diff --git a/MIBS/eltek/ELTEK-BC2000-DC-POWER-MIB b/MIBS/eltek/ELTEK-BC2000-DC-POWER-MIB new file mode 100644 index 0000000..4a68786 --- /dev/null +++ b/MIBS/eltek/ELTEK-BC2000-DC-POWER-MIB @@ -0,0 +1,3795 @@ +ELTEK-BC2000-DC-POWER-MIB DEFINITIONS ::= BEGIN
+
+ IMPORTS
+ MODULE-IDENTITY
+ , OBJECT-TYPE
+ , NOTIFICATION-TYPE
+ , OBJECT-IDENTITY
+ , Counter32
+ , Gauge32
+ , Integer32
+ , enterprises
+ , IpAddress
+ -- , Gauge
+ FROM SNMPv2-SMI
+
+ Gauge
+ FROM RFC1155-SMI
+
+ DisplayString
+ , TimeStamp
+-- , TimeInterval
+-- , TestAndIncr
+ , AutonomousType
+ , TEXTUAL-CONVENTION
+ FROM SNMPv2-TC
+
+-- MODULE-COMPLIANCE
+-- , OBJECT-GROUP
+-- FROM SNMPv2-CONF
+
+-- sysUpTime
+-- FROM RFC1213-MIB
+ ;
+
+ --
+ -- date and time in UTC format YYYYMMDDHHmmZ
+ --
+ eltek MODULE-IDENTITY
+ LAST-UPDATED "201403271038Z"
+ ORGANIZATION "Eltek Inc."
+ CONTACT-INFO
+ "Contact: Eltek Customer Support
+ Postal: 2925 E. Plano Pkwy
+ Plano, TX-75074
+ Web: http://www.eltek.com
+ email: techsupport.us@eltek.com
+ Phone 800-435-4872
+ "
+ DESCRIPTION
+ "SNMP access to Eltek DC Power systems through the BC2000 controller."
+ REVISION "201403271038Z"
+ DESCRIPTION
+ " Need History here.
+ MIB Version 2.10
+ Final edits to PM (was TRIO) table (branch 17)
+ MIB Version 2.00
+ Synchronized with new release
+ MIB Version 0.97
+ Updated contact information
+ MIB Version 0.96
+ Changed LVD Timers to read-only. Write not supported in this release
+ MIB Version 0.95
+ Traps 70-72 added
+ Changed vpwrPMIndex variable to non negative integer
+ MIB Version 0.94
+ Fixed module inventory process
+ Removed unused module test groups
+ Removed unused thermal probe entries
+ Changed vpwrBoostDuration from Hours to Seconds
+ New traps 63-69 added, trap 99 unknown added
+ Corrected Ringer present MIB
+ MIB Version 0.93
+ Fixed spelling of vpwrBatteryCurrentCapacity
+ Fixed spelling of vpwrRingerAlarmAFailed
+ Fixed spelling of vpwrRingerAlarmBFailed
+ Fixed message with vpwrRingerAlarmBOverTemp
+ Fixed message with vpwrRingerAlarmBOverCurrent
+ Changed Centigrade to Celsius
+ Changed use of battety to battery throughout
+ Changed vpwrBDTDuration from 480 minutes to 1080
+ Updated settable ringer parameters
+ Spelling corrections
+ MIB Version 0.92
+ Fixed duplicate usage of vpwrTrapsMsgString
+ Fixed spelling of Gauge data type
+ MIB Version 0.91
+ Version 2 Traps
+ MIB Version 0.9
+ Sept 1, 06
+ New Table- System Alarm History
+ New Table- for BDT Result History
+ New Table- for AVESTOR Battery
+
+ New Traps -
+ Aux Alarm Source
+ Distribution Alarm Source
+ Battery Capacity Alarm
+ Battery Alarm Source
+ Battery SOC Trap
+ Battery SOH Trap
+ AC Fail Duration Trap
+ Battery Operational mode change
+
+ MIB Version 0.8
+ Add table to retrieve module inventory info
+ MIB Version 0.7
+ Dec 1, 05
+ Fixed HP Openview error
+ Fixed warnings generated by MG-SOFT
+ Add table to retrieve rectifier inventory info
+ MIB Version 0.6
+ Feb 10, 2004 Added additional traps.
+ Defined Ringers and other modules.
+ Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable
+ Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry
+ This fixes errors generated by MG-SOFT mib compiler.
+ Oct 30, 2002 initial release - version 0.4
+ "
+
+ ::= {enterprises 13858}
+
+PositiveInteger ::= TEXTUAL-CONVENTION
+ DISPLAY-HINT "d"
+ STATUS current
+ DESCRIPTION
+ "This data type is a non-zero and non-negative value."
+ SYNTAX Integer32 (1..2147483647)
+
+NonNegativeInteger ::= TEXTUAL-CONVENTION
+ DISPLAY-HINT "d"
+ STATUS current
+ DESCRIPTION
+ "This data type is a non-negative value."
+ SYNTAX Integer32 (0..2147483647)
+
+GenericEnableDisableTC ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "The defines how was BDT started."
+ SYNTAX INTEGER {
+ disabled(0),
+ enabled(1)
+ }
+
+SysInputValue ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "These are the results of the system input value definitions."
+ SYNTAX INTEGER {
+ disabled(-127),
+ removed(-126),
+ shorted(-125),
+ auxAlarm(-124),
+ auxNormal(-123),
+ distAlarm(-122),
+ distNormal(-121),
+ undefined(255)
+ -- (0..127)
+ }
+
+-- BatteryOperModeTC ::= TEXTUAL-CONVENTION
+-- STATUS current
+-- DESCRIPTION
+-- "The defines operational mode enumerations for the battery."
+-- SYNTAX INTEGER {
+-- batModeStandby (0),
+-- batModeCharging(1),
+-- batModeFloating(2),
+-- batModeDischarging(3),
+-- batModeNotAvailable(255)
+-- }
+
+VpwrPMCnfgValue ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "These are the results of the system input value definitions."
+ SYNTAX INTEGER {
+ disabled(0),
+ tProbe(1),
+ auxNO(2),
+ auxNC(3),
+ distNO(4),
+ distNC(5),
+ undefined(255)
+ }
+
+
+-- BatteryOperStatusTC ::= TEXTUAL-CONVENTION
+-- STATUS current
+-- DESCRIPTION
+-- "The defines operational mode
+-- enumerations for the battery."
+-- SYNTAX INTEGER {
+-- batStatusOk (0),
+-- batStatusMinorFault(1),
+-- batStatusMajorFault(2),
+-- batStatusNotAvailable(255)
+-- }
+
+
+BDTStartSourceTC ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "The defines how was BDT started."
+ SYNTAX INTEGER {
+ bdtInactive(0),
+ bdtManualStart(1),
+ bdtSched01Start1(2),
+ bdtSched02Start2(3),
+ bdtSched03Start3(4),
+ bdtSched04Start4(5),
+ bdtSched05Start5(6),
+ bdtSched06Start6(7),
+ bdtSched07Start7(8),
+ bdtSched08Start8(9),
+ bdtSched09Start9(10),
+ bdtSched10Start10(11),
+ bdtSched11Start11(12),
+ bdtSched12Start12(13),
+ bdtACFailStart(14)
+ }
+BDTResultTC ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION
+ "The defines how was BDT started."
+ SYNTAX INTEGER {
+ bdtResultCleared(0),
+ bdtResultPassed(1),
+ bdtResultFailed(2),
+ bdtResultStopped(3),
+ bdtResultAborted(4),
+ bdtResultInProgress(5)
+ }
+
+
+-- vpwrDcPowerProducts OBJECT IDENTIFIER ::= { eltek 1 }
+ vpwrDcPowerSystem OBJECT IDENTIFIER ::= { eltek 2 }
+ vpwrDcPowerRectifier OBJECT IDENTIFIER ::= { eltek 3 }
+ vpwrDcPowerLvd OBJECT IDENTIFIER ::= { eltek 4 }
+-- vpwrDcPowerTest OBJECT IDENTIFIER ::= { eltek 5 }
+ vpwrDcPowerModuleIdent OBJECT IDENTIFIER ::= { eltek 6 }
+ vpwrDcPowerBatteryGroup OBJECT IDENTIFIER ::= { eltek 7 }
+ vpwrDcPowerAlarmGroup OBJECT IDENTIFIER ::= { eltek 8 }
+ vpwrDcPowerSnmpConfig OBJECT IDENTIFIER ::= { eltek 9 }
+ vpwrDcPowerTraps OBJECT IDENTIFIER ::= { eltek 10 }
+ vpwrDcPowerTrapVars OBJECT IDENTIFIER ::= { eltek 11 }
+
+ vpwrDcPowerRinger OBJECT IDENTIFIER ::= { eltek 12 }
+ vpwrDcPowerDcDcConverter OBJECT IDENTIFIER ::= { eltek 13 }
+ vpwrDcPowerDcAcInverter OBJECT IDENTIFIER ::= { eltek 14 }
+ vpwrDcPowerAcLineModule OBJECT IDENTIFIER ::= { eltek 15 }
+ vpwrDcPowerIoModule OBJECT IDENTIFIER ::= { eltek 16 }
+
+ vpwrDcPowerPMModule OBJECT IDENTIFIER ::= { eltek 17 }
+ vpwrDcPowerDistModule OBJECT IDENTIFIER ::= { eltek 18 }
+ vpwrDcPowerBattery OBJECT IDENTIFIER ::= { eltek 19 }
+ vpwrDcPowerController OBJECT IDENTIFIER ::= { eltek 20 }
+ vpwrDcPowerUnkModule OBJECT IDENTIFIER ::= { eltek 499 }
+ thirdPartyProduct OBJECT IDENTIFIER ::= { eltek 500 }
+
+-- vpwrDcPowerTraps OBJECT IDENTIFIER ::= { vpwrDcPowerTrapsRoot 0 }
+
+ vpwrSystemIdentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 1 }
+ vpwrSystemConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 2 }
+ vpwrSystemParameterGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 3 }
+ vpwrSystemPanelIdentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 4 }
+ vpwrSystemHistoryGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 5 }
+ vpwrSystemAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 6 }
+
+ vpwrLvdConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 1 }
+-- vpwrLvdAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 2 }
+-- vpwrLvdTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 3 }
+
+ vpwrRectifierConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 1 }
+ vpwrRectifierAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 2 }
+-- vpwrRectifierTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 3 }
+
+ vpwrBatteryTempGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 1 }
+ vpwrBatteryCurrentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 2 }
+ vpwrBatteryBoostGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 3 }
+ vpwrBatteryDischargeTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 4 }
+
+-- vpwrTrapsMsgString OBJECT IDENTIFIER ::= { vpwrDcPowerTrapVars 1 }
+
+ vpwrRingerConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 1 }
+ vpwrRingerAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 2 }
+ vpwrRingerTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 3 }
+
+ vpwrDcDcConverterConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 1 }
+ vpwrDcDcConverterAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 2 }
+ vpwrDcDcConverterTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 3 }
+
+
+ vpwrDcAcInverterConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 1 }
+ vpwrDcAcInverterAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 2 }
+ vpwrDcAcInverterTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 3 }
+
+ vpwrAcLineModuleConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 1 }
+ vpwrAcLineModuleAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 2 }
+ vpwrAcLineModuleTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 3 }
+
+ vpwrIoModuleConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 1 }
+ vpwrIoModuleAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 2 }
+ vpwrIoModuleTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 3 }
+
+-- vpwrTrioModuleConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerTrioModule 1 }
+ vpwrPMModuleAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerPMModule 4 }
+ vpwrPMModuleTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerPMModule 5 }
+
+--
+-- PM variables
+--
+
+--
+-- Trap variables
+--
+
+ vpwrTrapsMsgString OBJECT-TYPE
+ SYNTAX DisplayString(SIZE (0..127))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Place holder for trap notification message string"
+ ::= { vpwrDcPowerTrapVars 1 }
+
+ vpwrTrapUserIpAddress OBJECT-TYPE
+ SYNTAX IpAddress
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "Place holder for IP address of the user accessing the system"
+ ::= { vpwrDcPowerTrapVars 2}
+
+ vpwrTrapAcfDuration OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Place holder for duration."
