summaryrefslogtreecommitdiff
path: root/MIBS/avtech/ROOMALERT11E-MIB
diff options
context:
space:
mode:
authorDavid Leutgeb <david.leutgeb@mannundmouse.com>2023-12-05 12:25:34 +0100
committerDavid Leutgeb <david.leutgeb@mannundmouse.com>2023-12-05 12:25:34 +0100
commit98a672123c7872f6b9b75a9a2b6bb3aea504de6a (patch)
tree9b13bd7f563c3198047bd359195327cf28b3caf0 /MIBS/avtech/ROOMALERT11E-MIB
downloadmibs-main.tar.gz
mibs-main.zip
Initial commitHEADmain
Diffstat (limited to 'MIBS/avtech/ROOMALERT11E-MIB')
-rw-r--r--MIBS/avtech/ROOMALERT11E-MIB693
1 files changed, 693 insertions, 0 deletions
diff --git a/MIBS/avtech/ROOMALERT11E-MIB b/MIBS/avtech/ROOMALERT11E-MIB
new file mode 100644
index 0000000..8dc9f02
--- /dev/null
+++ b/MIBS/avtech/ROOMALERT11E-MIB
@@ -0,0 +1,693 @@
+--
+--defines ROOMALERT11E-MIB for SNMP agent extension of Room Alert 11E
+--Contents: Global Registration Module
+-- Room Alert OIDs - Enterprise 20916
+--Version: 1.1.3
+--Date: 9 January 2014
+--Developed By: AVTECH Software, Inc.
+
+--
+--Copyright (c) 2014 AVTECH Software, Inc.
+--
+
+ROOMALERT11E-MIB DEFINITIONS ::= BEGIN
+
+
+IMPORTS
+ enterprises, IpAddress, Counter, TimeTicks
+ FROM RFC1155-SMI
+ OBJECT-TYPE
+ FROM RFC-1212
+ TRAP-TYPE
+ FROM RFC-1215;
+
+
+avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
+products OBJECT IDENTIFIER ::= { avtech 1 }
+roomalert11E OBJECT IDENTIFIER ::= { products 3 }
+sensors OBJECT IDENTIFIER ::= { roomalert11E 1 }
+traps OBJECT IDENTIFIER ::= { roomalert11E 2 }
+thresholds OBJECT IDENTIFIER ::= { roomalert11E 3 }
+channel1 OBJECT IDENTIFIER ::= { sensors 1 }
+channel2 OBJECT IDENTIFIER ::= { sensors 2 }
+channel3 OBJECT IDENTIFIER ::= { sensors 3 }
+channel4 OBJECT IDENTIFIER ::= { sensors 4 }
+channels OBJECT IDENTIFIER ::= { thresholds 1 }
+channels1 OBJECT IDENTIFIER ::= { channels 1 }
+channels2 OBJECT IDENTIFIER ::= { channels 2 }
+channels3 OBJECT IDENTIFIER ::= { channels 3 }
+channels4 OBJECT IDENTIFIER ::= { channels 4 }
+
+-- Room Alert 11E MIB
+-- Parameters
+
+sensor1-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for internal switch sensor 1 (0 = OPEN, 1 = CLOSED)."
+::= { channel1 1 }
+
+sensor1-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for internal switch sensor 2 (0 = OPEN, 1 = CLOSED)."
+::= { channel1 2 }
+
+sensor1-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for internal switch sensor 3 (0 = OPEN, 1 = CLOSED)."
+::= { channel1 3 }
+
+sensor1-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for internal switch sensor 4 (0 = OPEN, 1 = CLOSED)."
+::= { channel1 4 }
+
+sensor1-5 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for internal switch sensor 5 (0 = OPEN, 1 = CLOSED)."
+::= { channel1 5 }
+
+sensor1-6 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for internal switch sensor 6 (0 = OPEN, 1 = CLOSED)."
+::= { channel1 6 }
+
+sensor1-7 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for internal switch sensor 7 (0 = OPEN, 1 = CLOSED)."
+::= { channel1 7 }
+
+sensor1-8 OBJECT-TYPE
+ SYNTAX INTEGER(0..1)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for internal switch sensor 8 (0 = OPEN, 1 = CLOSED)."
+::= { channel1 8 }
+
+switch-label-1 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 1"
+::= { channel1 9 }
+
+switch-label-2 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 2"
+::= { channel1 10 }
+
+switch-label-3 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 3"
+::= { channel1 11 }
+
+switch-label-4 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 4"
+::= { channel1 12 }
+
+switch-label-5 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 5"
+::= { channel1 13 }
+
+switch-label-6 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 6"
+::= { channel1 14 }
+
+switch-label-7 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 7"
+::= { channel1 15 }
+
+switch-label-8 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label for switch sensor 8"
+::= { channel1 16 }
+
+sensor2-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 2-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
+::= { channel2 1 }
+
+sensor2-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 2-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
+::= { channel2 2 }
+
+sensor2-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 2-3. If temp/humidity sensor is connected, value will be current %RH."
