurrent
+ MeasuresRange,
+ hwBatteryTemperature
+ Integer32,
+ hwBatteryRowStatus
+ RowStatus,
+ hwBatteryCurrentHigh
+ MeasuresRange,
+ hwBatteryFuseState
+ INTEGER,
+ hwBatteryContactState
+ INTEGER,
+ hwBatteryRemainCapacity
+ Integer32,
+ hwBatteryProtectState
+ INTEGER,
+ hwBatteryVoltageState
+ INTEGER,
+ hwBatteryHardwareState
+ INTEGER
+ }
+
+ hwBatteryIndex OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery group loop index"
+ ::= { hwBatteryEntry 1 }
+
+ hwBatteryCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The permitted max battery capacity of the battery group loop charge.
+ Unit: Ah"
+ DEFVAL { 100 }
+ ::= { hwBatteryEntry 2 }
+
+ hwBatteryLoopState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The battery group present status.
+ Options:
+ 1. on(1) - indicates that the present state of battery group is on
+ 2. off(2) - indicates that the present state of battery group is off
+ 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwBatteryEntry 3 }
+
+ hwBatteryVoltage OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The loop voltage of the battery group.
+ Unit: mV"
+ ::= { hwBatteryEntry 4 }
+
+ hwBatteryState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ charge(1),
+ discharge(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present state of the battery group loop.
+ Options:
+ 1. charge(1) - indicates that the present state of the battery group loop is charge
+ 2. discharge(2) - indicates that the present state of the battery group loop is discharge
+ 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwBatteryEntry 5 }
+
+ hwBatteryCurrent OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Present current .
+ Unit: mA"
+ ::= { hwBatteryEntry 6 }
+
+ hwBatteryTemperature OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "degree"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The loop temperature of the battery group.
+ Unit: degree"
+ ::= { hwBatteryEntry 7 }
+
+ hwBatteryRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "RowStatus standard operation"
+ ::= { hwBatteryEntry 8 }
+
+ hwBatteryCurrentHigh OBJECT-TYPE
+ SYNTAX MeasuresRange
+ UNITS "mA"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The over-current alarm point of the battery group.
+ Unit: mA"
+ ::= { hwBatteryEntry 9 }
+
+ hwBatteryFuseState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery fuse state.
+ Options:
+ 1. on(1) - indicates that the fuse is connected
+ 2. off(2) - indicates that the fuse is disconnected
+ 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
+ "
+ ::= { hwBatteryEntry 10 }
+
+ hwBatteryContactState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ on(1),
+ off(2),
+ invalid(-1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The state of the battery contactor.
+ Options:
+ 1. on(1) - indicates that the contactor is connected
+ 2. off(2) - indicates that the contactor is disconnected
+ 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal"
+ ::= { hwBatteryEntry 11 }
+
+ hwBatteryRemainCapacity OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Remain capacity of the battery
+ "
+ ::= { hwBatteryEntry 12 }
+
+ hwBatteryProtectState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ overtemperature(2),
+ overCurrent(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Protection status of the battery.
+ Options:
+ 1. normal(1) - indicates that the Protection status of the battery is normal
+ 2. overtemperature(2) - indicates that the Protection status of the battery is overtemperature
+ 3. overCurrent(3) - indicates that the Protection status of the battery is overCurrent
+ "
+ ::= { hwBatteryEntry 13 }
+
+ hwBatteryVoltageState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ exceedVoltage(2),
+ belowVoltage(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Voltage state of Battery.
+ Options:
+ 1. normal(1) - indicates that Voltage state of Battery is normal
+ 2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage
+ 3. belowVoltage(3) - indicates that Voltage state of Battery is belowVoltage
+ "
+ ::= { hwBatteryEntry 14 }
+
+ hwBatteryHardwareState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ fault(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Hardware State of Battery.
+ Options:
+ 1. normal(1) - indicates that the hardware state of Battery is normal
+ 2. fault(2) - indicates that the hardware state of Battery is fault
+ "
+ ::= { hwBatteryEntry 15 }
+
+ hwBatteryTestTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwBatteryTestEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Battery test table.
+ The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex is the index of the monitored unit,
+ and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ ::= { hwBatteryGroup 4 }
+
+ hwBatteryTestEntry OBJECT-TYPE
+ SYNTAX HwBatteryTestEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Battery test table.