+ ::= { vpwrDcPowerTrapVars 3}
+
+ vpwrAlarmingSubModuleBitMap OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "indices of alarming sources are encoded as a bit-map
+ e.g.,
+ source 1 and source 2 will be encoded as hex 3.
+ source 1 and 3 will be encoded as hex 5.
+ "
+ ::= { vpwrDcPowerTrapVars 4 }
+
+ vpwrBatteryCurrentCapacity OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Place holder for total battery capacity"
+ ::= { vpwrDcPowerTrapVars 5 }
+
+ vpwrAlarmingModuleIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "index of alarming module.
+ "
+ ::= { vpwrDcPowerTrapVars 6 }
+ vpwrAlarmingModuleOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "It indicates the type of the module by specifiying its OID"
+ ::= { vpwrDcPowerTrapVars 7}
+
+ vpwrAlarmingModuleBitMap OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "indices of alarming sources are encoded as a bit-map
+ e.g.,
+ source 1 and source 2 will be encoded as hex 3.
+ source 1 and 3 will be encoded as hex 5.
+ "
+ ::= { vpwrDcPowerTrapVars 8 }
+
+ vpwrBatteryRemainingTime OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Place holder for remaining battery
+ time at the current load
+ "
+ ::= { vpwrDcPowerTrapVars 9 }
+ --
+ -- The Identification group.
+ --
+
+
+ vpwrIdentManufacturer OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The name of the DC Power manufacturer."
+ ::= { vpwrSystemIdentGroup 1 }
+
+
+ vpwrIdentModel OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The DC Power Model designation."
+ ::= { vpwrSystemIdentGroup 2 }
+
+ vpwrIdentControllerVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The hardware/firmware version(s). This variable
+ may or may not have the same value as
+ vpwrIdentAgentSoftwareVersion."
+ ::= { vpwrSystemIdentGroup 3 }
+
+ vpwrIdentAgentSoftwareVersion OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (0..15))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The SNMP agent software version. This variable may or
+ may not have the same value as
+ vpwrIdentControllerVersion."
+ ::= { vpwrSystemIdentGroup 4 }
+
+ vpwrIdentName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE(0..31))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A string identifying the system. This object should be
+ set by the administrator."
+ ::= { vpwrSystemIdentGroup 5 }
+
+ --
+ -- The System Identifier group.
+ -- All objects in this group are read-only. It describes
+ -- various modules (rectifiers, converters, ringers, LVDs, etc.) that make up
+ -- the power system and are inserted into a shelf(.1) or panel(.2)
+ --
+ vpwrSystemIdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrSystemIdentEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ " This table describes shelves and modules
+ that make up the sysetm.
+ "
+ ::= { vpwrSystemIdentGroup 6 }
+
+ --
+ -- The System Identifier Entry. Defines the sequence for module tables.
+ --
+ vpwrSystemIdentEntry OBJECT-TYPE
+ SYNTAX VpwrSystemIdentEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular alarm."
+ INDEX { vpwrBayIndex, vpwrModuleIndex }
+ ::= { vpwrSystemIdentTable 1 }
+
+
+ VpwrSystemIdentEntry ::= SEQUENCE {
+ vpwrBayIndex PositiveInteger,
+ vpwrModuleIndex PositiveInteger,
+ vpwrModuleOID OBJECT IDENTIFIER ,
+ vpwrModuleCurrent INTEGER ,
+ vpwrModuleOperStatus INTEGER ,
+ vpwrModuleCapacity INTEGER
+ }
+
+ --
+ -- The System Shelf Identifier group.
+ --
+ -- vpwrShelfIdentEntry OBJECT-TYPE
+ -- SYNTAX VpwrSystemIdentEntry
+ -- MAX-ACCESS not-accessible
+ -- STATUS current
+ -- DESCRIPTION
+ -- "An entry containing information applicable to a
+ -- particular module making up the system."
+ -- INDEX { vpwrBayIndex, vpwrModuleIndex }
+ -- ::= { vpwrSystemIdentTable 1 }
+ --
+ vpwrBayIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Identifies shelf number that this module belongs to.
+ The possible values are 1 through 16 limited by vpwrSystemShelfCapacity."
+ ::= { vpwrSystemIdentEntry 1 }
+
+ vpwrModuleIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object identifies the module by its position in the shelf.
+ Module numbering is left to right starting with module 1. So, the
+ module in the first slot has an index of 1, the next module is 2 and
+ so on."
+ ::= { vpwrSystemIdentEntry 2 }
+
+ vpwrModuleOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "It indicates the type of the module by specifiying its OID"
+ ::= { vpwrSystemIdentEntry 3}
+
+ vpwrModuleCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The meaning of this object depends upon the module type
+ which is indicated by vpwrModuleOID as follows
+ - Current for Rectifier module in centiamps.
+ - Not Applicable for LVD module
+ "
+ ::= { vpwrSystemIdentEntry 4}
+
+ vpwrModuleOperStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ moduleStatusOK(0),
+ moduleStatusAlarm(1),
+ moduleStatusDisabled(2),
+ moduleStatusRingerAOn(3),
+ moduleStatusRingerBOn(4),
+ moduleStatusUnknown(5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object indicates current over all status of the module."
+ ::= { vpwrSystemIdentEntry 5}
+
+ vpwrModuleCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The meaning of this object depends upon the module type
+ which is indicated by vpwrModuleOID as follows
+ - Capacity for Rectifier module.
+ - Not Applicable for LVD module
+ "
+ ::= { vpwrSystemIdentEntry 6}
+
+
+
+ --
+ -- The System Panel Identifier group.
+ --
+
+ vpwrPanelStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrPanelStatusEntrySEQ
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ " This table describes shelves and modules
+ that make up the panels.
+ "
+ ::= { vpwrSystemPanelIdentGroup 1 }
+
+ vpwrPanelStatus OBJECT-TYPE
+ SYNTAX VpwrPanelStatusEntrySEQ
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular panel making up the system."
+ INDEX { vpwrPanelStatusIndex, vpwrPanelStatusModuleIndex }
+ ::= { vpwrPanelStatusTable 1 }
+
+ VpwrPanelStatusEntrySEQ ::= SEQUENCE {
+ vpwrPanelStatusIndex PositiveInteger,
+ vpwrPanelStatusModuleIndex PositiveInteger,
+ vpwrPanelStatusModuleOID OBJECT IDENTIFIER ,
+ vpwrPanelStatusModuleCurrent INTEGER ,
+ vpwrpanelStatusModuleOperStatus INTEGER ,
+ vpwrPanelStatusModuleCapacity INTEGER
+ }
+
+ vpwrPanelStatusIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Identifies panel number that this module belongs to.
+ The possible values are 1 through 8, starting from the top."
+ ::= { vpwrPanelStatus 1 }
+
+ vpwrPanelStatusModuleIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object identifies the module within the panel.
+ The orentation of modules within the panel is mappable."
+ ::= { vpwrPanelStatus 2 }
+
+ vpwrPanelStatusModuleOID OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The module OID."
+ ::= { vpwrPanelStatus 3}
+
+ vpwrPanelStatusModuleCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The current measured by the device (if applicable). LVD current reported in deciAmps.
+ "
+ ::= { vpwrPanelStatus 4}
+
+ vpwrpanelStatusModuleOperStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ moduleStatusOK(0),
+ moduleStatusAlarm(1),
+ moduleStatusDisabled(2),
+ moduleStatusRingerAOn(3),
+ moduleStatusRingerBOn(4),
+ moduleStatusUnknown(5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object indicates current over all status of the module."
+ ::= { vpwrPanelStatus 5}
+
+ vpwrPanelStatusModuleCapacity OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The maximum capacity of the module (if applicable)."
+ ::= { vpwrPanelStatus 6}
+
+
+ vpwrPanelIdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrPanelIdentEntrySEQ
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ " This table describes shelves and modules
+ that make up the panels.
+ "
+ ::= { vpwrSystemPanelIdentGroup 2 }
+
+
+
+ vpwrPanelIdentEntry OBJECT-TYPE
+ SYNTAX VpwrPanelIdentEntrySEQ
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular panel making up the system."
+ INDEX { vpwrPanelIndex, vpwrPanelModuleIndex }
+ ::= { vpwrPanelIdentTable 1 }
+
+
+
+
+ VpwrPanelIdentEntrySEQ ::= SEQUENCE {
+ vpwrPanelIndex PositiveInteger,
+ vpwrPanelModuleIndex PositiveInteger,
+ vpwrPanelModuleSerNum OBJECT IDENTIFIER ,
+ vpwrPanelModuleModelName OBJECT IDENTIFIER ,
+ vpwrPanelModuleFWVer OBJECT IDENTIFIER ,
+ vpwrPanelModuleTestDate INTEGER
+ }
+
+ vpwrPanelIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Identifies panel number that this module belongs to.
+ The possible values are 1 through 8, starting from the top."
+ ::= { vpwrPanelIdentEntry 1 }
+
+ vpwrPanelModuleIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object identifies the module within the panel.
+ The orentation of modules within the panel is mappable."
+ ::= { vpwrPanelIdentEntry 2 }
+
+ vpwrPanelModuleSerNum OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The module serial number."
+ ::= { vpwrPanelIdentEntry 3}
+
+ vpwrPanelModuleModelName OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The model name of the device."
+ ::= { vpwrPanelIdentEntry 4}
+
+ vpwrPanelModuleFWVer OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The module firmware version."
+ ::= { vpwrPanelIdentEntry 5}
+
+ vpwrPanelModuleTestDate OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The manufacturing test date."
+ ::= { vpwrPanelIdentEntry 6}
+
+--
+-- Power Module inventory info
+--
+ vpwrDcPowerModuleIdentTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF DCPowerModuleIdentEntrySEQ
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ " This table describes power modules
+ that make up the system.