+::= { channel2 3 }
+
+sensor2-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 2-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
+::= { channel2 4 }
+
+sensor2-5 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 2-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
+::= { channel2 5 }
+
+sensor2-6-label OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label of this sensor"
+::= { channel2 6}
+
+sensor3-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 3-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
+::= { channel3 1 }
+
+sensor3-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 3-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
+::= { channel3 2 }
+
+sensor3-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 3-3. If temp/humidity sensor is connected, value will be current %RH."
+::= { channel3 3 }
+
+sensor3-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 3-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
+::= { channel3 4 }
+
+sensor3-5 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 3-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
+::= { channel3 5 }
+
+sensor3-6-label OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label of this sensor"
+::= { channel3 6}
+
+sensor4-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 4-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
+::= { channel4 1 }
+
+sensor4-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 4-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
+::= { channel4 2 }
+
+sensor4-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 4-3. If temp/humidity sensor is connected, value will be current %RH."
+::= { channel4 3 }
+
+sensor4-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 4-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
+::= { channel4 4 }
+
+sensor4-5 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The reading for sensor 4-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
+::= { channel4 5 }
+
+sensor4-6-label OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "The label of this sensor"
+::= { channel4 6}
+
+alarm1 OBJECT-TYPE
+ SYNTAX INTEGER(0..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm for sensor channel 1. The binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
+::= { traps 1 }
+
+alarm2 OBJECT-TYPE
+ SYNTAX INTEGER(0..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm for sensor channel 2. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
+::= { traps 2 }
+
+alarm3 OBJECT-TYPE
+ SYNTAX INTEGER(0..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm for sensor channel 3. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
+::= { traps 3 }
+
+alarm4 OBJECT-TYPE
+ SYNTAX INTEGER(0..255)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm for sensor channel 4. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
+::= { traps 4 }
+
+alarmMessage1 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm Message from sensor channel 1 (Internal)"
+::= { traps 5 }
+
+alarmMessage2 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm Message from sensor channel 2 (External)"
+::= { traps 6 }
+
+alarmMessage3 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm Message from sensor channel 3 (External)"
+::= { traps 7 }
+
+alarmMessage4 OBJECT-TYPE
+ SYNTAX OCTET STRING
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Alarm Message from sensor channel 4 (External)"
+::= { traps 8 }
+
+threshold1-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 1 defined for Channel 1"
+::= { channels1 1 }
+
+threshold1-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 2 defined for Channel 1"
+::= { channels1 2 }
+
+threshold1-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 3 defined for Channel 1"
+::= { channels1 3 }
+
+threshold1-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 4 defined for Channel 1"
+::= { channels1 4 }
+
+threshold1-5 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 5 defined for Channel 1"
+::= { channels1 5 }
+
+threshold1-6 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 6 defined for Channel 1"
+::= { channels1 6 }
+
+threshold1-7 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 7 defined for Channel 1"
+::= { channels1 7 }
+
+threshold1-8 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 8 defined for Channel 1"
+::= { channels1 8 }
+
+threshold2-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 1 defined for Channel 2"
+::= { channels2 1 }
+
+threshold2-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 2 defined for Channel 2"
+::= { channels2 2 }
+
+threshold2-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 3 defined for Channel 2"
+::= { channels2 3 }
+
+threshold2-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 4 defined for Channel 2"
+::= { channels2 4 }
+
+threshold3-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 1 defined for Channel 3"
+::= { channels3 1 }
+
+threshold3-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 2 defined for Channel 3"
+::= { channels3 2 }
+
+threshold3-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 3 defined for Channel 3"
+::= { channels3 3 }
+
+threshold3-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 4 defined for Channel 3"
+::= { channels3 4 }
+
+threshold4-1 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 1 defined for Channel 4"
+::= { channels4 1 }
+
+threshold4-2 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 2 defined for Channel 4"
+::= { channels4 2 }
+
+threshold4-3 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 3 defined for Channel 4"
+::= { channels4 3 }
+
+threshold4-4 OBJECT-TYPE
+ SYNTAX INTEGER(0..65535)
+ ACCESS read-only
+ STATUS mandatory
+ DESCRIPTION "Threshold 4 defined for Channel 4"
+::= { channels4 4 }
+
+
+-- ROOMALERT11E TRAPS
+
+tempAlarm1-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-1 }
+ DESCRIPTION "A tempAlarm1 trap signifies that the current
+ temperature on external sensor 1 is outside the
+ defined high or low threshold."
