@@ -0,0 +1,1574 @@
+EATON-SENSOR-MIB DEFINITIONS ::= BEGIN
+
+IMPORTS
+ OBJECT-TYPE, NOTIFICATION-TYPE, MODULE-IDENTITY,
+ Counter32, Integer32
+ FROM SNMPv2-SMI
+ NOTIFICATION-GROUP, OBJECT-GROUP, MODULE-COMPLIANCE
+ FROM SNMPv2-CONF
+ TEXTUAL-CONVENTION
+ FROM SNMPv2-TC
+ sensorAgent
+ FROM EATON-OIDS;
+
+eatonSensor MODULE-IDENTITY
+ LAST-UPDATED "201812171200Z"
+ ORGANIZATION
+ "Eaton Corporation"
+ CONTACT-INFO
+ "http://powerquality.eaton.com"
+ DESCRIPTION
+ "The MIB module for Eaton Sensors."
+ REVISION "201812171200Z"
+ DESCRIPTION
+ "Initial release."
+::= { sensorAgent 1 }
+
+-- eatonSensor { iso org(3) dod(6) internet(1) private(4)
+-- enterprises(1) eaton(534) products(6) sensorAgent(8) (1) }
+
+sensor OBJECT IDENTIFIER ::= { eatonSensor 1 }
+temperature OBJECT IDENTIFIER ::= { eatonSensor 2 }
+humidity OBJECT IDENTIFIER ::= { eatonSensor 3 }
+digitalInput OBJECT IDENTIFIER ::= { eatonSensor 4 }
+conformance OBJECT IDENTIFIER ::= { eatonSensor 10 }
+
+-- Textual Conventions
+UnixTimeStamp ::= TEXTUAL-CONVENTION
+ DISPLAY-HINT "dddddddddd"
+ STATUS current
+ DESCRIPTION
+ "Unix time stamp. Measured in seconds since January 1, 1970."
+ SYNTAX Counter32
+
+PositionType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the position by reference to the data center aisle."
+ SYNTAX INTEGER {
+ undefined(0),
+ other(1),
+ rackRear(2),
+ rackFront(3),
+ batteryRoom(4)
+ }
+
+ElevationType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the elevation in the rack."
+ SYNTAX INTEGER {
+ undefined(0),
+ other(1),
+ bottom(2),
+ middle(3),
+ top(4)
+ }
+
+CommunicationStatus ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the communication sensor status or probe status."
+ SYNTAX INTEGER {
+ unknown(0),
+ communicationOK(2),
+ communicationLost(3)
+ }
+
+ProbeConnectionType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the probe connection to the sensor or probe."
+ SYNTAX INTEGER {
+ undefined(0),
+ internal(1),
+ wired(2),
+ wireless(3)
+ }
+
+EnableType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes enable/disable."
+ SYNTAX INTEGER {
+ disabled(0),
+ enabled(1)
+ }
+
+AlarmType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the alarm according to a measured value by reference to the triggers."
+ SYNTAX INTEGER {
+ good(0),
+ lowWarning(1),
+ lowCritical(2),
+ highWarning(3),
+ highCritical(4)
+ }
+
+ResetCommandType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Commands a reset."
+ SYNTAX INTEGER {
+ none(0),
+ reset(1)
+ }
+
+PolarityType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the polarity configuration."
+ SYNTAX INTEGER {
+ normallyOpened(0),
+ normallyClosed(1)
+ }
+
+AlarmSeverityType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the alarm severity."
+ SYNTAX INTEGER {
+ informationnal(1),
+ warning(2),
+ critical(3)
+ }
+
+AlarmLevelType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the alarm level."
+ SYNTAX INTEGER {
+ good(0),
+ informationnal(1),
+ warning(2),
+ critical(3)
+ }
+
+StateType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the state of a digital input that depends on its measure
+ and the polrity configuration."
+ SYNTAX INTEGER {
+ inactive(0),
+ active(1)
+ }
+
+TemperatureUnitType ::= TEXTUAL-CONVENTION
+ STATUS current
+ DESCRIPTION "Describes the temperature unit used to read/write the temperature data."
+ SYNTAX INTEGER {
+ tenthOfDegKelvin(0),
+ tenthOfDegCelsius(1),
+ tenthOfDegFarhenheit(2)
+ }
+
+-- -----------------------------------------------------------------------------
+
+sensorCount OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of sensor managed on this device."
+ ::= { sensor 1 }
+
+sensorIdentificationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SensorIdentificationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of sensor devices identification data.
+ The number of entries is given by sensorCount."
+ ::= { sensor 2}
+
+sensorIdentificationEntry OBJECT-TYPE
+ SYNTAX SensorIdentificationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a sensor device identification."