+ The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex is the index of the monitored unit,
+ and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ INDEX { hwEnvEmuIndex, hwPowerIndex }
+ ::= { hwBatteryTestTable 1 }
+
+ HwBatteryTestEntry ::=
+ SEQUENCE {
+ hwBatteryTestAdminStatus
+ INTEGER,
+ hwBatteryTestAutoDischargePeriod
+ Integer32,
+ hwBatteryTestResult
+ INTEGER,
+ hwBatteryTestStartTime
+ DateAndTime,
+ hwBatteryTestDuration
+ Integer32,
+ hwBatteryTestTerminateVoltage
+ Integer32,
+ hwBatteryTestTotalDischargeAH
+ Integer32,
+ hwBatteryTestOperStatus
+ INTEGER,
+ hwBatteryTestPhase
+ INTEGER,
+ hwBatteryTestStartHour
+ Integer32,
+ hwBatteryTestAlarmThreshold
+ Integer32
+ }
+
+ hwBatteryTestAdminStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ start(1),
+ terminate(2),
+ enableAutoTest(3),
+ disableAutoTest(4),
+ timeautoTest(5),
+ offautoTest(6),
+ timeoffautoTest(7)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery test admin status.
+ Options:
+ 1. start(1) - indicates that the Battery starts testing
+ 2. terminate(2) - indicates that the Battery terminates testing
+ 3. enableAutoTest(3) - indicates that the Battery enables auto test function
+ 4. disableAutoTest(4) - indicates that the Battery disables auto test function
+ 5. timeautoTest(5) - indicates that the Battery enable timing auto test function
+ 6. offautoTest(6) - indicates that the Battery enable off auto test function
+ 7. timeoffautoTest(7) - indicates that the Battery enable timing+off auto test
+ "
+ ::= { hwBatteryTestEntry 1 }
+
+ hwBatteryTestAutoDischargePeriod OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "day"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Auto discharge test period.
+ Effective range is 30 -240 days.
+ Default: 120
+ Unit: day
+ "
+ DEFVAL { 120 }
+ ::= { hwBatteryTestEntry 2 }
+
+ hwBatteryTestResult OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ testing(1),
+ complete(2),
+ alarmTerminated(3),
+ hostTerminated(4),
+ overtimeTerminated(5),
+ normal(6),
+ supplyRecoverAutotestTerminated(7)
+ }
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Test result:
+ Options:
+ 1. testing(1) - indicates that the Battery test is in operation
+ 2. complete(2) - indicates that the Battery test is completed normally
+ 3. alarmTerminated(3) - indicates that the Battery test is stopped by alarms
+ 4. hostTerminated(4) - indicates that the Battery test is stopped by the host
+ 5. overtimeTerminated(5) - indicates that the Battery test is stopped because of over time
+ 6. normal(6) - indicates that the Battery test is not started
+ 7. supplyRecoverAutotestTerminated(7) - indicates that the Battery test is stopped because of supply recover
+ "
+ ::= { hwBatteryTestEntry 3 }
+
+ hwBatteryTestStartTime OBJECT-TYPE
+ SYNTAX DateAndTime
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "Time of starting test"
+ ::= { hwBatteryTestEntry 4 }
+
+ hwBatteryTestDuration OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "hour"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery discharge test duration .
+ Effective range is 1�C100 hours.
+ Default :value is 10 hours
+ Unit: hour
+ "
+ ::= { hwBatteryTestEntry 5 }
+
+ hwBatteryTestTerminateVoltage OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "mV"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Battery discharge test end voltage.
+ Effective range (DC lack alarm voltage+0.5V�Cvoltage of floating charge).
+ Default: 45600
+ Unit: mV
+ "
+ ::= { hwBatteryTestEntry 6 }
+
+ hwBatteryTestTotalDischargeAH OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "mAH"
+ MAX-ACCESS read-only
+ STATUS obsolete
+ DESCRIPTION
+ "
+ Total discharge AH.
+ Unit: mAH
+ "
+ ::= { hwBatteryTestEntry 7 }
+
+ hwBatteryTestOperStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ autoTestPermit(1),
+ autoTestForbid(2),
+ timeautoTestPermit(3),
+ offautoTestPermit(4),
+ timeoffautoTestPermit(5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ Battery discharge test operate status.