+ "
+ ::= { vpwrDcPowerModuleIdent 1 }
+
+ --
+ -- The Module Identifier Entry. Defines the sequence for module tables.
+ --
+
+ vpwrDcPowerModuleIdentEntry OBJECT-TYPE
+ SYNTAX DCPowerModuleIdentEntrySEQ
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ power module."
+ INDEX { vpwrBayIndex1, vpwrDCModuleIndex }
+ ::= { vpwrDcPowerModuleIdentTable 1 }
+
+
+ DCPowerModuleIdentEntrySEQ ::= SEQUENCE {
+ vpwrBayIndex1 PositiveInteger,
+ vpwrDCModuleIndex PositiveInteger,
+ vpwrModuleSerialNumber DisplayString ,
+ vpwrModuleModelNumber DisplayString ,
+ vpwrModuleFwVersion DisplayString ,
+ vpwrModuleTestDate DisplayString ,
+ vpwrModuleOperHours Counter32
+ }
+
+ vpwrBayIndex1 OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Identifies shelf number that this module belongs to.
+ The possible values are 1 through 2, starting from the top."
+ ::= { vpwrDcPowerModuleIdentEntry 1 }
+
+ vpwrDCModuleIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This object identifies the module within the shelf."
+ ::= { vpwrDcPowerModuleIdentEntry 2 }
+
+
+ vpwrModuleSerialNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Serial Number of the module"
+ ::= { vpwrDcPowerModuleIdentEntry 3}
+
+ vpwrModuleModelNumber OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Model Number of the module."
+ ::= { vpwrDcPowerModuleIdentEntry 4}
+
+ vpwrModuleFwVersion OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Firmware version of the module."
+ ::= { vpwrDcPowerModuleIdentEntry 5}
+
+ vpwrModuleTestDate OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Date when the module was last tested."
+ ::= { vpwrDcPowerModuleIdentEntry 6}
+
+ vpwrModuleOperHours OBJECT-TYPE
+ SYNTAX Counter32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Cumulative Operating Hours."
+ ::= { vpwrDcPowerModuleIdentEntry 7}
+
+
+
+
+--
+ --
+ -- The System History group.
+ --
+ vpwrSysHistAlarmTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrSysHistAlarmEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ " This table provides a list of most recent alarms.
+ "
+ ::= { vpwrSystemHistoryGroup 1 }
+
+
+ vpwrSysHistAlarmEntry OBJECT-TYPE
+ SYNTAX VpwrSysHistAlarmEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry describing an alarm."
+ INDEX { vpwrSysHistAlarmIndex}
+ ::= { vpwrSysHistAlarmTable 1 }
+
+ VpwrSysHistAlarmEntry ::= SEQUENCE {
+ vpwrSysHistAlarmIndex PositiveInteger,
+ vpwrSysHistAlarmDescription DisplayString
+ }
+
+ vpwrSysHistAlarmIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Alarm index."
+ ::= { vpwrSysHistAlarmEntry 1 }
+
+ vpwrSysHistAlarmDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Alarm description including time stamp."
+ ::= { vpwrSysHistAlarmEntry 2 }
+
+
+
+--
+-- --
+--The System Configuration Parameters group.
+-- --
+
+ vpwrSystemTempCompensation OBJECT-TYPE
+ SYNTAX INTEGER {
+ tempCompDisabled(0),
+ tempCompEnabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter enables/disables temperature compensation.
+ "
+ REFERENCE " "
+
+ ::= {vpwrSystemConfigGroup 1}
+
+ vpwrSystemTempCompStartTemperature OBJECT-TYPE
+ SYNTAX INTEGER (25..60)
+ UNITS "degrees Centigrade"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " The temperature at which temperature compensation becomes
+ active.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemConfigGroup 2}
+
+ vpwrSystemTempCompStopVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " When temperature compensation is active, vpwrSystemTempCompStopVoltage is the
+ limit to which float voltage will be reduced.
+ For example, to set this voltage to 51.75 volts enter a value of 5175.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemConfigGroup 3}
+
+ vpwrSystemTempCompensationSlope OBJECT-TYPE
+ SYNTAX INTEGER (0..250)
+ UNITS " milli-Volts per degrees Centigrade"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " The rate at which float voltage is changed, within the specified limits,
+ when temperature compensation is active.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemConfigGroup 4}
+
+ vpwrSystemThermalSenseType OBJECT-TYPE
+ SYNTAX INTEGER {
+ internal(0),
+ external(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter selects the temperature sensing point for temperature
+ compensation (in)activation.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemConfigGroup 5}
+
+ vpwrSystemHVAlarmSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "System High voltage alarm voltage setting.
+ "
+ ::= { vpwrSystemConfigGroup 6}
+ vpwrSystemBDAlarmSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "System Battery Discharge voltage setting."
+ ::= { vpwrSystemConfigGroup 7}
+
+--
+-- Threshold for Internal Temperature Trap
+--
+ vpwrSystemInternalTempLThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Centigrade"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Temperature value at which temperature compensation inactive (clear)
+ trap would be sent if temperature compensation was active when this
+ value is reached.
+ "
+ ::= { vpwrSystemConfigGroup 8}
+
+ vpwrSystemInternalTempUThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Centigrade"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Temperature value at which temperature compensation active (set) trap
+ would be sent.
+ "
+ ::= { vpwrSystemConfigGroup 9}
+
+ --
+ -- The System Current Operating Parameters group.
+ --
+
+
+ vpwrSystemShelfCapacity OBJECT-TYPE
+ SYNTAX INTEGER (1..16)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " It describes the maximum number of shelves that can/are controlled
+ by the controller. Each shelf is uniquely numbered in the range
+ from 1 to vpwrShelfCapacity.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemParameterGroup 1}
+
+ vpwrSystemVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " The current system voltage.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemParameterGroup 2}
+
+ vpwrSystemCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " Amperes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " The current system current.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemParameterGroup 3}
+
+ vpwrSystemControllerState OBJECT-TYPE
+ SYNTAX INTEGER {
+ systemControllerStateUnknown(0),
+ systemControllerStateNormal(1),
+ systemControllerStateChange(2) ,
+ systemControllerStateAlarm(3),
+ systemControllerStateMenu(4 ),
+ systemControllerStateIrActive(5)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Current System state as shown on the enhanced display.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemParameterGroup 4}
+
+
+ vpwrSystemInternalTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Centigrade"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " The current controller internal temperature.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemParameterGroup 5}
+
+ vpwrSystemTempCompensationState OBJECT-TYPE
+ SYNTAX INTEGER {
+ systemTempCompInactive(0),
+ systemTempCompActive(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Active or Inactive. Applicable only if temperature compensation is enabled.
+ This means that the controller is temperature compensating the float voltage.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemParameterGroup 6}
+
+ vpwrSystemType OBJECT-TYPE
+ SYNTAX INTEGER {
+ sysType48V (0),
+ sysType24V(1) ,
+ sysType12V(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This parameter describes the type of the system being managed.
+ This object is set by Eltek Valere Inc.
+ "
+ ::= { vpwrSystemParameterGroup 7 }
+
+ vpwrSystemCumulativeUpTime OBJECT-TYPE
+ SYNTAX Gauge
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This parameter describes the cumulative runtime in seconds
+ of the Eltek Valere controller.
+ "
+ ::= { vpwrSystemParameterGroup 8 }
+
+ vpwrSystemBatteryRemainingTime OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS "Hours"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "This parameter describes the remaining battery capacity
+ based upon installed battery capacity and
+ plant load. This number would change as the SOC
+ parameters of the batteries changes.
+ "
+ ::= { vpwrSystemParameterGroup 9 }
+
+ --
+ -- The System Alarm group.
+ --
+
+
+ vpwrSystemAlarmMajor OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Indicates a Major Alarm exists on the system.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemAlarmGroup 1}
+
+ vpwrSystemAlarmMinor OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Indicates a Minor Alarm exists on the system.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemAlarmGroup 2}
+
+ vpwrSystemACFailAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " One or more rectifiers have reported AC failure. If system
+ is configured to report rectifier communication failure as AC fail
+ this alarm will report.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemAlarmGroup 3}
+
+ vpwrSystemHighVoltageWarningAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " System has exceeded High Voltage Warning Setpoint. Check for high voltage on system bus.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemAlarmGroup 4}
+
+
+ vpwrSystemHighVoltageShutdownAlarm OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " One or more rectifiers have shut down due to high voltage present on output. Check bus voltage
+ and reseat rectifiers that have indicated this problem.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemAlarmGroup 5}
+
+ vpwrSystemBatteryonDischargeAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ systemTempCompInactive(0),
+ systemTempCompActive(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " System voltage has currently dropped below the alarm setpoint. This may be due to battery testing or AC failure.
+ "
+ REFERENCE " "
+ ::= {vpwrSystemAlarmGroup 6}
+
+ vpwrSystemLowVoltageWarningAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ sysType48V (0),
+ sysType24V(1) ,
+ sysType12V(2)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "System Voltage has dropped below setpoint for Low Voltage Alarm. This may occur during battery testing or AC failure
+ "
+ ::= { vpwrSystemAlarmGroup 7 }
+
+ vpwrSystemLVDOpenAlarm OBJECT-TYPE
+ SYNTAX Gauge
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "One or more contactors have opened. This occurs normally during system power on. If it occurs during operation this may
+ indicate system is operating below LVD disconnect voltage.
+ "
+ ::= { vpwrSystemAlarmGroup 8 }
+
+ vpwrSystemDistributionAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "One or more distribution alarm inputs are reporting an error condition. Check source of alarm and correct issue.
+ "
+ ::= { vpwrSystemAlarmGroup 9 }
+
+ vpwrSystemAuxiliaryAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "One or more Auxliary alarm inputs are reporting an error condition. Check source of alarm and correct issue.
+ "
+ ::= { vpwrSystemAlarmGroup 10 }
+
+ vpwrSystemRedundantCapAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The system load has exceeded the requirements for redundancy. This may be a temporary system overload condition or caused by a rectifier alarm.
+ "
+ ::= { vpwrSystemAlarmGroup 11 }
+
+ vpwrSystemRectIShareAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "One or more rectifiers are reporting a mismatch in current. This may be due to mismatched rectifier models or one or more rectifiers not current sharing
+ "
+ ::= { vpwrSystemAlarmGroup 12 }
+
+ vpwrSystemSnglRectAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 13 }
+
+ vpwrSystemMultRectAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 14 }
+
+ vpwrSystemModlCommAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 15 }
+
+ vpwrSystemOverTempAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 16 }
+
+ vpwrSystemThermRAAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Thermal Runaway has occurred on system. Check temperature inputs.