+ INDEX { sensorIndex }
+ ::= { sensorIdentificationTable 1 }
+
+SensorIdentificationEntry ::= SEQUENCE {
+ sensorIndex
+ Integer32,
+ sensorUuid
+ OCTET STRING,
+ sensorConnectionType
+ ProbeConnectionType,
+ sensorAddress
+ OCTET STRING,
+ sensorMonitoredBy
+ OBJECT IDENTIFIER,
+ sensorManufacturer
+ OCTET STRING,
+ sensorModel
+ OCTET STRING,
+ sensorPartNumber
+ OCTET STRING,
+ sensorSerialNumber
+ OCTET STRING,
+ sensorFirmwareVersion
+ OCTET STRING
+}
+
+sensorIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..3)
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "A unique value for each sensor device. Its value
+ ranges from 1 to sensorCount."
+ ::= { sensorIdentificationEntry 1 }
+
+sensorUuid OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique uuid value for each sensor device."
+ ::= { sensorIdentificationEntry 2 }
+
+sensorConnectionType OBJECT-TYPE
+ SYNTAX ProbeConnectionType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Sensor connection type with the device that monitors it."
+ ::= { sensorIdentificationEntry 3 }
+
+sensorAddress OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Depending of the connection implementation : Modbus Slave Id, BT Mac address, ..."
+ ::= { sensorIdentificationEntry 4 }
+
+sensorMonitoredBy OBJECT-TYPE
+ SYNTAX OBJECT IDENTIFIER
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Parent oid device where the sensor is connected to and monitored by."
+ ::= { sensorIdentificationEntry 5 }
+
+sensorManufacturer OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The vendor name of the sensor device."
+ ::= { sensorIdentificationEntry 6 }
+
+sensorModel OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The model name of the sensor device."
+ ::= { sensorIdentificationEntry 7 }
+
+sensorPartNumber OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The catalog part number of the sensor device."
+ ::= { sensorIdentificationEntry 8 }
+
+sensorSerialNumber OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The serial number of the sensor device."
+ ::= { sensorIdentificationEntry 9 }
+
+sensorFirmwareVersion OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "The firmware version of the sensor device."
+ ::= { sensorIdentificationEntry 10 }
+
+
+sensorConfigurationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SensorConfigurationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of sensor devices configuration data.
+ The number of entries is given by sensorCount."
+ ::= { sensor 3 }
+
+sensorConfigurationEntry OBJECT-TYPE
+ SYNTAX SensorConfigurationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a sensor device configuration."
+ INDEX { sensorIndex }
+ ::= { sensorConfigurationTable 1 }
+
+SensorConfigurationEntry ::= SEQUENCE {
+ sensorName
+ OCTET STRING,
+ sensorLocation
+ OCTET STRING,
+ sensorPosition
+ PositionType,
+ sensorElevation
+ ElevationType,
+ sensorUElevation
+ Integer32
+}
+
+sensorName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The friendly name of the sensor device."
+ ::= { sensorConfigurationEntry 1 }
+
+sensorLocation OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The location of the sensor device."
+ ::= { sensorConfigurationEntry 2 }
+
+sensorPosition OBJECT-TYPE
+ SYNTAX PositionType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The Position by reference to the data center aisle."
+ ::= { sensorConfigurationEntry 3 }
+
+sensorElevation OBJECT-TYPE
+ SYNTAX ElevationType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The Elevation in the rack."
+ ::= { sensorConfigurationEntry 4 }
+
+sensorUElevation OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The elevation in the rack in count of U position from the bottom."
+ ::= { sensorConfigurationEntry 5 }
+
+
+sensorMonitoringTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF SensorMonitoringEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of sensor devices monitoring data.
+ The number of entries is given by sensorCount."
+ ::= { sensor 4 }
+
+sensorMonitoringEntry OBJECT-TYPE
+ SYNTAX SensorMonitoringEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a sensor device monitoring."
+ INDEX { sensorIndex }
+ ::= { sensorMonitoringTable 1 }
+
+SensorMonitoringEntry ::= SEQUENCE {
+ sensorStatus
+ CommunicationStatus,
+ sensorStatusSince
+ UnixTimeStamp,
+ sensorTemperatureCount
+ Integer32,
+ sensorHumidityCount
+ Integer32,
+ sensorDigitalInputCount
+ Integer32,
+ sensorAnalogInputCount
+ Integer32
+}
+
+sensorStatus OBJECT-TYPE
+ SYNTAX CommunicationStatus
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates how the sensor is communicating or not."
+ ::= { sensorMonitoringEntry 1 }
+
+sensorStatusSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the sensor status last change."
+ ::= { sensorMonitoringEntry 2 }
+
+sensorTemperatureCount OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of temperature probes managed by the sensor device."
+ ::= { sensorMonitoringEntry 3 }
+
+sensorHumidityCount OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of humidity probes managed by the sensor device."
+ ::= { sensorMonitoringEntry 4 }
+
+sensorDigitalInputCount OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of digital input probes managed by the sensor device."
+ ::= { sensorMonitoringEntry 5 }
+
+sensorAnalogInputCount OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Number of analog input probes managed by the sensor device."