+ Options:
+ 1. autoTestPermit(1) - indicates that auto discharge test is enabled
+ 2. autoTestForbid(2) - indicates that auto discharge test is disabled
+ 3. timeautoTestPermit(3) - indicates that timing auto discharge test is enabled
+ 4. offautoTestPermit(4) - indicates that off auto discharge test is enabled
+ 5. timeoffautoTestPermit(5) - indicates that timing-off auto discharge test is enabled"
+ ::= { hwBatteryTestEntry 8 }
+
+ hwBatteryTestPhase OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ charge(1),
+ discharge(2),
+ record(3),
+ finish(4),
+ waitingfordischarge(5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery test phase.
+ Options:
+ 1. charge(1) - indicates the batter test phase is charge
+ 2. discharge(2) - indicates the batter test phase is discharge
+ 3. record(3) - indicates the power equipment recording test result
+ 4. finish(4) - indicates that the discharge is complete
+ 5.waitingfordischarge(5) - indicates that preparation is ready for discharge command
+ "
+ ::= { hwBatteryTestEntry 9 }
+
+ hwBatteryTestStartHour OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "hour"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Discharge start time.
+ Effective range is 0 23
+ Default: 0
+ Unit: hour
+ "
+ DEFVAL { '0'b }
+ ::= { hwBatteryTestEntry 10 }
+
+ hwBatteryTestAlarmThreshold OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "percent"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The battery discharge test alarm threshold in ratio of the range:1~79."
+ DEFVAL { 70 }
+ ::= { hwBatteryTestEntry 11 }
+
+ hwBatteryLogTestTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwBatteryLogTestEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Battery test result table,
+ Through this table, the discharging test result of the battery group can be saved and queried.
+ The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
+ hwEnvEmuIndex is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwBatteryLogTestIndex is the index of the monitored battery.
+ "
+ ::= { hwBatteryGroup 5 }
+
+ hwBatteryLogTestEntry OBJECT-TYPE
+ SYNTAX HwBatteryLogTestEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Battery test result table,
+ Through this table, the discharging test result of the battery group can be saved and queried.
+ The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
+ hwEnvEmuIndex is the index of the monitored unit.
+ hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ hwBatteryLogTestIndex is the index of the monitored battery.
+ "
+ INDEX { hwEnvEmuIndex, hwPowerIndex, hwBatteryLogTestIndex }
+ ::= { hwBatteryLogTestTable 1 }
+
+ HwBatteryLogTestEntry ::=
+ SEQUENCE {
+ hwBatteryLogTestIndex
+ Integer32,
+ hwBatteryLogTestStartTime
+ DateAndTime,
+ hwBatteryLogTestDischargeDuration
+ Integer32,
+ hwBatteryLogTestTerminateVoltage
+ Integer32,
+ hwBatteryLogTestBatteryStatus
+ INTEGER,
+ hwBatteryLogTestTotalDischargeAH
+ Integer32,
+ hwBatteryLogTestFinish
+ INTEGER,
+ hwBatteryLogTestEfficiency
+ Integer32,
+ hwBatteryLogTestBatteryTemperature
+ Integer32,
+ hwBatteryLogTestBatteryCurrent
+ Integer32
+ }
+
+ hwBatteryLogTestIndex OBJECT-TYPE
+ SYNTAX Integer32 (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery discharge test result index"
+ ::= { hwBatteryLogTestEntry 1 }
+
+ hwBatteryLogTestStartTime OBJECT-TYPE
+ SYNTAX DateAndTime
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery discharge test start time"
+ ::= { hwBatteryLogTestEntry 2 }
+
+ hwBatteryLogTestDischargeDuration OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "minute"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Duration of discharge.
+ Unit: minute"
+ ::= { hwBatteryLogTestEntry 3 }
+
+ hwBatteryLogTestTerminateVoltage OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "mV"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "End voltage of battery discharge test .
+ Unit: mV"
+ ::= { hwBatteryLogTestEntry 4 }
+
+ hwBatteryLogTestBatteryStatus OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ expectant(1),
+ unexpected(2),
+ unknown(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery status.
+ Options:
+ 1. expectant(1) - indicates the batter test state is expectant
+ 2. unexpected(2) - indicates the batter test state is unexpected
+ 3. unknown(3) - indicates the batter test state is unknown
+ "
+ ::= { hwBatteryLogTestEntry 5 }
+
+ hwBatteryLogTestTotalDischargeAH OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "mAH"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ Discharge cumulate AH.
+ Unit: mAH
+ "
+ ::= { hwBatteryLogTestEntry 6 }
+
+ hwBatteryLogTestFinish OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ testing(1),
+ completed(2),
+ alarmTerminated (3),
+ hostTerminated(4),
+ overtimeTerminated(5),
+ notTest(6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery Test result.