+ "
+ ::= { vpwrSystemAlarmGroup 17 }
+
+ vpwrSystemBDTAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "System has entered Battery Discharge Test mode
+ "
+ ::= { vpwrSystemAlarmGroup 18 }
+
+ vpwrSystemRectUVAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Rectifier output has dropped 1V below Low Voltage Alarm setpoint
+ "
+ ::= { vpwrSystemAlarmGroup 19 }
+
+ vpwrSystemMultRectUVAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 20 }
+
+ vpwrSystemSnglRngrAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 21 }
+
+ vpwrSystemMultRngrAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 22 }
+
+ vpwrSystemTempProbeAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Temp probe input missing or failed
+ "
+ ::= { vpwrSystemAlarmGroup 23 }
+
+ vpwrSystemRngrCommAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Ringer Module has stopped communicating with Controller.
+ "
+ ::= { vpwrSystemAlarmGroup 24 }
+
+ vpwrSystemDistPMCommAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "One or more distribution alarm modules, TRIOs, or PM modules has stopped communicating with Controller.
+ "
+ ::= { vpwrSystemAlarmGroup 25 }
+
+ vpwrSystemRectILimitAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Rectifier has reached current limit setpoint.
+ "
+ ::= { vpwrSystemAlarmGroup 26 }
+
+ vpwrSystemMultRectILimitAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 27 }
+
+ vpwrSystemUnmappedI2CCANAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Recheck all I2C and CAN dip switch settings. One or more devices in conflict.
+ "
+ ::= { vpwrSystemAlarmGroup 28 }
+
+ vpwrSystemConfigErrAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Recheck all I2C and CAN dip switch settings. One or more devices in conflict.
+ "
+ ::= { vpwrSystemAlarmGroup 29 }
+
+ vpwrSystemDispFWAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 30 }
+
+ vpwrSystemUndefinedAlarm OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= { vpwrSystemAlarmGroup 31 }
+
+ -- vpwrSystemModlCommAlarm OBJECT-TYPE
+ -- SYNTAX PositiveInteger
+ -- MAX-ACCESS read-only
+ -- STATUS current
+ -- DESCRIPTION
+ -- "
+ -- "
+ -- ::= { vpwrSystemAlarmGroup 32 }
+
+ --
+ -- The System LVD Operating Setpoints group.
+ --
+
+ vpwrLvdWarningSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " * .01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD Warning voltage setpoint."
+ ::= { vpwrLvdConfigGroup 1}
+
+ vpwrLvdDisconnectSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD disconnect voltage setpoint."
+ ::= { vpwrLvdConfigGroup 2}
+ vpwrLvdReconnectSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD Reconnect voltage setpoint."
+ ::= { vpwrLvdConfigGroup 3}
+ vpwrLvdReconnectDelayTimer OBJECT-TYPE
+ SYNTAX INTEGER (20..240)
+ UNITS " Seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The delay time, in seconds, before LVD is reconnected"
+ ::= { vpwrLvdConfigGroup 4}
+ --
+ -- The System LVD Operating Setpoints group.
+ --
+
+ vpwrLvd2DisconnectSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD disconnect voltage setpoint."
+ ::= { vpwrLvdConfigGroup 7}
+ vpwrLvd2ReconnectSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD Reconnect voltage setpoint."
+ ::= { vpwrLvdConfigGroup 8}
+ vpwrLvd2ReconnectDelayTimer OBJECT-TYPE
+ SYNTAX INTEGER (20..240)
+ UNITS " Seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The delay time, in seconds, before LVD is reconnected"
+ ::= { vpwrLvdConfigGroup 9}
+
+
+ --
+ -- The System LVD Operating Setpoints group.
+ --
+
+ vpwrLvd3DisconnectSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD disconnect voltage setpoint."
+ ::= { vpwrLvdConfigGroup 11}
+ vpwrLvd3ReconnectSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD Reconnect voltage setpoint."
+ ::= { vpwrLvdConfigGroup 12}
+ vpwrLvd3ReconnectDelayTimer OBJECT-TYPE
+ SYNTAX INTEGER (20..240)
+ UNITS " Seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The delay time, in seconds, before LVD is reconnected"
+ ::= { vpwrLvdConfigGroup 13}
+
+ --
+ -- The System LVD Operating Setpoints group.
+ --
+
+
+ vpwrLvd4DisconnectSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD disconnect voltage setpoint."
+ ::= { vpwrLvdConfigGroup 15}
+ vpwrLvd4ReconnectSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "LVD Reconnect voltage setpoint."
+ ::= { vpwrLvdConfigGroup 16}
+ vpwrLvd4ReconnectDelayTimer OBJECT-TYPE
+ SYNTAX INTEGER (20..240)
+ UNITS " Seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The delay time, in seconds, before LVD is reconnected"
+ ::= { vpwrLvdConfigGroup 17}
+
+-- vpwrLvd4DisconnectDelayTimer OBJECT-TYPE
+-- SYNTAX INTEGER (20..240)
+-- UNITS " Seconds"
+-- MAX-ACCESS read-only
+-- STATUS current
+-- DESCRIPTION
+-- "The delay time, in seconds, before LVD is reconnected"
+-- ::= { vpwrLvdConfigGroup 18}
+ --
+ -- The Rectifier Operating Parameters group.
+ --
+
+ vpwrRectifierFVSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "System Float Voltage setting"
+ ::= { vpwrRectifierConfigGroup 1}
+ vpwrRectifierHVSDSetpoint OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "System High Voltage Shutdown voltage setting"
+ ::= { vpwrRectifierConfigGroup 2}
+
+ vpwrRectifierCurrentLimitAdminState OBJECT-TYPE
+ SYNTAX INTEGER {
+ rectCurrentLimitDisabled(0),
+ rectCurrentLimitEnabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter allows enabling or rectifier current limit"
+ REFERENCE " "
+
+ ::= {vpwrRectifierConfigGroup 3}
+
+ vpwrRectifierCurrentLimit OBJECT-TYPE
+ SYNTAX INTEGER (5..220)
+ UNITS "Amperes"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Rectifier current limit setpoint"
+ ::= { vpwrRectifierConfigGroup 4}
+
+ vpwrRectifierFallbackAdminState OBJECT-TYPE
+ SYNTAX GenericEnableDisableTC
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Enables Rectifier to use
+ Fallback Voltage when it loses
+ communication with the controller.
+ This applies to all rectifiers."
+ ::= { vpwrRectifierConfigGroup 5}
+
+ vpwrRectifierFallbackVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Fallback Voltage setpoint to use
+ when rectifier loses
+ communication with the controller.
+ This applies to all rectifiers."
+ ::= { vpwrRectifierConfigGroup 6}
+
+ --
+ -- The Alarm group.
+ --
+
+
+ vpwrAlarmsPresent OBJECT-TYPE
+ SYNTAX Gauge32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present number of active alarm conditions."
+ ::= { vpwrDcPowerAlarmGroup 1 }
+
+ vpwrAlarmTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrAlarmEntrySEQ
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of alarm table entries. The table contains
+ zero, one, or multiple rows at any time depending upon
+ the number of alarm conditions in effect. The table
+ is initially empty at agent startup. The agent
+ creates a row in the table each time a condition is
+ detected and deletes that row when that condition no
+ longer exists.
+ The vpwrAlarmIndex, for each type of module starts at 1
+ and is limited by the total number of alarms that can be
+ generated by the module.
+
+ Alarms are named by an AutonomousType (OBJECT
+ IDENTIFIER), vpwrAlarmDescr, to allow a single table to
+ reflect alarms for different types of modules.
+
+ The number of rows in the table at any given time is
+ reflected by the value of vpwrAlarmsPresent."
+
+ ::= { vpwrDcPowerAlarmGroup 2 }
+
+ vpwrAlarmEntry OBJECT-TYPE
+ SYNTAX VpwrAlarmEntrySEQ
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular alarm."
+ INDEX { vpwrBayIndex, vpwrModuleIndex, vpwrAlarmIndex }
+ ::= { vpwrAlarmTable 1 }
+
+ VpwrAlarmEntrySEQ ::= SEQUENCE {
+ vpwrAlarmIndex PositiveInteger,
+ vpwrAlarmDescr AutonomousType,
+ vpwrAlarmTime TimeStamp
+ }
+
+ vpwrAlarmIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Identifies the alarm associated with the module.
+ It is unique on per module type basis. For example,
+ multiple rectifiers can have the same alarm and therefore same
+ vpwrAlarmIndex active at any one time.
+ "
+ ::= { vpwrAlarmEntry 1 }
+
+
+ vpwrAlarmDescr OBJECT-TYPE
+ SYNTAX AutonomousType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A reference to an alarm description object. The
+ object referenced should not be accessible, but rather
+ be used to provide a unique description of the alarm
+ condition."
+ ::= { vpwrAlarmEntry 2 }
+
+ vpwrAlarmTime OBJECT-TYPE
+ SYNTAX TimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The value of sysUpTime when the alarm condition was
+ detected."
+
+ ::= { vpwrAlarmEntry 3 }
+
+
+
+ --
+ -- The Battery Group
+ --
+
+
+
+ vpwrBatteryTempTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrBatteryTempEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table describes battery temperature probes.
+ "
+ ::= { vpwrBatteryTempGroup 1 }
+
+ vpwrBatteryTempEntry OBJECT-TYPE
+ SYNTAX VpwrBatteryTempEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular temperature probe."
+ INDEX { vpwrBatteryTempIndex }
+ ::= { vpwrBatteryTempTable 1 }
+
+ VpwrBatteryTempEntry ::= SEQUENCE {
+ vpwrBatteryTempIndex INTEGER,
+ vpwrBatteryTempName DisplayString,
+ vpwrBatteryTemp SysInputValue
+ }
+
+ vpwrBatteryTempIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Index into temperature table"
+ ::= { vpwrBatteryTempEntry 1}
+
+ vpwrBatteryTempName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (1..8))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A string identifying probe location."
+ ::= { vpwrBatteryTempEntry 2}
+
+ vpwrBatteryTemp OBJECT-TYPE
+ SYNTAX SysInputValue
+ UNITS "degrees Celsius"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Current temperature as recorded by the probe."
+ ::= { vpwrBatteryTempEntry 3}
+
+
+-- Threshold for Battery Temperature Trap
+
+ vpwrBatteryTempLThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Celsius"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Temperature value at which a clear trap would be sent.
+ All three battery temperature must be at or below this value
+ to trigger this trap.
+ "
+ ::= { vpwrBatteryTempGroup 2}
+
+ vpwrBatteryTempUThreshold OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Celsius"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Temperature value at which a set trap would be sent.
+ Any one of the three battery temperatures at or exceeding this limit
+ would trigger the trap.
+ "
+ ::= { vpwrBatteryTempGroup 3}
+
+ batteryTempCompensation OBJECT-TYPE
+ SYNTAX INTEGER {
+ tempCompDisabled(0),
+ tempCompEnabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter enables/disables temperature compensation.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryTempGroup 4}
+
+ batteryTempCompHighStartTemperature OBJECT-TYPE
+ SYNTAX INTEGER (25..60)
+ UNITS "degrees Celsius"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " The temperature at which temperature compensation becomes
+ active.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 5}
+
+ batteryTempCompHighStopVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " When temperature compensation is active, batteryTempCompHighStopVoltage is the
+ limit to which float voltage will be reduced.