+ ::= { sensorMonitoringEntry 6 }
+
+sensorNotification OBJECT IDENTIFIER ::= { sensor 0 }
+
+notifySensorCount NOTIFICATION-TYPE
+ OBJECTS { sensorCount }
+ STATUS current
+ DESCRIPTION
+ "Sent whenever the sensor count changes after a discovery or removing
+ from the UI."
+ ::= { sensorNotification 1 }
+
+notifySensorStatus NOTIFICATION-TYPE
+ OBJECTS { sensorIndex,
+ sensorUuid,
+ sensorStatus,
+ sensorStatusSince }
+ STATUS current
+ DESCRIPTION
+ "Sent whenever the sensor status changes."
+ ::= { sensorNotification 2 }
+
+-- -----------------------------------------------------------------------------
+
+temperatureIdentificationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TemperatureIdentificationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of temperature probe measurements. the number of entries
+ is given by the temperature count."
+ ::= { temperature 1 }
+
+temperatureIdentificationEntry OBJECT-TYPE
+ SYNTAX TemperatureIdentificationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a temperature probe identification."
+ INDEX { sensorIndex, temperatureIndex }
+ ::= { temperatureIdentificationTable 1 }
+
+TemperatureIdentificationEntry ::= SEQUENCE {
+ temperatureIndex
+ Integer32,
+ temperatureUuid
+ OCTET STRING,
+ temperatureConnectionType
+ ProbeConnectionType
+}
+
+temperatureIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..2)
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "A unique value for each temperature probe measurement. Its value
+ ranges from 1 to sensorTemperatureCount."
+ ::= { temperatureIdentificationEntry 1 }
+
+temperatureUuid OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique uuid value for each temperature."
+ ::= { temperatureIdentificationEntry 2 }
+
+temperatureConnectionType OBJECT-TYPE
+ SYNTAX ProbeConnectionType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Probe connection type with the sensor that monitors it."
+ ::= { temperatureIdentificationEntry 3 }
+
+
+temperatureConfigurationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TemperatureConfigurationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of temperature probe configuration. The number of entries is
+ given by sensorTemperatureCount."
+ ::= { temperature 2 }
+
+temperatureConfigurationEntry OBJECT-TYPE
+ SYNTAX TemperatureConfigurationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a temperature probe configuration."
+ INDEX { sensorIndex, temperatureIndex }
+ ::= { temperatureConfigurationTable 1 }
+
+TemperatureConfigurationEntry ::= SEQUENCE {
+ temperatureName
+ OCTET STRING,
+ temperatureEnable
+ EnableType,
+ temperatureOffset
+ Integer32,
+ temperatureAlarmEnable
+ EnableType,
+ temperatureThresholdLowWarning
+ Integer32,
+ temperatureThresholdLowCritical
+ Integer32,
+ temperatureThresholdHighWarning
+ Integer32,
+ temperatureThresholdHighCritical
+ Integer32,
+ temperatureThresholdHysteresis
+ Integer32,
+ temperatureAlarmGracePeriod
+ Integer32
+}
+
+temperatureName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The friendly name of the sensor temperature probe."
+ ::= { temperatureConfigurationEntry 1 }
+
+temperatureEnable OBJECT-TYPE
+ SYNTAX EnableType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the temperature acquired or not.
+ 0:disabled, 1:enabled"
+ ::= { temperatureConfigurationEntry 2 }
+
+temperatureOffset OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the offset (Minus or Plus) to be added to the acquired value
+ in order to correct the probe measurement error.
+ See temperatureUnit data for the units."
+ ::= { temperatureConfigurationEntry 3 }
+
+temperatureAlarmEnable OBJECT-TYPE
+ SYNTAX EnableType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the temperature alarm depending on the thresholds evaluated or not.
+ 0:disabled, 1:enabled"
+ ::= { temperatureConfigurationEntry 4 }
+
+temperatureThresholdLowWarning OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Low warning temperature threshold.
+ See temperatureUnit data for the units."
+ ::= { temperatureConfigurationEntry 5 }
+
+temperatureThresholdLowCritical OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Low critical temperature threshold.
+ See temperatureUnit data for the units."
+ ::= { temperatureConfigurationEntry 6 }
+
+temperatureThresholdHighWarning OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "High warning temperature threshold.
+ See temperatureUnit data for the units."
+ ::= { temperatureConfigurationEntry 7 }
+
+temperatureThresholdHighCritical OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "High critical temperature threshold.
+ See temperatureUnit data for the units."
+ ::= { temperatureConfigurationEntry 8 }
+
+temperatureThresholdHysteresis OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Temperature threshold hysteresis.
+ See temperatureUnit data for the units."
+ ::= { temperatureConfigurationEntry 9 }
+
+temperatureAlarmGracePeriod OBJECT-TYPE
+ SYNTAX Integer32 (1..60)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The grace period the alarm triggers after the acquired value crosses
+ a trigger value (in seconds)."
+ ::= { temperatureConfigurationEntry 10 }
+
+
+temperatureMonitoringTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TemperatureMonitoringEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of temperature probe monitoring. The number of entries is
+ given by sensorTemperatureCount."