+ Options:
+ 1. testing(1) - indicates that it is during testing
+ 2. completed(2) - indicates that the test is completed normally
+ 3. alarmTerminated(3) - indicates that the test is stopped by alarms
+ 4. hostTerminated(4) - indicates that the test is stopped by the host
+ 5. overtimeTerminated(5) - indicates that the test is stopped because of over 100 hours
+ 6. notTest(6) - indicates that the test is not started
+ "
+ ::= { hwBatteryLogTestEntry 7 }
+
+ hwBatteryLogTestEfficiency OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "percent"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ The information of battery test efficiency.
+ "
+ ::= { hwBatteryLogTestEntry 8 }
+
+ hwBatteryLogTestBatteryTemperature OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "0.01 Degree"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery discharge test end Temperature.
+ Unit: 0.01 Degree
+ "
+ ::= { hwBatteryLogTestEntry 9 }
+
+ hwBatteryLogTestBatteryCurrent OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "mA"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery discharge test average Current.
+ Unit: mA
+ "
+ ::= { hwBatteryLogTestEntry 10 }
+
+ hwRemoteProvidePowerInfoTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwRemoteProvidePowerInfoEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Remote provide power basic information table.
+ The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex is the index of the monitored unit,
+ and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ ::= { hwPowerMonObjects 7 }
+
+ hwRemoteProvidePowerInfoEntry OBJECT-TYPE
+ SYNTAX HwRemoteProvidePowerInfoEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Remote provide power basic information table.
+ The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
+ hwEnvEmuIndex is the index of the monitored unit,
+ and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
+ "
+ INDEX { hwEnvEmuIndex,hwPowerIndex }
+ ::= { hwRemoteProvidePowerInfoTable 1 }
+
+ HwRemoteProvidePowerInfoEntry ::=
+ SEQUENCE {
+ hwPowerCentralState
+ INTEGER,
+ hwPowerCentralDCInPutState
+ INTEGER,
+ hwPowerCentralDCOutputState
+ INTEGER,
+ hwPowerCentralDCOutputMode
+ INTEGER,
+ hwPowerRemoteCommState
+ INTEGER,
+ hwPowerRemoteDCInputState
+ INTEGER,
+ hwPowerRemoteLineCurState
+ INTEGER,
+ hwPowerRemotePowerState
+ INTEGER,
+ hwPowerRemoteLineState
+ BITS,
+ hwPowerCentralLoadState
+ INTEGER
+ }
+
+ hwPowerCentralState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ temOver(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of the central module.
+ Options:
+ 1. normal(1) - indicates the normal state
+ 2. temOver(2) - indicates the over-temperature
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 1 }
+
+ hwPowerCentralDCInPutState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ lack(2),
+ over(3)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of central module DC input:
+ Options:
+ 1.normal(1) - indicates the normal state
+ 2.lack(2) - indicates the voltage underflow
+ 3.over(3) - indicates the voltage overflow
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 2}
+
+ hwPowerCentralDCOutputState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ volLack(2),
+ volOver(3),
+ loadOver(4),
+ shortCircuit(5),
+ noLoad(6)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "State of central module DC output.
+ Options:
+ 1. normal(1) - indicates the normal state
+ 2. volLack(2) - indicates the voltage underflow
+ 3. volOver(3) - indicates the voltage overflow
+ 4. loadOver(4) - indicates the over-loading
+ 5. shortCircuit(5) - indicates the short circuit
+ 6. noLoad(6) - indicates no load
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 3 }
+
+ hwPowerCentralDCOutputMode OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ highVolMode(1),
+ lowVolMode(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Mode of central module DC output.
+ Options:
+ 1. highVolMode(1) - indicates the high voltage output mode
+ 2. lowVolMode(2) - indicates the low voltage output mode
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 4 }
+
+ hwPowerRemoteCommState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ revfault(2),
+ sendfault(3)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Remote power module communications state.
+ Options:
+ 1. normal(1) - indicates the normal state
+ 2. revfault(2) - indicates the receiving of fault
+ 3. sendfault(3) - indicates the sending of fault"
+ ::= { hwRemoteProvidePowerInfoEntry 5 }
+
+ hwPowerRemoteDCInputState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ lack(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "State of remote module DC input.