+ For example, to set this voltage to 51.75 volts enter a value of 5175.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 6}
+
+ batteryTempCompHighSlope OBJECT-TYPE
+ SYNTAX INTEGER (0..250)
+ UNITS " milli-Volts per degrees Celsius"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " The rate at which float voltage is changed, within the specified limits,
+ when temperature compensation is active.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 7}
+
+
+ batteryTempCompLowStartTemperature OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "degrees Celsius"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " The temperature at which temperature compensation becomes
+ active.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 8}
+
+ batteryTempCompLowStopVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " When temperature compensation is active, batteryTempCompLowStopVoltage is the
+ limit to which float voltage will be reduced.
+ For example, to set this voltage to 51.75 volts enter a value of 5175.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 9}
+
+ batteryTempCompLowSlope OBJECT-TYPE
+ SYNTAX INTEGER (0..250)
+ UNITS " milli-Volts per degrees Celsius"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " The rate at which float voltage is changed, within the specified limits,
+ when temperature compensation is active.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 10}
+
+ batteryTempCompRunawayTemperature OBJECT-TYPE
+ SYNTAX INTEGER (25..60)
+ UNITS "degrees Celsius"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " The temperature at which system voltage will be set to
+ batteryTempCompRunawayStopVoltage.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 11}
+
+ batteryTempCompRunawayStopVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " When temperature compensation is enabled, float voltage will be reduced to
+ batteryTempCompRunawayStopVoltage if temperature
+ reaches batteryTempCompRunawayTemperature.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 12}
+
+ batteryTempCompSenseSource OBJECT-TYPE
+ SYNTAX INTEGER {
+ internal(0),
+ external(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter selects the temperature sensing point for temperature
+ compensation (in)activation.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 13}
+
+ batteryTempCompRunawayState OBJECT-TYPE
+ SYNTAX INTEGER {
+ inactive(0),
+ active(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter selects the temperature sensing point for temperature
+ compensation (in)activation.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryTempGroup 14}
+
+-- thermalProbeTable OBJECT-TYPE
+-- SYNTAX SEQUENCE OF ThermalProbeEntry
+-- MAX-ACCESS not-accessible
+-- STATUS current
+-- DESCRIPTION
+-- "This table describes battery temperature probes.
+-- "
+-- ::= { vpwrBatteryTempGroup 15 }
+--
+-- thermalProbeEntry OBJECT-TYPE
+-- SYNTAX ThermalProbeEntry
+-- MAX-ACCESS not-accessible
+-- STATUS current
+-- DESCRIPTION
+-- "An entry containing information applicable to a
+-- particular temperature probe."
+-- INDEX { vpwrBatteryTempIndex }
+-- AUGMENTS {vpwrBatteryTempEntry}
+-- ::= { thermalProbeTable 1 }
+--
+-- ThermalProbeEntry ::= SEQUENCE {
+-- thermalProbeState INTEGER
+-- }
+--
+-- thermalProbeState OBJECT-TYPE
+-- SYNTAX INTEGER {
+-- notPresent(0),
+-- present(1),
+-- removed(2),
+-- shorted(3)
+-- }
+-- MAX-ACCESS read-only
+-- STATUS current
+-- DESCRIPTION
+-- "State of thermal probe."
+-- ::= { thermalProbeEntry 1}
+
+
+--
+-- The SNMP Configuration Parameters
+--
+
+ vpwrTrapTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrTrapEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of possible trap destinations depending upon
+ the criticality of the trap.
+ "
+ ::= { vpwrDcPowerSnmpConfig 1 }
+
+ vpwrTrapEntry OBJECT-TYPE
+ SYNTAX VpwrTrapEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular trap destination."
+ INDEX { vpwrTrapIpIndex }
+ ::= { vpwrTrapTable 1 }
+
+ VpwrTrapEntry ::= SEQUENCE {
+ vpwrTrapIpIndex INTEGER,
+ vpwrTrapIpAddress IpAddress,
+ vpwrTrapCriticality INTEGER
+ }
+ vpwrTrapIpIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Trap Entry Index "
+ ::= { vpwrTrapEntry 1}
+
+ vpwrTrapIpAddress OBJECT-TYPE
+ SYNTAX IpAddress
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Trap destination IP Address"
+ ::= { vpwrTrapEntry 2}
+
+ vpwrTrapCriticality OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Criticality of traps sent to this IP Address"
+ ::= { vpwrTrapEntry 3}
+
+
+ vpwrReadCommunityString OBJECT-TYPE
+ SYNTAX DisplayString(SIZE (3..8))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This allows setting password to be able to do Get operations"
+ ::= { vpwrDcPowerSnmpConfig 2 }
+
+ vpwrWriteCommunityString OBJECT-TYPE
+ SYNTAX DisplayString(SIZE (3..8))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This allows setting password to be able to do Get and Set
+ operations.
+ The read-access is not allowed in the actual implementation.
+ "
+ ::= { vpwrDcPowerSnmpConfig 3 }
+
+ vpwrTrapCommunityString OBJECT-TYPE
+ SYNTAX DisplayString(SIZE (3..8))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This allows setting community string required for the
+ trap to be accepted at the destination.
+ "
+ ::= { vpwrDcPowerSnmpConfig 4 }
+
+ vpwrTrapVersion OBJECT-TYPE
+ SYNTAX INTEGER
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This allows setting the version of trap message sent from the system"
+ ::= { vpwrDcPowerSnmpConfig 5 }
+
+
+
+--
+-- LVD Alarm Group
+--
+
+-- vpwrLvdAlarmContactorOpen OBJECT-IDENTITY
+-- STATUS current
+-- DESCRIPTION
+-- "Contactor open"
+-- ::= {vpwrLvdAlarmGroup 1 }
+
+
+-- vpwrLvdAlarmCBOpen OBJECT-IDENTITY
+-- STATUS current
+-- DESCRIPTION
+-- "Circuit Breaker open"
+-- ::= {vpwrLvdAlarmGroup 2 }
+
+-- vpwrTrapLvdFuseOpen OBJECT-IDENTITY
+-- STATUS current
+-- DESCRIPTION
+-- "Fuse open"
+-- ::= {vpwrLvdAlarmGroup 3 }
+
+-- vpwrLvdAlarmWarning OBJECT-IDENTITY
+-- STATUS current
+-- DESCRIPTION
+-- "Plant Voltage below warning threshold"
+-- ::= {vpwrLvdAlarmGroup 4 }
+
+--
+-- Rectifier Alarm Group
+--
+
+ vpwrRectAlarmDCFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 1}
+
+ vpwrRectAlarmBoostFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 2}
+
+ vpwrRectAlarmACFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 3}
+
+ vpwrRectAlarmHVSD OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 4}
+
+ vpwrRectAlarmFanFail OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 5}
+
+ vpwrRectAlarmAmbTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 6}
+ vpwrRectAlarmIntTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 7}
+
+ vpwrRectAlarmIShare OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 8}
+
+ vpwrRectAlarmUV OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 9}
+
+ vpwrRectAlarmLowVoltage OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 10}
+
+ vpwrRectAlarmReserved OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 11}
+
+ vpwrRectAlarmDCEnable OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 12}
+
+ vpwrRectAlarmRemoteShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 13}
+
+ vpwrRectAlarmModDisableShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 14}
+
+ vpwrRectAlarmShortPinShutdown OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 15}
+
+ vpwrRectAlarmBoostComm OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ ::= {vpwrRectifierAlarmGroup 16}
+
+
+
+
+
+ sysAlarmConfigTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SysAlarmConfigEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table describes system alarm configuration and current
+ status.
+ "
+ ::= { vpwrDcPowerAlarmGroup 3 }
+
+ sysAlarmConfigEntry OBJECT-TYPE
+ SYNTAX SysAlarmConfigEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular system alarm."
+ INDEX { sysAlarmIndex }
+ ::= { sysAlarmConfigTable 1 }
+
+ SysAlarmConfigEntry ::= SEQUENCE {
+ sysAlarmIndex INTEGER,
+ sysAlarmDefaultName DisplayString,
+ sysAlarmCustomName DisplayString,
+ sysAlarmSeverity INTEGER ,
+ sysAlarmToRelayMapping DisplayString ,
+ sysAlarmOperStatus INTEGER
+ }
+
+ sysAlarmIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..255)
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Index into system alarm table"
+ ::= { sysAlarmConfigEntry 1}
+
+ sysAlarmDefaultName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (1..8))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Default alarm name."
+ ::= { sysAlarmConfigEntry 2}
+
+ sysAlarmCustomName OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (1..8))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "A custom alarm name."
+ ::= { sysAlarmConfigEntry 3}
+
+ sysAlarmSeverity OBJECT-TYPE
+ SYNTAX INTEGER {
+ none(0),
+ major(1),
+ minor(2),
+ majorAndMinor(3)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Alarm Severity as denoted by Major and Minor Alarm Mask"
+ ::= { sysAlarmConfigEntry 4}
+
+ sysAlarmToRelayMapping OBJECT-TYPE
+ SYNTAX DisplayString (SIZE (1..8))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "No additional mapping = 0
+ Map to Relay A = 1
+ Map to Relay B = 2
+ Map to Relay C = 4
+ Map to Relay D = 8
+ Map to Relay E = 16
+ Map to Relay F = 32
+ Map to Relay A and B = (1 + 2) and so on
+ The major/minor classification of alarms automatically
+ associates it with Major/Minor relay. Assigning a null
+ mapping here does not override vpwrPMRelayAlarmSeverity for
+ the alarm.
+ It should be used to define mapping to additional relays.
+ "
+ ::= { sysAlarmConfigEntry 5}
+
+ sysAlarmOperStatus OBJECT-TYPE
+ SYNTAX INTEGER {
+ inactive(0),
+ active(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates current alarm status"
+ ::= { sysAlarmConfigEntry 6}
+
+
+
+
+ sysAlarmComFailState OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(0),
+ enabled(1),
+ other(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Enable/Disable generation of comm fail alarm."
+ ::= { vpwrDcPowerAlarmGroup 4 }
+
+ sysAlarmIShareState OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(0),
+ enabled(1),
+ other(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Enable/Disable generation of current share alarm."
+ ::= { vpwrDcPowerAlarmGroup 5}
+
+ sysAlarmRedundancyState OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(0),
+ nPlus1(1),
+ nPlus2(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Enable/Disable generation of redundancy alarm."
+ ::= { vpwrDcPowerAlarmGroup 6}
+
+ sysAlarmComFailToACFailState OBJECT-TYPE
+ SYNTAX INTEGER {
+ disabled(0),
+ enabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Enable/Disable generation of ACF upon Com Fail"
+ ::= { vpwrDcPowerAlarmGroup 7}
+
+-------------------------------------------------------------------------------------------
+
+ vpwrDCPowerLampTest OBJECT-TYPE
+ SYNTAX INTEGER{
+ disabled(0),
+ enabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Lamp Test for modules"
+ ::= { eltek 5 }
+
+ vpwrPMCnfgTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrPMCnfgEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table shows the current configuration of the TRIO/PM86000/Controller inputs."