+ ::= { temperature 3 }
+
+temperatureMonitoringEntry OBJECT-TYPE
+ SYNTAX TemperatureMonitoringEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a temperature probe monitoring."
+ INDEX { sensorIndex, temperatureIndex }
+ ::= { temperatureMonitoringTable 1 }
+
+TemperatureMonitoringEntry ::= SEQUENCE {
+ temperatureAlarm
+ AlarmType,
+ temperatureAlarmChangeSince
+ UnixTimeStamp,
+ temperatureValue
+ Integer32,
+ temperatureCommunicationStatus
+ CommunicationStatus,
+ temperatureCommunicationStatusSince
+ UnixTimeStamp
+}
+
+temperatureAlarm OBJECT-TYPE
+ SYNTAX AlarmType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Alarm set according to the realtime measure compared to the thresholds."
+ ::= { temperatureMonitoringEntry 1 }
+
+temperatureAlarmChangeSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the temperature alarm last change."
+ ::= { temperatureMonitoringEntry 2 }
+
+temperatureValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Realtime measured value after correction with the offset.
+ See temperatureUnit data for the units."
+ ::= { temperatureMonitoringEntry 3 }
+
+temperatureCommunicationStatus OBJECT-TYPE
+ SYNTAX CommunicationStatus
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates how the temperature probe is communicating or not."
+ ::= { temperatureMonitoringEntry 4 }
+
+temperatureCommunicationStatusSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the temperature communication status last change."
+ ::= { temperatureMonitoringEntry 5 }
+
+
+temperatureMonitoringMinMaxTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF TemperatureMonitoringMinMaxEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of temperature probe monitoring Min and Max. The number of entries is
+ given by sensorTemperatureCount."
+ ::= { temperature 4 }
+
+temperatureMonitoringMinMaxEntry OBJECT-TYPE
+ SYNTAX TemperatureMonitoringMinMaxEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a temperature probe monitoring Min and Max."
+ INDEX { sensorIndex, temperatureIndex }
+ ::= { temperatureMonitoringMinMaxTable 1 }
+
+TemperatureMonitoringMinMaxEntry ::= SEQUENCE {
+ temperatureMinValue
+ Integer32,
+ temperatureMinValueSince
+ UnixTimeStamp,
+ temperatureMaxValue
+ Integer32,
+ temperatureMaxValueSince
+ UnixTimeStamp,
+ temperatureResetMinMax
+ ResetCommandType
+}
+
+temperatureMinValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Minimum value registered since the 1st connection of the sensor or the last reset.
+ See temperatureUnit data for the units."
+ ::= { temperatureMonitoringMinMaxEntry 1 }
+
+temperatureMinValueSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the temperature min value last change."
+ ::= { temperatureMonitoringMinMaxEntry 2 }
+
+temperatureMaxValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Maximum value registered since the 1st connection of the sensor or the last reset.
+ See temperatureUnit data for the units."
+ ::= { temperatureMonitoringMinMaxEntry 3 }
+
+temperatureMaxValueSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the temperature max value last change."
+ ::= { temperatureMonitoringMinMaxEntry 4 }
+
+temperatureResetMinMax OBJECT-TYPE
+ SYNTAX ResetCommandType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Command that resets the min and max data with the current measure.
+ 0:None, 1:Reset"
+ ::= { temperatureMonitoringMinMaxEntry 5 }
+
+temperatureUnit OBJECT-TYPE
+ SYNTAX TemperatureUnitType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Temperature unit configuration. It is a global setting for all the v1
+ and v3 SNMP client. It does not involve the temperature unit of data
+ stored and managed in the card. But it does configure the unit the temperatures
+ data are red and written in this Mib.
+ The possible values are tenthOfDegCelsius(0), tenthOfDegFarhenheit(1),
+ tenthOfDegKelvin(2)."
+ ::= { temperature 5 }
+
+
+temperatureNotification OBJECT IDENTIFIER ::= { temperature 0 }
+
+notifyTemperatureAlarm NOTIFICATION-TYPE
+ OBJECTS { sensorIndex,
+ temperatureIndex,
+ temperatureUuid,
+ temperatureAlarm,
+ temperatureAlarmChangeSince,
+ temperatureValue }
+ STATUS current
+ DESCRIPTION
+ "Sent whenever the temperature alarm changes."
+ ::= { temperatureNotification 1 }
+
+notifyTemperatureCommunicationStatus NOTIFICATION-TYPE
+ OBJECTS { sensorIndex,
+ temperatureIndex,
+ temperatureUuid,
+ temperatureCommunicationStatus,
+ temperatureCommunicationStatusSince }
+ STATUS current
+ DESCRIPTION
+ "Sent whenever the temperature communication status changes.
+ Is not implemented when the probe is internal (see temperatureConnectionType)."
+ ::= { temperatureNotification 2 }
+
+-- -----------------------------------------------------------------------------
+
+
+humidityIdentificationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HumidityIdentificationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of humidity probe measurements. the number of entries
+ is given by the humidity count."