+::= 1
+
+room-alert-11E-SNMP-trap TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1,alarmMessage2,alarmMessage3,alarmMessage4 }
+ DESCRIPTION "A Room Alert 11E SNMP Trap indicates that an alarm
+ condition has occurred on the sensor inidcated
+ by the alarmMessage variable."
+::= 2
+
+tempAlarm2-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
+ DESCRIPTION "A tempAlarm2 trap signifies that the current
+ temperature on external sensor 2 is outside the
+ defined high or low threshold."
+::= 3
+
+tempClear2-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
+ DESCRIPTION "A tempClear2 trap signifies that the current
+ temperature on external sensor 2 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 4
+
+tempAlarm3-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
+ DESCRIPTION "A tempAlarm3 trap signifies that the current
+ temperature on external sensor 3 is outside the
+ defined high or low threshold."
+::= 5
+
+tempClear3-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
+ DESCRIPTION "A tempClear3 trap signifies that the current
+ temperature on external sensor 3 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 6
+
+humidityAlarm1-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
+ DESCRIPTION "A humidityAlarm1 trap signifies that the current
+ humidity on external sensor 1 is outside the
+ defined high or low threshold."
+::= 7
+
+humidityClear1-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
+ DESCRIPTION "A humidityClear1 trap signifies that the current
+ humidity on external sensor 1 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 8
+
+humidityAlarm2-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
+ DESCRIPTION "A humidityAlarm2 trap signifies that the current
+ humidity on external sensor 2 is outside the
+ defined high or low threshold."
+::= 9
+
+humidityClear2-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
+ DESCRIPTION "A humidityClear2 trap signifies that the current
+ humidity on external sensor 2 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 10
+
+humidityAlarm3-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
+ DESCRIPTION "A humidityAlarm3 trap signifies that the current
+ humidity on external sensor 3 is outside the
+ defined high or low threshold."
+::= 11
+
+humidityClear3-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
+ DESCRIPTION "A humidityClear3 trap signifies that the current
+ humidity on external sensor 3 has returned to
+ a normal condition and is within the defined
+ high or low threshold."
+::= 12
+
+switchAlarm1-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
+ DESCRIPTION "A switchAlarm1 trap signifies that switch sensor 1
+ is in an alarm state."
+::= 13
+
+switchClear1-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
+ DESCRIPTION "A switchClear1 trap signifies that the switch sensor 1
+ has returned to a normal state."
+::= 14
+
+switchAlarm2-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
+ DESCRIPTION "A switchAlarm2 trap signifies that switch sensor 2
+ is in an alarm state."
+::= 15
+
+switchClear2-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
+ DESCRIPTION "A switchClear2 trap signifies that the switch sensor 2
+ has returned to a normal state."
+::= 16
+
+switchAlarm3-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
+ DESCRIPTION "A switchAlarm1 trap signifies that switch sensor 1
+ is in an alarm state."
+::= 17
+
+switchClear3-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
+ DESCRIPTION "A switchClear3 trap signifies that the switch sensor 3
+ has returned to a normal state."
+::= 18
+
+switchAlarm4-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
+ DESCRIPTION "A switchAlarm4 trap signifies that switch sensor 4
+ is in an alarm state."
+::= 19
+
+switchClear4-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
+ DESCRIPTION "A switchClear4 trap signifies that the switch sensor 4
+ has returned to a normal state."
+::= 20
+
+switchAlarm5-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
+ DESCRIPTION "A switchAlarm5 trap signifies that switch sensor 5
+ is in an alarm state."
+::= 21
+
+switchClear5-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
+ DESCRIPTION "A switchClear5 trap signifies that the switch sensor 5
+ has returned to a normal state."
+::= 22
+
+switchAlarm6-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
+ DESCRIPTION "A switchAlarm6 trap signifies that switch sensor 6
+ is in an alarm state."
+::= 23
+
+switchClear6-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
+ DESCRIPTION "A switchClear6 trap signifies that the switch sensor 6
+ has returned to a normal state."
+::= 24
+
+switchAlarm7-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
+ DESCRIPTION "A switchAlarm7 trap signifies that switch sensor 7
+ is in an alarm state."
+::= 25
+
+switchClear7-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
+ DESCRIPTION "A switchClear7 trap signifies that the switch sensor 7
+ has returned to a normal state."
+::= 26
+
+switchAlarm8-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
+ DESCRIPTION "A switchAlarm8 trap signifies that switch sensor 8
+ is in an alarm state."
+::= 27
+
+switchClear8-11e TRAP-TYPE
+ ENTERPRISE roomalert11E
+ VARIABLES { alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
+ DESCRIPTION "A switchClear8 trap signifies that the switch sensor 8
+ has returned to a normal state."
+::= 28
+END