+ ::= { vpwrDcPowerPMModule 1 }
+
+ vpwrPMCnfgEntry OBJECT-TYPE
+ SYNTAX VpwrPMCnfgEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing current configuration of the TRIO/PM86000/Controller inputs."
+ INDEX { vpwrPMIndex }
+ ::= { vpwrPMCnfgTable 1 }
+
+ VpwrPMCnfgEntry ::= SEQUENCE {
+ vpwrPMIndex NonNegativeInteger,
+ vpwrPMDescription DisplayString,
+ vpwrPMCnfg1 VpwrPMCnfgValue,
+ vpwrPMCnfg2 VpwrPMCnfgValue,
+ vpwrPMCnfg3 VpwrPMCnfgValue,
+ vpwrPMCnfg4 VpwrPMCnfgValue,
+ vpwrPMCnfg5 VpwrPMCnfgValue,
+ vpwrPMCnfg6 VpwrPMCnfgValue,
+ vpwrPMCnfg7 VpwrPMCnfgValue,
+ vpwrPMCnfg8 VpwrPMCnfgValue
+ }
+
+ vpwrPMIndex OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter describes which TRIO/PM86000 device is being accessed."
+ ::= {vpwrPMCnfgEntry 1}
+
+ vpwrPMDescription OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter describes the configuration of the TRIO/PM86000 device."
+ ::= {vpwrPMCnfgEntry 2}
+
+ vpwrPMCnfg1 OBJECT-TYPE
+ SYNTAX VpwrPMCnfgValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current configuration of the TRIO/PM86000, input 1"
+ ::= {vpwrPMCnfgEntry 3}
+
+ vpwrPMCnfg2 OBJECT-TYPE
+ SYNTAX VpwrPMCnfgValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current configuration of the TRIO/PM86000, input 2"
+ ::= {vpwrPMCnfgEntry 4}
+
+ vpwrPMCnfg3 OBJECT-TYPE
+ SYNTAX VpwrPMCnfgValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current configuration of the TRIO/PM86000, input 3"
+ ::= {vpwrPMCnfgEntry 5}
+
+ vpwrPMCnfg4 OBJECT-TYPE
+ SYNTAX VpwrPMCnfgValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current configuration of the TRIO/PM86000, input 4"
+ ::= {vpwrPMCnfgEntry 6}
+
+ vpwrPMCnfg5 OBJECT-TYPE
+ SYNTAX VpwrPMCnfgValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current configuration of the TRIO/PM86000, input 5"
+ ::= {vpwrPMCnfgEntry 7}
+
+ vpwrPMCnfg6 OBJECT-TYPE
+ SYNTAX VpwrPMCnfgValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current configuration of the TRIO/PM86000, input 6"
+ ::= {vpwrPMCnfgEntry 8}
+
+ vpwrPMCnfg7 OBJECT-TYPE
+ SYNTAX VpwrPMCnfgValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current configuration of the TRIO (PM86000), input 7"
+ ::= {vpwrPMCnfgEntry 9}
+
+ vpwrPMCnfg8 OBJECT-TYPE
+ SYNTAX VpwrPMCnfgValue
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current configuration of the TRIO/PM86000, input 8"
+ ::= {vpwrPMCnfgEntry 10}
+
+-------------------------------------------------------------------------------------------
+
+ vpwrPMInputStatusTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrPMInputStatusEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table shows the current values of the TRIO/PM86000/Controller inputs."
+ ::= { vpwrDcPowerPMModule 2 }
+
+ vpwrPMInputStatusEntry OBJECT-TYPE
+ SYNTAX VpwrPMInputStatusEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing current state of the TRIO/PM86000/Controller inputs."
+ INDEX { vpwrPMIndex1 }
+ ::= { vpwrPMInputStatusTable 1 }
+
+ VpwrPMInputStatusEntry ::= SEQUENCE {
+ vpwrPMIndex1 NonNegativeInteger,
+ vpwrPMDescription1 DisplayString,
+ vpwrPMInput1State SysInputValue,
+ vpwrPMInput2State SysInputValue,
+ vpwrPMInput3State SysInputValue,
+ vpwrPMInput4State SysInputValue,
+ vpwrPMInput5State SysInputValue,
+ vpwrPMInput6State SysInputValue,
+ vpwrPMInput7State SysInputValue,
+ vpwrPMInput8State SysInputValue
+ }
+
+ vpwrPMIndex1 OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter describes which TRIO/PM86000 device is being accessed."
+ ::= {vpwrPMInputStatusEntry 1}
+
+ vpwrPMDescription1 OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter describes the input values of the TRIO/PM86000 device."
+ ::= {vpwrPMInputStatusEntry 2}
+
+ vpwrPMInput1State OBJECT-TYPE
+ SYNTAX SysInputValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current state of input 1"
+ ::= {vpwrPMInputStatusEntry 3}
+
+ vpwrPMInput2State OBJECT-TYPE
+ SYNTAX SysInputValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current state of input 2"
+ ::= {vpwrPMInputStatusEntry 4}
+
+ vpwrPMInput3State OBJECT-TYPE
+ SYNTAX SysInputValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current state of input 3"
+ ::= {vpwrPMInputStatusEntry 5}
+
+ vpwrPMInput4State OBJECT-TYPE
+ SYNTAX SysInputValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current state of input 4"
+ ::= {vpwrPMInputStatusEntry 6}
+
+ vpwrPMInput5State OBJECT-TYPE
+ SYNTAX SysInputValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current state of input 5"
+ ::= {vpwrPMInputStatusEntry 7}
+
+ vpwrPMInput6State OBJECT-TYPE
+ SYNTAX SysInputValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current state of input 6"
+ ::= {vpwrPMInputStatusEntry 8}
+
+ vpwrPMInput7State OBJECT-TYPE
+ SYNTAX SysInputValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current state of input 7"
+ ::= {vpwrPMInputStatusEntry 9}
+
+ vpwrPMInput8State OBJECT-TYPE
+ SYNTAX SysInputValue
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter gets the current state of input 8"
+ ::= {vpwrPMInputStatusEntry 10}
+
+-------------------------------------------------------------------------------------------
+ vpwrPMRelayCtrlTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrPMRelayCtrlEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "This table describes/controls system relays."
+ ::= { vpwrDcPowerPMModule 3 }
+
+ vpwrPMRelayCtrlEntry OBJECT-TYPE
+ SYNTAX VpwrPMRelayCtrlEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing current state of the relays."
+ INDEX { vpwrPMIndex2 }
+ ::= { vpwrPMRelayCtrlTable 1 }
+
+ VpwrPMRelayCtrlEntry ::= SEQUENCE {
+ vpwrPMIndex2 NonNegativeInteger,
+ vpwrPMDescription2 DisplayString,
+ vpwrPMRelay1State INTEGER,
+ vpwrPMRelay2State INTEGER,
+ vpwrPMRelay3State INTEGER,
+ vpwrPMRelay4State INTEGER,
+ vpwrPMRelay5State INTEGER,
+ vpwrPMRelay6State INTEGER
+ }
+
+ vpwrPMIndex2 OBJECT-TYPE
+ SYNTAX NonNegativeInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter describes the TRIO/PM device"
+ ::= {vpwrPMRelayCtrlEntry 1}
+
+ vpwrPMDescription2 OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " This parameter describes the TRIO/PM device"
+ ::= {vpwrPMRelayCtrlEntry 2}
+
+ vpwrPMRelay1State OBJECT-TYPE
+ SYNTAX INTEGER {
+ vpwrPMRelayOff(0),
+ vpwrPMRelayOn(1),
+ undefined(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the current state of relay 1"
+ ::= {vpwrPMRelayCtrlEntry 3}
+
+ vpwrPMRelay2State OBJECT-TYPE
+ SYNTAX INTEGER {
+ vpwrPMRelayOff(0),
+ vpwrPMRelayOn(1),
+ undefined(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the current state of relay 2"
+ ::= {vpwrPMRelayCtrlEntry 4}
+
+ vpwrPMRelay3State OBJECT-TYPE
+ SYNTAX INTEGER {
+ vpwrPMRelayOff(0),
+ vpwrPMRelayOn(1),
+ undefined(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the current state of relay 3"
+ ::= {vpwrPMRelayCtrlEntry 5}
+
+ vpwrPMRelay4State OBJECT-TYPE
+ SYNTAX INTEGER {
+ vpwrPMRelayOff(0),
+ vpwrPMRelayOn(1),
+ undefined(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the current state of relay 4"
+ ::= {vpwrPMRelayCtrlEntry 6}
+
+ vpwrPMRelay5State OBJECT-TYPE
+ SYNTAX INTEGER {
+ vpwrPMRelayOff(0),
+ vpwrPMRelayOn(1),
+ undefined(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the current state of relay 5"
+ ::= {vpwrPMRelayCtrlEntry 7}
+
+ vpwrPMRelay6State OBJECT-TYPE
+ SYNTAX INTEGER {
+ vpwrPMRelayOff(0),
+ vpwrPMRelayOn(1),
+ undefined(255)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the current state of relay 6"
+ ::= {vpwrPMRelayCtrlEntry 8}
+
+
+
+ --
+ -- The Ringer Configuration Parameters group.
+ --
+
+
+ vpwrRingerIndex OBJECT-TYPE
+ SYNTAX INTEGER (0..2)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter allows selecting ringer A or Ringer B as the active ringer.
+ "
+ ::= {vpwrRingerConfigGroup 1}
+
+ vpwrRingerParameterAdminState OBJECT-TYPE
+ SYNTAX INTEGER {
+ ringerDisabled(0),
+ ringerAOn(1) ,
+ ringerBOn(2)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter allows selecting ringer A or Ringer B as the active ringer.
+ "
+ ::= {vpwrRingerConfigGroup 2}
+
+ vpwrRingerParameterAcVoltage OBJECT-TYPE
+ SYNTAX INTEGER (7000..10000)
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the output AC voltage of the ringer.
+ "
+ ::= {vpwrRingerConfigGroup 3}
+
+ vpwrRingerParameterDcVoltage OBJECT-TYPE
+ SYNTAX INTEGER (0..5500 )
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the DC offset value of the ringer.
+ "
+ ::= {vpwrRingerConfigGroup 4}
+
+ vpwrRingerParameterFrequency OBJECT-TYPE
+ SYNTAX INTEGER (17..50)
+ UNITS " Hz"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter sets the ringer AC frequency.
+ "
+ ::= {vpwrRingerConfigGroup 5}
+
+ vpwrRingerNumberPresent OBJECT-TYPE
+ SYNTAX Gauge32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The present number of ringer modules."