+ ::= { humidity 1 }
+
+humidityIdentificationEntry OBJECT-TYPE
+ SYNTAX HumidityIdentificationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a humidity probe identification."
+ INDEX { sensorIndex, humidityIndex }
+ ::= { humidityIdentificationTable 1 }
+
+HumidityIdentificationEntry ::= SEQUENCE {
+ humidityIndex
+ Integer32,
+ humidityUuid
+ OCTET STRING,
+ humidityConnectionType
+ ProbeConnectionType
+}
+
+humidityIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..2)
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "A unique value for each humidity probe measurement. Its value
+ ranges from 1 to sensorhumidityCount."
+ ::= { humidityIdentificationEntry 1 }
+
+humidityUuid OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique uuid value for each humidity."
+ ::= { humidityIdentificationEntry 2 }
+
+humidityConnectionType OBJECT-TYPE
+ SYNTAX ProbeConnectionType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Probe connection type with the sensor that monitors it."
+ ::= { humidityIdentificationEntry 3 }
+
+
+humidityConfigurationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HumidityConfigurationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of humidity probe configuration. The number of entries is
+ given by sensorhumidityCount."
+ ::= { humidity 2 }
+
+humidityConfigurationEntry OBJECT-TYPE
+ SYNTAX HumidityConfigurationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a humidity probe configuration."
+ INDEX { sensorIndex, humidityIndex }
+ ::= { humidityConfigurationTable 1 }
+
+HumidityConfigurationEntry ::= SEQUENCE {
+ humidityName
+ OCTET STRING,
+ humidityEnable
+ EnableType,
+ humidityOffset
+ Integer32,
+ humidityAlarmEnable
+ EnableType,
+ humidityThresholdLowWarning
+ Integer32,
+ humidityThresholdLowCritical
+ Integer32,
+ humidityThresholdHighWarning
+ Integer32,
+ humidityThresholdHighCritical
+ Integer32,
+ humidityThresholdHysteresis
+ Integer32,
+ humidityAlarmGracePeriod
+ Integer32
+}
+
+humidityName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The friendly name of the sensor humidity probe."
+ ::= { humidityConfigurationEntry 1 }
+
+humidityEnable OBJECT-TYPE
+ SYNTAX EnableType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the humidity acquired or not.
+ 0:disabled, 1:enabled"
+ ::= { humidityConfigurationEntry 2 }
+
+humidityOffset OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the offset (Minus or Plus) to be added to the acquired value
+ in order to correct the probe measurement error. in tenth of % units."
+ ::= { humidityConfigurationEntry 3 }
+
+humidityAlarmEnable OBJECT-TYPE
+ SYNTAX EnableType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the humidity alarm depending on the thresholds evaluated or not.
+ 0:disabled, 1:enabled"
+ ::= { humidityConfigurationEntry 4 }
+
+humidityThresholdLowWarning OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Low warning humidity threshold in tenth of % units."
+ ::= { humidityConfigurationEntry 5 }
+
+humidityThresholdLowCritical OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Low critical humidity threshold in tenth of % units."
+ ::= { humidityConfigurationEntry 6 }
+
+humidityThresholdHighWarning OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "High warning humidity threshold in tenth of % units."
+ ::= { humidityConfigurationEntry 7 }
+
+humidityThresholdHighCritical OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "High critical humidity threshold in tenth of % units."
+ ::= { humidityConfigurationEntry 8 }
+
+humidityThresholdHysteresis OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "humidity threshold hysteresis in tenth of % units."
+ ::= { humidityConfigurationEntry 9 }
+
+humidityAlarmGracePeriod OBJECT-TYPE
+ SYNTAX Integer32 (1..60)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The grace period the alarm triggers after the acquired value crosses
+ a trigger value (in seconds)."
+ ::= { humidityConfigurationEntry 10 }
+
+
+humidityMonitoringTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HumidityMonitoringEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of humidity probe monitoring. The number of entries is
+ given by sensorhumidityCount."
+ ::= { humidity 3 }
+
+humidityMonitoringEntry OBJECT-TYPE
+ SYNTAX HumidityMonitoringEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a humidity probe monitoring."
+ INDEX { sensorIndex, humidityIndex }
+ ::= { humidityMonitoringTable 1 }
+
+HumidityMonitoringEntry ::= SEQUENCE {
+ humidityAlarm
+ AlarmType,
+ humidityAlarmChangeSince
+ UnixTimeStamp,
+ humidityValue
+ Integer32,
+ humidityCommunicationStatus
+ CommunicationStatus,
+ humidityCommunicationStatusSince
+ UnixTimeStamp
+}
+
+humidityAlarm OBJECT-TYPE
+ SYNTAX AlarmType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Alarm set according to the realtime measure compared to the thresholds."
+ ::= { humidityMonitoringEntry 1 }
+
+humidityAlarmChangeSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the humidity alarm last change."
+ ::= { humidityMonitoringEntry 2 }
+
+humidityValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Realtime measured value after correction with the offset. in tenth of % units."