+ Options:
+ 1. normal(1) - indicates the normal state
+ 2. lack(2) - indicates that the voltage is underflow
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 6 }
+
+ hwPowerRemoteLineCurState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ cablejoining(2),
+ curLeakage(3),
+ curOver(4)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "state of line between central and remote module.
+ Options:
+ 1.normal(1) - indicates the normal state
+ 2.cablejoining(2) - indicates the cable joining
+ 3.curLeakage(3) - indicates the cur Leakage
+ 4.curOver(4) - indicates the cur Over
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 7 }
+
+ hwPowerRemotePowerState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ fault(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "state of remote UA60 power.
+ Options:
+ 1. normal(1) - indicates the normal state
+ 2. fault(2) - indicates the faulty state
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 8 }
+
+ hwPowerRemoteLineState OBJECT-TYPE
+ SYNTAX BITS
+ {
+ u1state(0),
+ u2state(1),
+ u3state(2),
+ u4state(3),
+ a1state(4),
+ a2state(5),
+ a3state(6),
+ a4state(7)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "State of line U1.
+ Options:
+ 1. u1state(0) - indicates the power remote line state is u1 state
+ 2. u2state(1) - indicates the power remote line state is u2 state
+ 3. u3state(2) - indicates the power remote line state is u3 state
+ 4. u4state(3) - indicates the power remote line state is u4 state
+ 5. a1state(4) - indicates the power remote line state is a1 state
+ 6. a2state(5) - indicates the power remote line state is a2 state
+ 7. a3state(6) - indicates the power remote line state is a3 state
+ 8. a4state(7) - indicates the power remote line state is a4 state
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 9 }
+
+ hwPowerCentralLoadState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(1),
+ overload(2),
+ nonload(3)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "state of central load.
+ Options:
+ 1. normal(1) - indicates the normal state
+ 2. overload(2) - indicates overload
+ 3. nonload(3) - indicates non-load
+ "
+ ::= { hwRemoteProvidePowerInfoEntry 10 }
+
+
+ hwPowerMibTrap OBJECT IDENTIFIER ::= { hwPower 2 }
+
+ hwPowerTrapOid OBJECT IDENTIFIER ::= { hwPowerMibTrap 1 }
+
+ hwPowerTrapsDefine OBJECT IDENTIFIER ::= { hwPowerMibTrap 2 }
+
+ hwPowerTraps OBJECT IDENTIFIER ::= { hwPowerTrapsDefine 0 }
+
+ powerConnFaultAlarm NOTIFICATION-TYPE
+ OBJECTS {hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ " This trap message is reported when the communication between
+ the power module and the monitoring board is fault."
+ ::= { hwPowerTraps 1 }
+
+ powerConnFaultAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the communication between
+ the power module and the monitoring board resumes."
+ ::= { hwPowerTraps 2 }
+
+ acInputVoltageAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when there is a exception of AC input voltage."
+ ::= { hwPowerTraps 3 }
+
+ acInputVoltageAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the state of AC input voltage resumes."
+ ::= { hwPowerTraps 4 }
+
+ acInputVoltageHighAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the input voltage is too high."
+ ::= { hwPowerTraps 5 }
+
+ acInputVoltageHighAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the input voltage
+ resumes to the normal range from a high value."
+ ::= { hwPowerTraps 6 }
+
+ acInputVoltageLowAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the input voltage is too low."
+ ::= { hwPowerTraps 7 }
+
+ acInputVoltageLowAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the input voltage
+ resumes to the normal range from a low value."
+ ::= { hwPowerTraps 8 }
+
+ dcOutputVoltageHighAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the output voltage is too high."
+ ::= { hwPowerTraps 9 }
+
+ dcOutputVoltageHighAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the output voltage
+ resumes to the normal range from a high value."
+ ::= { hwPowerTraps 10 }
+
+ dcOutputCurrentHighAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the output current is too high."
+ ::= { hwPowerTraps 11 }
+
+ dcOutputCurrentHighAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the output current
+ resumes to the normal range from a high value."
+ ::= { hwPowerTraps 12 }
+
+ dcOutputVoltageLowAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the output voltage is too low."
+ ::= { hwPowerTraps 13 }
+
+ dcOutputVoltageLowAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the output voltage
+ resumes to the normal range from a low value."
+ ::= { hwPowerTraps 14 }
+
+ dcOutputCurrentLowAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the output current is too low."
+ ::= { hwPowerTraps 15 }
+
+ dcOutputCurrentLowAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the output current
+ resumes to the normal range from a low value."