+ ::= { vpwrRingerConfigGroup 6 }
+
+
+--
+-- ringer Alarm Group
+--
+
+ vpwrRingerAlarmAFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ringer A Failed"
+ ::= {vpwrRingerAlarmGroup 1 }
+
+ vpwrRingerAlarmAOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ringer A Heatsink Over-Temperature"
+ ::= {vpwrRingerAlarmGroup 2 }
+
+ vpwrRingerAlarmAOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ringer A Over-Current protection"
+ ::= {vpwrRingerAlarmGroup 3 }
+
+ vpwrRingerAlarmBFailed OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ringer B Failed"
+ ::= {vpwrRingerAlarmGroup 4 }
+
+ vpwrRingerAlarmBOverTemp OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ringer B Heatsink Over-Temperature"
+ ::= {vpwrRingerAlarmGroup 5 }
+
+ vpwrRingerAlarmBOverCurrent OBJECT-IDENTITY
+ STATUS current
+ DESCRIPTION
+ "Ringer B Over-Current protection"
+ ::= {vpwrRingerAlarmGroup 6 }
+
+
+
+ vpwrBoostAdminState OBJECT-TYPE
+ SYNTAX INTEGER {
+ boostDisabled(0),
+ boostEnabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter allows enabling or disabling boost.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryBoostGroup 1}
+
+ vpwrBoostVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryBoostGroup 2}
+
+ vpwrBoostDuration OBJECT-TYPE
+ SYNTAX INTEGER (1..921599)
+ UNITS "Seconds"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " Number of seconds for boost.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryBoostGroup 3}
+
+ vpwrBoostOperState OBJECT-TYPE
+ SYNTAX INTEGER {
+ boostInactive(0),
+ boostActive(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter allows starting or stopping boost if it is enabled.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryBoostGroup 4}
+
+
+ vpwrBatteryCurrentLimitAdminState OBJECT-TYPE
+ SYNTAX INTEGER {
+ batteryCurrentLimitDisabled(0),
+ batteryCurrentLimitEnabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " This parameter allows enabling or disabling battery current limit.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryCurrentGroup 1}
+
+ vpwrBatteryCurrentLimit OBJECT-TYPE
+ SYNTAX INTEGER (5..600)
+ UNITS "Ampere"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryCurrentGroup 2}
+
+ vpwrBatteryCurrent OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "Ampere"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Battery current
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryCurrentGroup 3}
+
+
+
+ vpwrBDTAdminState OBJECT-TYPE
+ SYNTAX INTEGER {
+ bdtManualDisabled(0),
+ bdtManualEnabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " Enable / Disable Battery Discharge Test execution.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryDischargeTestGroup 1}
+
+ vpwrBDTDuration OBJECT-TYPE
+ SYNTAX INTEGER (0..64799)
+ UNITS "Seconds"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "BDT Duration Setpoint.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryDischargeTestGroup 2}
+ vpwrBDTAlarmVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "BDT Alarm Voltage Setpoint.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryDischargeTestGroup 3}
+
+ vpwrBDTAbortVoltage OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "BDT Abort Voltage Setpoint.
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryDischargeTestGroup 4}
+
+ vpwrBDTAlarmCoefficient OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "None"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Deprecated. Always returns 1
+ "
+ REFERENCE " "
+ ::= {vpwrBatteryDischargeTestGroup 5}
+
+ vpwrBDTOperState OBJECT-TYPE
+ SYNTAX INTEGER {
+ bdtInactive(0),
+ bdtManualStart(1),
+ bdtACFailStart(14)
+
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Start/Stop Battery Discharge Test execution.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryDischargeTestGroup 6}
+
+ vpwrBDTClearAlarm OBJECT-TYPE
+ SYNTAX INTEGER {
+ bdtNoAlarm(0),
+ bdtAlarmPresent(1)
+ }
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Clears any active BDT alarm.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryDischargeTestGroup 7}
+
+ vpwrBDTActualTime OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "minutes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Actual BDT runtime in minutes.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryDischargeTestGroup 8}
+
+ vpwrBDTAlarmDelay OBJECT-TYPE
+ SYNTAX INTEGER
+ UNITS "minutes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Delay, in minutes, before checking and raising
+ BDT alarm.
+ Test: Plant Voltage <= BDTAlarmVoltage
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryDischargeTestGroup 9}
+ vpwrBDTResult OBJECT-TYPE
+ SYNTAX BDTResultTC
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Results of BDT.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryDischargeTestGroup 10}
+
+ vpwrBDTAutoAdminState OBJECT-TYPE
+ SYNTAX INTEGER {
+ bdtAutoDisabled(0),
+ bdtAutoEnabled(1)
+ }
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " Enable /Disable Battery Discharge Test data collection
+ upon detecting AC Fail condition.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBatteryDischargeTestGroup 11}
+
+--
+-- BDT History Start
+ --
+ -- The System History group.
+ --
+ vpwrBDTHistTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrBDTHistEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ " This table provides results of past BDT test.
+ "
+ ::= { vpwrBatteryDischargeTestGroup 12 }
+
+
+ vpwrBDTHistEntry OBJECT-TYPE
+ SYNTAX VpwrBDTHistEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry containing information applicable to a
+ particular BDT History."
+
+ INDEX { vpwrBDTHistIndex }
+
+ ::= { vpwrBDTHistTable 1 }
+ VpwrBDTHistEntry ::= SEQUENCE {
+ vpwrBDTHistIndex PositiveInteger,
+ vpwrBDTHistDateTime DisplayString,
+ vpwrBDTHistDuration PositiveInteger,
+ vpwrBDTHistAlarmVoltage PositiveInteger,
+ vpwrBDTHistAbortVoltage PositiveInteger,
+ vpwrBDTHistStartMethod BDTStartSourceTC,
+ vpwrBDTHistResult BDTResultTC,
+ vpwrBDTHistActualTime PositiveInteger,
+ vpwrBDTHistStartVoltage PositiveInteger,
+ vpwrBDTHistEndVoltage PositiveInteger
+ }
+
+ vpwrBDTHistIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "BDT History index."
+ ::= { vpwrBDTHistEntry 1 }
+
+ vpwrBDTHistDateTime OBJECT-TYPE
+ SYNTAX DisplayString
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " BDT run date as
+ yr-mm-dd hh:mm
+ "
+ REFERENCE " "
+ ::= {vpwrBDTHistEntry 2}
+ vpwrBDTHistDuration OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS "Minutes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "BDT duration at the time
+ this test was run.
+ "
+ REFERENCE " "
+ ::= {vpwrBDTHistEntry 3}
+
+ vpwrBDTHistAlarmVoltage OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "BDT Alarm Voltage setpoint when
+ this test was run.
+ "
+ REFERENCE " "
+ ::= {vpwrBDTHistEntry 4}
+
+ vpwrBDTHistAbortVoltage OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "BDT Abort Voltage setpoint when
+ this test was run.
+ "
+ REFERENCE " "
+ ::= {vpwrBDTHistEntry 5}
+
+
+ vpwrBDTHistStartMethod OBJECT-TYPE
+ SYNTAX BDTStartSourceTC
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "How Battery Discharge Test
+ was started.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBDTHistEntry 6}
+
+ vpwrBDTHistResult OBJECT-TYPE
+ SYNTAX BDTResultTC
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Results of BDT.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBDTHistEntry 7}
+
+ vpwrBDTHistActualTime OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS "minutes"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ " Actual BDT runtime in minutes.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBDTHistEntry 8}
+
+ vpwrBDTHistStartVoltage OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Plant Voltage at the time
+ the BDT was started.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBDTHistEntry 9}
+ vpwrBDTHistEndVoltage OBJECT-TYPE
+ SYNTAX PositiveInteger
+ UNITS " *.01 Volts"
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Plant Voltage at the time
+ the BDT was completed.
+ "
+ REFERENCE " "
+
+ ::= {vpwrBDTHistEntry 10}
+
+-- BDT History End
+
+-- BDT scheduled Start
+ --
+ -- The System History group.
+ --
+ vpwrBDTSchedTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF VpwrBDTSchedEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ " This table provides the list of the 12 BDTs that can be
+ scheduled. Need to set date(month and day) and
+ time (hh and minutes) when the test should be
+ started.
+ "
+ ::= { vpwrBatteryDischargeTestGroup 13 }
+
+
+ vpwrBDTSchedEntry OBJECT-TYPE
+ SYNTAX VpwrBDTSchedEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry describing an alarm."
+ INDEX { vpwrBDTSchedIndex}
+ ::= { vpwrBDTSchedTable 1 }
+
+ VpwrBDTSchedEntry ::= SEQUENCE {
+ vpwrBDTSchedIndex PositiveInteger,
+ vpwrBDTSchedMonth PositiveInteger,
+ vpwrBDTSchedDay PositiveInteger,
+ vpwrBDTSchedHour PositiveInteger,
+ vpwrBDTSchedMinute PositiveInteger
+ }
+
+ vpwrBDTSchedIndex OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "BDT Sched index."