+ ::= { humidityMonitoringEntry 3 }
+
+humidityCommunicationStatus OBJECT-TYPE
+ SYNTAX CommunicationStatus
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates how the humidity probe is communicating or not."
+ ::= { humidityMonitoringEntry 4 }
+
+humidityCommunicationStatusSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the humidity communication status last change."
+ ::= { humidityMonitoringEntry 5 }
+
+
+humidityMonitoringMinMaxTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF HumidityMonitoringMinMaxEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of humidity probe monitoring Min and Max. The number of entries is
+ given by sensorhumidityCount."
+ ::= { humidity 4 }
+
+humidityMonitoringMinMaxEntry OBJECT-TYPE
+ SYNTAX HumidityMonitoringMinMaxEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a humidity probe monitoring Min and Max."
+ INDEX { sensorIndex, humidityIndex }
+ ::= { humidityMonitoringMinMaxTable 1 }
+
+HumidityMonitoringMinMaxEntry ::= SEQUENCE {
+ humidityMinValue
+ Integer32,
+ humidityMinValueSince
+ UnixTimeStamp,
+ humidityMaxValue
+ Integer32,
+ humidityMaxValueSince
+ UnixTimeStamp,
+ humidityResetMinMax
+ ResetCommandType
+}
+
+humidityMinValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Minimum value registered since the 1st connection of the sensor or the last reset.
+ in tenth of % units."
+ ::= { humidityMonitoringMinMaxEntry 1 }
+
+humidityMinValueSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the humidity min value last change."
+ ::= { humidityMonitoringMinMaxEntry 2 }
+
+humidityMaxValue OBJECT-TYPE
+ SYNTAX Integer32
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Maximum value registered since the 1st connection of the sensor or the last reset.
+ in tenth of % units."
+ ::= { humidityMonitoringMinMaxEntry 3 }
+
+humidityMaxValueSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the humidity max value last change."
+ ::= { humidityMonitoringMinMaxEntry 4 }
+
+humidityResetMinMax OBJECT-TYPE
+ SYNTAX ResetCommandType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Command that resets the min and max data with the current measure.
+ 0:None, 1:Reset"
+ ::= { humidityMonitoringMinMaxEntry 5 }
+
+
+humidityNotification OBJECT IDENTIFIER ::= { humidity 0 }
+
+notifyHumidityAlarm NOTIFICATION-TYPE
+ OBJECTS { sensorIndex,
+ humidityIndex,
+ humidityUuid,
+ humidityAlarm,
+ humidityAlarmChangeSince,
+ humidityValue }
+ STATUS current
+ DESCRIPTION
+ "Sent whenever the humidity alarm changes."
+ ::= { humidityNotification 1 }
+
+notifyHumidityCommunicationStatus NOTIFICATION-TYPE
+ OBJECTS { sensorIndex,
+ humidityIndex,
+ humidityUuid,
+ humidityCommunicationStatus,
+ humidityCommunicationStatusSince }
+ STATUS current
+ DESCRIPTION
+ "Sent whenever the humidity communication status changes.
+ Is not implemented when the probe is internal (see humidityConnectionType)."
+ ::= { humidityNotification 2 }
+
+-- -----------------------------------------------------------------------------
+
+
+digitalInputIdentificationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF DigitalInputIdentificationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of digital input probe measurements. The number of entries is
+ given by sensorDigitalInputCount."
+ ::= { digitalInput 1 }
+
+digitalInputIdentificationEntry OBJECT-TYPE
+ SYNTAX DigitalInputIdentificationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a digital input identification."
+ INDEX { sensorIndex, digitalInputIndex }
+ ::= { digitalInputIdentificationTable 1 }
+
+DigitalInputIdentificationEntry ::= SEQUENCE {
+ digitalInputIndex
+ Integer32,
+ digitalInputUuid
+ OCTET STRING,
+ digitalInputConnectionType
+ ProbeConnectionType
+}
+
+digitalInputIndex OBJECT-TYPE
+ SYNTAX Integer32 (1..2)
+ MAX-ACCESS accessible-for-notify
+ STATUS current
+ DESCRIPTION
+ "A unique value for each digital input probe measurement. Its value
+ ranges from 1 to sensorDigitalInputCount."
+ ::= { digitalInputIdentificationEntry 1 }
+
+digitalInputUuid OBJECT-TYPE
+ SYNTAX OCTET STRING
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "A unique uuid value for each digital Input."
+ ::= { digitalInputIdentificationEntry 2 }
+
+digitalInputConnectionType OBJECT-TYPE
+ SYNTAX ProbeConnectionType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Probe connection type with the sensor that monitors it."
+ ::= { digitalInputIdentificationEntry 3 }
+
+
+digitalInputConfigurationTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF DigitalInputConfigurationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of digital input probe configuration. The number of entries is
+ given by sensorDigitalInputCount."
+ ::= { digitalInput 2 }
+
+digitalInputConfigurationEntry OBJECT-TYPE
+ SYNTAX DigitalInputConfigurationEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a digital input probe configuration."