+ ::= { hwPowerTraps 16 }
+
+ overLoadPowerAbnormalAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the state of load power is abnormal."
+ ::= { hwPowerTraps 17 }
+
+ overLoadPowerAbnormalAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the state of load power recovers to normal."
+ ::= { hwPowerTraps 18 }
+
+ overBattPowerOffAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the battery is powered off."
+ ::= { hwPowerTraps 19 }
+
+ overBattPowerOffAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the battery is powered on."
+ ::= { hwPowerTraps 20 }
+
+ overLoadPowerOffAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the loadpower is powered off."
+ ::= { hwPowerTraps 21 }
+
+ overLoadPowerOffAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the loadpower is powered on."
+ ::= { hwPowerTraps 22 }
+
+ acMainsSupplyAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the AC mains supply is abnormal."
+ ::= { hwPowerTraps 23 }
+
+ acMainsSupplyAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the AC mains supply recovers to normal."
+ ::= { hwPowerTraps 24 }
+
+ batteryLoopAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the loop of battery group disconnects."
+ ::= { hwPowerTraps 25 }
+
+ batteryLoopAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the loop of battery group connects."
+ ::= { hwPowerTraps 26 }
+
+ batteryFuseAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the fuse of battery group disconnects."
+ ::= { hwPowerTraps 27 }
+
+ batteryFuseAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the fuse of battery group connects. "
+ ::= { hwPowerTraps 28 }
+
+ batteryContachAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the contactor of battery group disconnects."
+ ::= { hwPowerTraps 29 }
+
+ batteryContachAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the contactor of battery group connects."
+ ::= { hwPowerTraps 30 }
+
+ userModuleOffAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the user module is powered off."
+ ::= { hwPowerTraps 31 }
+
+ userModuleOffAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the user module is powered on."
+ ::= { hwPowerTraps 32 }
+
+ transferModuleOffAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the transfer module is powered off."
+ ::= { hwPowerTraps 33 }
+
+ transferModuleOffAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the transfer module is powered on."
+ ::= { hwPowerTraps 34 }
+
+ userModuleSwitchAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the user module is switched off."
+ ::= { hwPowerTraps 35 }
+
+ transferModuleSwitchAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the transfer module is switched off."
+ ::= { hwPowerTraps 37 }
+
+ loadFuseAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the load fuse is abnormal."
+ ::= { hwPowerTraps 39 }
+
+ loadFuseAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the load fuse resumes."
+ ::= { hwPowerTraps 40 }
+
+ chargeCtrlStateAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the control state of average or floating charge converts."
+ ::= { hwPowerTraps 41 }
+
+ chargeModeAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the charge state converts."
+ ::= { hwPowerTraps 42 }
+
+ acCommFailAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the AC panel communication fails."
+ ::= { hwPowerTraps 43 }
+
+ acCommFailAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the AC panel communication resumes."
+ ::= { hwPowerTraps 44 }
+
+ batteryChargeOverAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the Over-current of battery group happens."
+ ::= { hwPowerTraps 45 }
+
+ batteryChargeOverAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "OThis trap message is reported when the Over-current of battery group resumes."
+ ::= { hwPowerTraps 46 }
+
+ batteryVoltageLackAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the voltage of battery group lacks."
+ ::= { hwPowerTraps 47 }
+
+ batteryVoltageLackAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the voltage of battery group recovers from lack."
+ ::= { hwPowerTraps 48 }
+
+ loadTwiceOffAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the load is powered off twice."
+ ::= { hwPowerTraps 49 }
+
+ loadTwiceOffAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the load recovers from powering off twice."
+ ::= { hwPowerTraps 50 }
+
+ loadOnceOffAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the load is powered off once."
+ ::= { hwPowerTraps 51 }
+
+ loadOnceOffAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the load recovers from powering off once."
+ ::= { hwPowerTraps 52 }
+
+ acInputPowerOffAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the AC input is powered off."
+ ::= { hwPowerTraps 53 }
+
+ acInputPowerOffAlarmResume NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the AC input power is powered off."
+ ::= { hwPowerTraps 54 }
+
+ acInputLoopSwtichAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the AC input loop switches to another one."
+ ::= { hwPowerTraps 55 }
+
+ batteryDischargeTestStartAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the battery discharge test starts."
+ ::= { hwPowerTraps 56 }
+
+ batteryDischargeTestStopAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the battery discharge test stops."