+ ::= { vpwrBDTSchedEntry 1 }
+
+ vpwrBDTSchedDay OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " 1 to 28,29,30 or 31 depending upon the month
+ "
+ REFERENCE " "
+ ::= {vpwrBDTSchedEntry 2}
+
+ vpwrBDTSchedMonth OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " range 1 to 12
+ "
+ REFERENCE " "
+ ::= {vpwrBDTSchedEntry 3}
+
+ vpwrBDTSchedHour OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " range 0 to 23
+ "
+ REFERENCE " "
+ ::= {vpwrBDTSchedEntry 4}
+
+ vpwrBDTSchedMinute OBJECT-TYPE
+ SYNTAX PositiveInteger
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ " range 0 to 59
+ "
+ REFERENCE " "
+ ::= {vpwrBDTSchedEntry 5}
+
+
+-- BDT Scheduled End
+
+--
+-- traps
+--
+-- New Rules for trap numbering
+-- Rules are even number = trap set
+-- odd number = trap clear
+
+vpwrTrapPowerMajorAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Major Alarm"
+ ::= {vpwrDcPowerTraps 1}
+
+ vpwrTrapPowerMinorAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Minor Alarm"
+ ::= {vpwrDcPowerTraps 2}
+
+ vpwrTrapACFAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "AC Fail Alarm"
+ ::= {vpwrDcPowerTraps 3}
+
+ vpwrTrapHVAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "High Voltage Warning Alarm"
+ ::= {vpwrDcPowerTraps 4}
+
+ vpwrTrapHVSDAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "High Voltage Shutdown Alarm"
+ ::= {vpwrDcPowerTraps 5}
+
+ vpwrTrapBDAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Battery on Discharge Alarm"
+ ::= {vpwrDcPowerTraps 6}
+
+ vpwrTrapLVDWarningAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "LVD Warning Alarm"
+ ::= {vpwrDcPowerTraps 7}
+
+ vpwrTrapLVDOpenAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "LVD Open Alarm"
+ ::= {vpwrDcPowerTraps 8}
+
+ vpwrTrapDistAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Distribution Open Alarm"
+ ::= {vpwrDcPowerTraps 9}
+
+ vpwrTrapAuxAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Auxiliary System Alarm"
+ ::= {vpwrDcPowerTraps 10}
+
+ vpwrTrapSystemRedundancyAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "System Redundant Capacity Alarm"
+ ::= {vpwrDcPowerTraps 11}
+
+ vpwrTrapIShareAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Rectifier Current Share Alarm"
+ ::= {vpwrDcPowerTraps 12}
+
+ vpwrTrapModuleFailAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Single Rectifier Fail Alarm"
+ ::= {vpwrDcPowerTraps 13}
+
+ vpwrTrapMultipleModuleFailAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Multiple Rectifier Fail Alarm"
+ ::= {vpwrDcPowerTraps 14}
+
+ vpwrTrapModuleCommAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Power Module Communication Alarm"
+ ::= {vpwrDcPowerTraps 15}
+
+ vpwrTrapSystemOverTemperatureAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "System Over Temperature Alarm"
+ ::= {vpwrDcPowerTraps 16}
+
+ vpwrTrapSystemOK NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "SYSTEM OK - No Active Alarms"
+ ::= {vpwrDcPowerTraps 17}
+
+ vpwrTrapModuleInserted NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString, vpwrBayIndex, vpwrModuleIndex }
+ STATUS current
+ DESCRIPTION "A new module has been inserted into the system"
+ ::= {vpwrDcPowerTraps 18}
+
+ vpwrTrapModuleRemoved NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString,vpwrBayIndex, vpwrModuleIndex }
+ STATUS current
+ DESCRIPTION "A module has been removed from the system"
+ ::= {vpwrDcPowerTraps 19}
+
+ vpwrTrapThermalCompActive NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Thermal compensation has become active"
+ ::= {vpwrDcPowerTraps 20}
+
+ vpwrTrapThermalCompInactive NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Thermal compensation has been de-activated"
+ ::= {vpwrDcPowerTraps 21}
+
+ vpwrTrapInternalTempAlarmSet NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Internal Temperature upper threshold exceeded"
+ ::= {vpwrDcPowerTraps 22}
+
+ vpwrTrapInternalTempAlarmCleared NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Internal Temperature within limits"
+ ::= {vpwrDcPowerTraps 23}
+
+ vpwrTrapBatteryTempAlarmSet NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ At least one Battery Temperature exceeded upper threshold"
+ ::= {vpwrDcPowerTraps 24}
+
+ vpwrTrapBatteryTempAlarmCleared NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ All Battery Temperatures within limits"
+ ::= {vpwrDcPowerTraps 25}
+
+ vpwrTrapLoginFail NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Admin login failed due to wrong username/password"
+ ::= {vpwrDcPowerTraps 26}
+
+ vpwrTrapLoginSuccess NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Admin login successful"
+ ::= {vpwrDcPowerTraps 27}
+
+ vpwrTrapLogout NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Admin logout"
+ ::= {vpwrDcPowerTraps 28}
+
+ vpwrTrapAdminPwdChange NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Config change submitted with invalid access"
+ ::= {vpwrDcPowerTraps 29}
+
+ vpwrTrapIllegalConfigSubmit NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Config change submitted with invalid access"
+ ::= {vpwrDcPowerTraps 30}
+
+ vpwrTrapCfgChange NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Config change submitted"
+ ::= {vpwrDcPowerTraps 31}
+
+ vpwrTrapClearEventHistory NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Clear Event history buffer clear request"
+ ::= {vpwrDcPowerTraps 32}
+
+ vpwrTrapSwDownloadNoReboot NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ System software upgrade without reboot"
+ ::= {vpwrDcPowerTraps 33}
+
+ vpwrTrapSwDownloadAndReboot NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ System reboot due to software upgrade"
+ ::= {vpwrDcPowerTraps 34}
+
+ vpwrTrapSystemClockChange NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ System clock updated"
+ ::= {vpwrDcPowerTraps 35}
+
+ vpwrTrapModuleAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Module Alarm"
+ ::= {vpwrDcPowerTraps 36}
+
+ vpwrTrapOIDChange NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Change in OID"
+ ::= {vpwrDcPowerTraps 37}
+
+ vpwrTrapThermalRunaway NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Thermal Runaway Alarm"
+ ::= {vpwrDcPowerTraps 38}
+
+ vpwrTrapBatteryDischargeTestAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "System Voltage dropped to BDT Alarm Setpoint"
+ ::= {vpwrDcPowerTraps 39}
+
+ vpwrTrapBayUnnameAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Unassigned Bay Fail Alarm"
+ ::= {vpwrDcPowerTraps 40}
+
+ vpwrTrapPMComFailAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ PM Communication Fail Alarm"
+ ::= {vpwrDcPowerTraps 41}
+
+ vpwrTrapFuseOverloadAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Fuse Overload Alarm"
+ ::= {vpwrDcPowerTraps 42}
+
+ vpwrTrapPeripheralAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Peripheral Alarm."
+ ::= {vpwrDcPowerTraps 43}
+
+ vpwrTrapThermalProbeAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Thermal Probe Missing Alarm"
+ ::= {vpwrDcPowerTraps 44}
+
+ vpwrTrapBayCommAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Bay Communication Alarm"
+ ::= {vpwrDcPowerTraps 45}
+
+ vpwrTrapDistributionCommAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Distribution Communication Alarm"
+ ::= {vpwrDcPowerTraps 46}
+
+ vpwrTrapConverterAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Single Converter Fail Alarm"
+ ::= {vpwrDcPowerTraps 47}
+
+ vpwrTrapMultipleConvFailAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Multiple Converter Fail Alarm"
+ ::= {vpwrDcPowerTraps 48}
+
+ vpwrTrapDGUAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! For Future Use. !!!
+ DGU Alarm"
+ ::= {vpwrDcPowerTraps 49}
+
+ vpwrTrapConfigErrorAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Configuration Error"
+ ::= {vpwrDcPowerTraps 50}
+
+ vpwrTrapDisplayFirmwareMismatchAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Display Firmware Mismatch"
+ ::= {vpwrDcPowerTraps 51}
+
+ vpwrTrapConverterInputFailAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Converter Input Fail Alarm"
+ ::= {vpwrDcPowerTraps 52}
+
+ vpwrTrapBatteryRechgIlimitFailAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Battery Recharge Current Limit Fail"
+ ::= {vpwrDcPowerTraps 53}
+
+ vpwrTrapSystemAlive NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Periodic Keepalive trap"
+ ::= {vpwrDcPowerTraps 54}
+
+ vpwrTrapSystemAuxAlmSource NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString,
+ vpwrAlarmingModuleOID,
+ vpwrAlarmingModuleIndex,
+ vpwrAlarmingSubModuleBitMap }
+ STATUS current
+ DESCRIPTION
+ "Source of Auxilary Alarms.
+ Indicates the module and the aux within
+ the module causing alarms"
+ ::= {vpwrDcPowerTraps 55}
+
+ vpwrTrapSystemDistAlmSource NOTIFICATION-TYPE
+ OBJECTS{ vpwrTrapsMsgString,
+ vpwrAlarmingModuleOID,
+ vpwrAlarmingModuleIndex,
+ vpwrAlarmingSubModuleBitMap }
+ STATUS current
+ DESCRIPTION
+ "Source of Distribution Alarms.
+ Indicates the module and the dist within
+ the module causing alarms"
+ ::= {vpwrDcPowerTraps 56}
+
+ vpwrTrapSystemBatCapacityAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString,
+ vpwrSystemCurrent,
+ vpwrBatteryCurrentCapacity }
+ STATUS current
+ DESCRIPTION
+ "Plant Load exceeds Plant Battery Current Capacity.
+ Useful for batteries that limit maximum discharge current
+ It will not be sent out for VRLA batteries, eg"
+
+ ::= {vpwrDcPowerTraps 58}
+
+ vpwrTrapSystemACFClearAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString,
+ vpwrTrapAcfDuration}
+ STATUS current
+ DESCRIPTION
+ "AC Fail (ACF) Conditioned Cleared Alarm.
+ Duration is in minutes.
+ "
+ ::= {vpwrDcPowerTraps 61}
+
+ vpwrTrapSystemACFSetAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString,
+ vpwrTrapAcfDuration}
+ STATUS current
+ DESCRIPTION
+ "ACF Conditioned detected Alarm.
+ The duration would always be zero.
+ Msg String: ACF Alarm Set
+ "
+ ::= {vpwrDcPowerTraps 62}
+
+ vpwrTrapSystemBatCapacityLeft NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString,
+ vpwrBatteryRemainingTime }
+ STATUS current
+ DESCRIPTION
+ "!!! For Future Use. !!!
+ Battery Useful Capacity Remaining"
+ ::= {vpwrDcPowerTraps 64}
+
+ vpwrTrapRectifierUVAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString, vpwrBayIndex, vpwrModuleIndex }
+ STATUS current
+ DESCRIPTION "Rectifier Under Voltage Alarm"
+ ::= {vpwrDcPowerTraps 65}
+
+ vpwrTrapMultRectifierUVAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! For Future Use. !!!
+ Multiple Rectifier Under Voltage Alarm"
+ ::= {vpwrDcPowerTraps 66}
+
+ vpwrTrapRingerAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Ringer Alarm"
+ ::= {vpwrDcPowerTraps 67}
+
+ vpwrTrapMultRingerAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString}
+ STATUS current
+ DESCRIPTION "!!! For Future Use. !!!
+ Multiple Ringer Alarm"
+ ::= {vpwrDcPowerTraps 68}
+
+ vpwrTrapI2CCANAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString}
+ STATUS current
+ DESCRIPTION "!!! For Future Use. !!!
+ Unmapped I2C/CAN Address Alarm
+ One of your I2C or CAN devices
+ has a duplicate or invalid address
+ and can not be mapped. Please
+ recheck all device addresses."
+ ::= {vpwrDcPowerTraps 69}
+
+vpwrTrapRectifierIlimitAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString, vpwrBayIndex, vpwrModuleIndex }
+ STATUS current
+ DESCRIPTION "Rectifier Current Limit Alarm"
+ ::= {vpwrDcPowerTraps 70}
+
+ vpwrTrapMultRectifierIlimitAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "!!! For Future Use. !!!
+ Multiple Rectifier Current Limit Alarm"
+ ::= {vpwrDcPowerTraps 71}
+
+ vpwrTrapRingerCommAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString }
+ STATUS current
+ DESCRIPTION "Ringer Communication Alarm"
+ ::= {vpwrDcPowerTraps 72}
+
+ vpwrTrapUnassignedAlarm NOTIFICATION-TYPE
+ OBJECTS { vpwrTrapsMsgString}
+ STATUS current
+ DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
+ Unassigned Alarm(Trap) - Check Web Page"
+ ::= {vpwrDcPowerTraps 99}
+
+END
|