+ INDEX { sensorIndex, digitalInputIndex }
+ ::= { digitalInputConfigurationTable 1 }
+
+DigitalInputConfigurationEntry ::= SEQUENCE {
+ digitalInputName
+ OCTET STRING,
+ digitalInputEnable
+ EnableType,
+ digitalInputPolarity
+ PolarityType,
+ digitalInputAlarmEnable
+ EnableType,
+ digitalInputAlarmSeverity
+ AlarmSeverityType,
+ digitalInputAlarmGracePeriod
+ Integer32
+}
+
+digitalInputName OBJECT-TYPE
+ SYNTAX OCTET STRING (SIZE(1..31))
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The friendly name of the digital input probe."
+ ::= { digitalInputConfigurationEntry 1 }
+
+digitalInputEnable OBJECT-TYPE
+ SYNTAX EnableType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the digital input acquired or not.
+ 0:disabled, 1:enabled"
+ ::= { digitalInputConfigurationEntry 2 }
+
+digitalInputPolarity OBJECT-TYPE
+ SYNTAX PolarityType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the digitalInput polarity.
+ 0 : Normally opened, 1 : Normally closed"
+ ::= { digitalInputConfigurationEntry 3 }
+
+digitalInputAlarmEnable OBJECT-TYPE
+ SYNTAX EnableType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the digitalInput alarm depending on the polarity evaluated or not.
+ 0:disabled, 1:enabled"
+ ::= { digitalInputConfigurationEntry 4 }
+
+digitalInputAlarmSeverity OBJECT-TYPE
+ SYNTAX AlarmSeverityType
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "Configure the alarm severity."
+ ::= { digitalInputConfigurationEntry 5 }
+
+digitalInputAlarmGracePeriod OBJECT-TYPE
+ SYNTAX Integer32 (1..60)
+ MAX-ACCESS read-write
+ STATUS current
+ DESCRIPTION
+ "The delay the alarm triggers when the state change event occurs (in seconds)."
+ ::= { digitalInputConfigurationEntry 6 }
+
+
+digitalInputMonitoringTable OBJECT-TYPE
+ SYNTAX SEQUENCE OF DigitalInputMonitoringEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "A list of digital input probee monitoring. The number of entries is
+ given by sensorDigitalInputCount."
+ ::= { digitalInput 3 }
+
+digitalInputMonitoringEntry OBJECT-TYPE
+ SYNTAX DigitalInputMonitoringEntry
+ MAX-ACCESS not-accessible
+ STATUS current
+ DESCRIPTION
+ "An entry for a digital Input probe."
+ INDEX { sensorIndex, digitalInputIndex }
+ ::= { digitalInputMonitoringTable 1 }
+
+DigitalInputMonitoringEntry ::= SEQUENCE {
+ digitalInputAlarm
+ AlarmLevelType,
+ digitalInputAlarmChangeSince
+ UnixTimeStamp,
+ digitalInputState
+ Integer32,
+ digitalInputStateSince
+ UnixTimeStamp,
+ digitalInputCommunicationStatus
+ CommunicationStatus,
+ digitalInputCommunicationStatusSince
+ UnixTimeStamp
+}
+
+digitalInputAlarm OBJECT-TYPE
+ SYNTAX AlarmLevelType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Alarm set according to the polarity and alarm severity configuration."
+ ::= { digitalInputMonitoringEntry 1 }
+
+digitalInputAlarmChangeSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the digital input alarm last change."
+ ::= { digitalInputMonitoringEntry 2 }
+
+digitalInputState OBJECT-TYPE
+ SYNTAX StateType
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Measure of the digital input after applying the polarity configured.
+ 0 : Inactive, 1 : Active"
+ ::= { digitalInputMonitoringEntry 3 }
+
+digitalInputStateSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the digital input state last change."
+ ::= { digitalInputMonitoringEntry 4 }
+
+digitalInputCommunicationStatus OBJECT-TYPE
+ SYNTAX CommunicationStatus
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "Indicates how the digital input is communicating or not."
+ ::= { digitalInputMonitoringEntry 5 }
+
+digitalInputCommunicationStatusSince OBJECT-TYPE
+ SYNTAX UnixTimeStamp
+ MAX-ACCESS read-only
+ STATUS current
+ DESCRIPTION
+ "UTC time in seconds since 1970/01/01 dating the digital input communication status last change."
+ ::= { digitalInputMonitoringEntry 6 }
+
+
+digitalInputNotification OBJECT IDENTIFIER ::= { digitalInput 0 }
+
+notifyDigitalInputAlarm NOTIFICATION-TYPE
+ OBJECTS { sensorIndex,
+ digitalInputIndex,
+ digitalInputUuid,
+ digitalInputAlarm,
+ digitalInputAlarmChangeSince,
+ digitalInputState,
+ digitalInputStateSince }
+ STATUS current
+ DESCRIPTION
+ "Sent whenever the digital input alarm changes."