+ ::= { hwPowerTraps 57 }
+
+ powerProtectAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the power protection function is enbaled."
+ ::= { hwPowerTraps 58 }
+
+ powerUndoProtectAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the power protection function is disabled."
+ ::= { hwPowerTraps 59 }
+
+ powerCentralOutputModeSwtichAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the central output mode swtiches to another one."
+ ::= { hwPowerTraps 60 }
+
+ powerCentralTempretaureAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the central tempretaure is abnormal."
+ ::= { hwPowerTraps 61 }
+
+ powerCentralInputAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the central input voltage is abnormal."
+ ::= { hwPowerTraps 62 }
+
+ powerCentralOutputAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the central output voltage is abnormal."
+ ::= { hwPowerTraps 63 }
+
+ powerRemoteCommFaultAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the communiction between the remote and central fails."
+ ::= { hwPowerTraps 64 }
+
+ powerRemoteVoltageAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the remote voltage is abnormal."
+ ::= { hwPowerTraps 65}
+
+ powerLineAlarm NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the power line is abnormal."
+ ::= { hwPowerTraps 66 }
+
+ powerRemotePowerAlarm1 NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the remote power is abnormal."
+ ::= { hwPowerTraps 67 }
+
+ powerRemotePowerAlarm2 NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the Line UA is abnormal."
+ ::= { hwPowerTraps 68 }
+
+ powerRemotePowerAlarm3 NOTIFICATION-TYPE
+ OBJECTS { hwEnvEmuIndex, hwPowerIndex }
+ STATUS current
+ DESCRIPTION
+ "This trap message is reported when the Central load is abnormal."
+ ::= { hwPowerTraps 69 }
+
+ hwACInfomationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HwACInfomationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "AC infomation table. The table is not supported.
+ The indexes of this table are hwEnvEmuIndex and hwPowerIndex."
+ ::= { hwPowerMonObjects 8 }
+
+ hwACInfomationEntry OBJECT-TYPE
+ SYNTAX HwACInfomationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "AC infomation table. The table is not supported.
+ The indexes of this entry are hwEnvEmuIndex and hwPowerIndex."
+ INDEX { hwEnvEmuIndex, hwPowerIndex }
+ ::= { hwACInfomationTable 1 }
+
+ HwACInfomationEntry ::=
+ SEQUENCE {
+ hwACInfoCommState
+ INTEGER,
+ hwACInfoThunderState
+ INTEGER,
+ hwACInfoCurrentLoop
+ Integer32,
+ hwACInfoMCBTrigger
+ INTEGER,
+ hwACInfoFrequency
+ Integer32,
+ hwACInfoRowStatus
+ RowStatus
+ }
+
+ hwACInfoCommState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(0),
+ fault(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "communication state of AC input module.
+ The node is not supported.
+ Options:
+ 1. normal(0) - indicates the communication state of AC is normal
+ 2. fault(1) - indicates the communication state of AC is fault
+ "
+ ::= { hwACInfomationEntry 1 }
+
+ hwACInfoThunderState OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(0),
+ fault(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Thunder's state.
+ The node is not supported.
+ Options:
+ 1. normal(0) - indicates the state of Thunder is normal
+ 2. fault(1) - indicates the state of Thunder is fault
+ "
+ ::= { hwACInfomationEntry 2 }
+
+ hwACInfoCurrentLoop OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Current AC input working loop.
+ The leaf is not supported.
+ "
+ ::= { hwACInfomationEntry 3 }
+
+ hwACInfoMCBTrigger OBJECT-TYPE
+ SYNTAX INTEGER
+ {
+ normal(0),
+ break-down(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "AC input MCB trigger state.
+ The leaf is not supported.
+ Options:
+ 1. normal(0) - indicates the AC input MCB trigger state is normal
+ 2. break-down(1)- indicates the AC input MCB trigger state is break-down
+ "
+ ::= { hwACInfomationEntry 4 }
+
+ hwACInfoFrequency OBJECT-TYPE
+ SYNTAX Integer32
+ UNITS "HZ"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The infomation of AC input frequency.
+ This leaf is not supported.
+ Unit: HZ
+ "
+ ::= { hwACInfomationEntry 5 }
+
+ hwACInfoRowStatus OBJECT-TYPE
+ SYNTAX RowStatus
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "RowStatus standard operation
+ The leaf is not supported.