+ ::= { digitalInputNotification 1 }
+
+notifydigitalInputCommunicationStatus NOTIFICATION-TYPE
+ OBJECTS { sensorIndex,
+ digitalInputIndex,
+ digitalInputUuid,
+ digitalInputCommunicationStatus,
+ digitalInputCommunicationStatusSince }
+ STATUS current
+ DESCRIPTION
+ "Sent whenever the digital input communication status changes.
+ Is not implemented when the probe is internal (see digitalInputConnectionType)."
+ ::= { digitalInputNotification 2 }
+
+
+eatonSensorCompliances MODULE-COMPLIANCE
+ STATUS current
+ DESCRIPTION
+ "The requirements for conforming to the Sensor MIB."
+ MODULE
+ MANDATORY-GROUPS { sensorRequiredGroup }
+ GROUP sensorOptionalGroup
+ DESCRIPTION
+ "Different sensors will support a subset of the defined objects."
+ GROUP sensorNotifyGroup
+ DESCRIPTION
+ "Different sensors will support a subset of the defined notifications."
+ ::= { conformance 1 }
+
+objectGroups OBJECT IDENTIFIER ::= { conformance 2 }
+
+sensorRequiredGroup OBJECT-GROUP
+ OBJECTS { sensorCount,
+ sensorIndex,
+ sensorManufacturer,
+ sensorModel,
+ sensorPartNumber,
+ sensorSerialNumber,
+ sensorFirmwareVersion,
+ sensorName,
+ sensorStatus,
+ sensorStatusSince,
+ sensorTemperatureCount,
+ sensorHumidityCount,
+ sensorDigitalInputCount,
+ temperatureIndex,
+ temperatureName,
+ temperatureValue,
+ temperatureUnit,
+ humidityIndex,
+ humidityName,
+ humidityValue,
+ digitalInputIndex,
+ digitalInputName
+ }
+ STATUS current
+ DESCRIPTION
+ "These objects are required to conform to this MIB."
+ ::= { objectGroups 1 }
+
+sensorOptionalGroup OBJECT-GROUP
+ OBJECTS { sensorUuid,
+ sensorConnectionType,
+ sensorAddress,
+ sensorMonitoredBy,
+ sensorLocation,
+ sensorPosition,
+ sensorElevation,
+ sensorUElevation,
+ sensorAnalogInputCount,
+ temperatureUuid,
+ temperatureConnectionType,
+ temperatureEnable,
+ temperatureOffset,
+ temperatureAlarmEnable,
+ temperatureThresholdLowWarning,
+ temperatureThresholdLowCritical,
+ temperatureThresholdHighWarning,
+ temperatureThresholdHighCritical,
+ temperatureThresholdHysteresis,
+ temperatureAlarmGracePeriod,
+ temperatureAlarm,
+ temperatureAlarmChangeSince,
+ temperatureCommunicationStatus,
+ temperatureCommunicationStatusSince,
+ temperatureMinValue,
+ temperatureMinValueSince,
+ temperatureMaxValue,
+ temperatureMaxValueSince,
+ temperatureResetMinMax,
+ humidityUuid,
+ humidityConnectionType,
+ humidityEnable,
+ humidityOffset,
+ humidityAlarmEnable,
+ humidityThresholdLowWarning,
+ humidityThresholdLowCritical,
+ humidityThresholdHighWarning,
+ humidityThresholdHighCritical,
+ humidityThresholdHysteresis,
+ humidityAlarmGracePeriod,
+ humidityAlarm,
+ humidityAlarmChangeSince,
+ humidityCommunicationStatus,
+ humidityCommunicationStatusSince,
+ humidityMinValue,
+ humidityMinValueSince,
+ humidityMaxValue,
+ humidityMaxValueSince,
+ humidityResetMinMax,
+ digitalInputUuid,
+ digitalInputConnectionType,
+ digitalInputEnable,
+ digitalInputPolarity,
+ digitalInputAlarmEnable,
+ digitalInputAlarmSeverity,
+ digitalInputAlarmGracePeriod,
+ digitalInputState,
+ digitalInputStateSince,
+ digitalInputAlarm,
+ digitalInputAlarmChangeSince,
+ digitalInputCommunicationStatus,
+ digitalInputCommunicationStatusSince
+ }
+ STATUS current
+ DESCRIPTION
+ "These objects in this MIB are optional."
+ ::= { objectGroups 2 }
+
+sensorNotifyGroup NOTIFICATION-GROUP
+ NOTIFICATIONS { notifySensorStatus,
+ notifySensorCount,
+ notifyTemperatureAlarm,
+ notifyTemperatureCommunicationStatus,
+ notifyHumidityAlarm,
+ notifyHumidityCommunicationStatus,
+ notifyDigitalInputAlarm,
+ notifydigitalInputCommunicationStatus
+ }
+ STATUS current
+ DESCRIPTION
+ "These notifications will be supported depending on the features of the sensor."
+ ::= { objectGroups 3 }
+
+
+END