+ "
+ ::= { hwACInfomationEntry 6 }
+
+ powerConformance OBJECT IDENTIFIER ::= { hwPower 3 }
+
+ powerCompliances OBJECT IDENTIFIER ::= { powerConformance 1 }
+
+ powerGroups OBJECT IDENTIFIER ::= { powerConformance 2 }
+
+ hwEnvironPowerTraps OBJECT IDENTIFIER ::= { hwPower 4 }
+
+ hwEnvironPowerCommonTraps OBJECT IDENTIFIER ::= { hwEnvironPowerTraps 1 }
+
+ hwEnvironPowerAlarmTraps OBJECT IDENTIFIER ::= { hwEnvironPowerTraps 2 }
+
+ hwEnvironPowerAlarmTrapsPrefix OBJECT IDENTIFIER ::= { hwEnvironPowerAlarmTraps 0 }
+
+ hwEmmPowerBattaryTestStartTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ device battary discharge test starts.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 1 }
+
+ hwEmmPowerBattaryTestStopTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType,
+ hwBatteryLogTestBatteryStatus,
+ hwBatteryLogTestEfficiency
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ device battary discharge test ends.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 2 }
+
+ hwEmmPowerAcvolFaultTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwACLoopIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ device AC input voltage is abnormal.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 3 }
+
+ hwEmmPowerAcvolRecoverTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwACLoopIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ device AC input voltage recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 4 }
+
+ hwEmmPowerDcvolFaultTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ device DC output voltage is abnormal.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 5 }
+
+ hwEmmPowerDcvolRecoverTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ device DC output voltage recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 6 }
+
+ hwEmmPowerBattloopFaultTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwBatteryIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ device the battery loop is broken.
+ In this case, the function of he backup power is lost.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 7 }
+
+ hwEmmPowerBattloopRecoverTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwBatteryIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ device battery loop recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 8 }
+
+ hwEmmPowerLoadfuseFaultTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwLoadIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the fuse of the power device
+ is broken. In this case, the device is powered off.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 9 }
+
+ hwEmmPowerLoadfuseRecoverTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwLoadIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the fuse of the power
+ device recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 10 }
+
+ hwEmmPowerRectifierFaultTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwRectifierIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the rectifier
+ module of the power device is abnormal and the spully power may decrease.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 11 }
+
+ hwEmmPowerRectifierRecoverTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwRectifierIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the rectifier module of the
+ power device recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 12 }
+
+ hwEmmDigMainsupplyFaultTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwDigChannelIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ main supply digital is faulty.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 13 }
+
+ hwEmmDigMainsupplyRecoverTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwDigChannelIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ main supply digital recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 14 }
+
+ hwEmmPowerBatteryOffTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ of battary is off.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 15 }
+
+ hwEmmBatt1TempFaultTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ battery group 1 temperature sensor fault
+ occurs.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 16 }
+
+ hwEmmBatt1TempRestoreTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ battery group 1 temperature sensor fault
+ recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 17 }
+
+ hwEmmEnviHumFaultTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ environment humidity sensor fault occurs.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 18 }
+
+ hwEmmEnviHumRestoreTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ environment humidity sensor fault recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 19 }
+
+ hwEmmEnvi1TempFaultTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ environment 1 temperature sensor fault
+ occurs.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 20 }
+
+ hwEmmEnvi1TempRestoreTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ environment 1 temperature sensor fault
+ recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 21 }
+
+ hwEmmBattTemFaultTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the battery
+ temperature out of normal range.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 22 }
+
+ hwEmmBattTemRecoverTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the battery
+ temperature recovers to normal range.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 23 }
+
+ hwEmmPowerBatteryOffRecoverTrap NOTIFICATION-TYPE
+ OBJECTS {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power
+ of battary recovers to on state.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 24 }
+
+ hwEmmPowerBatteryUnDetectTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ one or more batteries are not detected.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 25 }
+
+ hwEmmPowerBatteryDetectRecoverTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ batteries recover.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 26 }
+
+ hwPowerModuleMismatchTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the
+ the power supply system detects mismatched power module .
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 27 }
+
+ hwPowerModuleRestoreTrap NOTIFICATION-TYPE
+ OBJECTS
+ {
+ hwFrameIndex,
+ hwEnvEmuIndex,
+ hwPowerIndex,
+ hwEnvEmuType,
+ hwPowerType
+ }
+ STATUS current
+ DESCRIPTION
+ "The agent generates this trap when the power module recovers.
+ "
+ ::= { hwEnvironPowerAlarmTrapsPrefix 28 }
+END